AR No. ____ - Insulate Pipes Estimated Gas Energy Savings = **.* MMBtu/yr Estimated Gas Cost Savings = $***/yr Implementation Cost = $*** Simple Payback = *.* years Recommended Action Pipes located in the _______ area should be insulated to reduce heat losses and associated energy costs. Background Measurements of uninsulated pipes were taken during the site visit. This information is summarized in the table below. **** CUT & PASTE SPECIAL THE "SITE_SHEET" TABLE FROM THE INSPIPES.WB1 FILE HERE. **** ****INCLUDE ANY ADDITIONAL INFORMATION THAT MAY APPLY HERE *** Anticipated Savings The annual energy savings, ES, and energy cost savings, ECS, which could be realized by insulating pipes, can be estimated as follows: ( ) L UH ES HL b HL i EFF C ECS ES avoided cost of natural gas where HLb HLi L UH = = = = EFF = C = heat loss rate from bare pipe, Btu/h ft heat loss rate from insulated bare pipe, Btu/h ft pipe length, ft annual time during which pipes are heated and heat loss does not contribute to space heating, h/yr efficiency of the heat supply, no units (assumed to be 80%) conversion constant, 1,000,000 Btu/MMBtu The 3E Plus Insulation Thickness Computer Program developed by the North American Insulation Manufacturers Association is used to determine the heat loss from the bare and insulated pipes. The program determines the most economically attractive thickness of a selected insulation type and determines the heat loss from the pipe diameter, temperature, orientation, and other data related to the heating system and economic criteria used at this facility. A summary of the heating system, economic, and technical data used to determine the heat loss and most economically attractive insulation thickness specifically for this plant is presented in the table below. Summary of Heating System, Economic, and Technical Data TECHNICAL DATA Emittance of Outer Jacketing 0.10 Wind Speed 0 mph (indoors) Emittance of Existing Surface 0.80 Additional information on the calculation routine used in the program is provided at the end of this analysis. As an example calculation, the approximately ____ feet of uninsulated ___" diameter pipe in the _______ area was measured to be _____F during the site visit. This area is not heated for ___ hours annually (the unheated hours are used because the bare pipe provides some space heating to this area. Insulating the pipe will require some additional space heating.) From the 3E Plus program, the heat loss from the bare pipe is ___ Btu/h ft. The suggested insulation is ___" of ___________, which costs about $___/ft installed. The heat loss from the insulated pipe is ___ Btu/h. Thus, ES (**** ****)(***) (***) *,*** MMBt u/yr (***)( 1,000 ,000) ECS (*** MMBtu /yr)($***/ MMBtu) $***/yr The energy and cost savings for other bare pipes in this plant are listed in the table below. Summary of Energy and Cost Savings ***** CUT & PASTE SPECIAL "SAVINGS" TABLE FROM INSPIPES.WB1 **** As shown in the table, the total energy savings are ____ ccf/yr and the corresponding cost savings are $____/yr. Implementation Cost The installed cost of the insulation costs1 and simple payback are given in the table below. *** CUT & PASTE SPECIAL "IMPLEMENT" TABLE FROM INSPIPES.WB1 *** From the table, the total installation cost is $____. The cost savings of $_____/yr will pay for the implementation cost in about ___ years. Equations for Heat Loss From Pipes The 3E Plus Insulation Thickness Computer Program developed by the North American Insulation Manufacturers Association is used to determine the heat loss from the bare and insulated pipes. For pipes, the heat loss per unit of outside surface area is given by the following equation: 1 From R. W. Means Company, Inc., CostWorks 2000 Software, R. W. Means Company, Inc.: Kingston, Mass. Q t t P S A R RS with R r2 where Q/A tP tS R r1 r2 k Rs ho = = = = = = = = = r ln 2 r1 k and Rs 1 ho heat loss per unit of outside surface area, Btu/h ft2 process temperature, F outer surface temperature of insulation, F thermal resistance of insulation subsurface (conduction only), F ft2 h/Btu inner radius of insulation layer, ft outer radius of insulation layer, ft thermal conductivity of insulation subsurface, Btu/F ft h thermal resistance of insulation surface, F ft2 h/Btu surface heat loss coefficient, Btu/F ft2 h The surface resistance on the process temperature side is assumed to be small in comparison to the other resistances so that it can be neglected. The conduction resistance R is a function of temperature because k is temperature dependent. The surface resistance Rs represents the combined effects of radiation and convection heat loss. To calculate Rs, a variation of the Heilman equations is used. The equation is presented in ASTM C680. The combined convection and radiation heat loss from the pipe surface is calculated as follows: Q t tA S A Rs or Q 1 ε σ ( T S 4 - T A4 ) C A D where tA = T = ε = 0.2 1 1 ( TS TA 2 ) ambient temperature, F temperature in degrees Rankine, R = F + 460 outer surface emittance, no units 0.181 ( t S t A ) 0.266 1 1.277 V σ = C = D = V = Stefan-Boltzman constant, 1.714 x 10-9 Btu/ft2 h R4 constant depending on pipe orientation: C = 1.016 for horizontal pipe C = 1.235 for vertical pipe outside diameter of last insulation layer, inches (if D > 24", then D = 24") wind velocity, mph Since the surface resistance depends on surface temperature in a nonlinear manner, some type of iteration process is necessary. A back substitution method is used until the routine converges. Within the iteration loop, the thermal conductivity of the insulation material is continuously updated. For the bare pipe case, the resistance of the pipe walls is not neglected. Geometrical data for Schedule 40 pipe and the conductivity of steel are stored in the program. The resistance of the pipe walls is calculated and then used to iterate on the surface energy balance. The thermal conductivity k is calculated by integrating the thermal conductivity equation from the hot face temperature to the surface temperature. This requires an initial guess of the surface temperature. Each time the program iterates, the surface temperature is recalculated and a new thermal conductivity is calculated. Contact Information Vendor contact name: Vendor company name: Address: City: State: Phone: Fax: E-mail: Internet: Make and Model Number: Other Info: