Fire Mode application Confidential / Property of Danfoss Drives A/S Fire Mode application ◊ Fire Mode is for use in critical situations when the drive must perform the desired function ● Stairwell pressurization fans ● Ventilation fans in tunnels ◊ Drive operation ● In many cases, the drive will continue to run ● In cases like output short circuits, it may trip off and immediately restart VLT®HVAC Drive Confidential / Property of Danfoss Drives A/S November, 2007 Andrzej Sokolowski PLCO 2 Fire Mode Introduction ◊ Is activated by a digital input ◊ It ignores ● Other digital inputs ● External interlocks ● Input from the keypad ◊ It can be programmed to ignore or automatically reset ● Alarms ● Motor overload indications VLT®HVAC Drive Confidential / Property of Danfoss Drives A/S November, 2007 Andrzej Sokolowski PLCO 3 Fire Mode Display Indications ◊ When it is active, its display will show ● Fire Mode This is to indicate that Fire Mode is active and normal methods of drive control as disabled VLT®HVAC Drive Confidential / Property of Danfoss Drives A/S November, 2007 Andrzej Sokolowski PLCO 4 Fire Mode Display Indications ◊ After Fire mode has been turned off, the drive’s display will show either: ● Fire M Was Active or ● Fire M Limits Exceeded (If it ignored a critical alarm) ◊ This display is turned off by cycling power to the drive VLT®HVAC Drive Confidential / Property of Danfoss Drives A/S November, 2007 Andrzej Sokolowski PLCO 5 Fire Mode Introduction ◊ History of the operation of Fire Mode is stored in the Fire Mode Log (parameters 18-1*) ◊ This can be used when considering a warranty claim for a drive VLT®HVAC Drive Confidential / Property of Danfoss Drives A/S November, 2007 Andrzej Sokolowski PLCO 6 Action 24-00 Fire Mode Function [0]* [1] [2] [3] Disabled Enable – Run Enable – Run Reverse Enable – Coast VLT®HVAC Drive Confidential / Property of Danfoss Drives A/S November, 2007 Andrzej Sokolowski PLCO 7 Speed Control Method 24-01 Fire Mode Configuration [0] Open Loop [1]* Closed Loop VLT®HVAC Drive Confidential / Property of Danfoss Drives A/S November, 2007 Andrzej Sokolowski PLCO 8 Setting up speed control 24-02 Fire Mode Unit [0] None [1]* % … 24-03 Fire Mode Min Reference 24-04 Fire Mode Max Reference VLT®HVAC Drive Confidential / Property of Danfoss Drives A/S November, 2007 Andrzej Sokolowski PLCO 9 How Fast Should the Motor Run? 24-05 Fire Mode Preset Reference ● For Open Loop or Closed Loop operation 24-06 Fire Mode Reference Source ● For Open Loop or Closed Loop operation 24-07 Fire Mode Feedback Source ● For Closed Loop operation VLT®HVAC Drive Confidential / Property of Danfoss Drives A/S November, 2007 Andrzej Sokolowski PLCO 10 How should alarms be handled? 24-09 Fire Mode Alarm Handling [0] Trip + reset, Critical Alarms This is how Fire Mode is most often expected to operate Caution! Resetting a critical alarm during Fire Mode operation can impact the drive’s warranty [1]* Trip, Critical Alarms [2] Trip, All Alarms/Test VLT®HVAC Drive Confidential / Property of Danfoss Drives A/S November, 2007 Andrzej Sokolowski PLCO 11 What are Critical Alarms? ◊ 4 Mains Phase Loss ◊ 9 Inverter Overloaded ◊ 29 Drive Over Temperature ◊ 33 Inrush Fault ◊ 65 Control Card Over Temperature VLT®HVAC Drive Confidential / Property of Danfoss Drives A/S November, 2007 Andrzej Sokolowski PLCO 12 Bypass and Fire Mode 24-11 Bypass Delay Function 0 s* [0 – 600 s] The bypass function will wait this to see if the drive can recover from an alarm before activating the bypass relay VLT®HVAC Drive Confidential / Property of Danfoss Drives A/S November, 2007 Andrzej Sokolowski PLCO 13 Fire Mode – ventilation in garage BMS system VLT HVAC Drive Fire Mode Binary signal start/stop reference dirrection PLC Fire controler speed reference signal I/O CARD Mains 3x400V+PE Smoke Smoke Smoke sensor sensor sensor Zone 1 Zone 2 Zone 3 Contactor power off Contactor by-pass Sevice circuit breaker Pressure Transsmitter motor cable smoke fan VLT®HVAC Drive Confidential / Property of Danfoss Drives A/S November, 2007 Andrzej Sokolowski PLCO 14 Fire Mode – pressurization system (open loop) VLT HVAC Drive BMS system Fire Mode Binary signal start/stop reference dirrection PLC Frire controler speed reference signal I/O CARD Mains 3x400V+PE Smoke sensor Zone 1 Sevice circuit breaker Pressure Transsmitter Pressure Transsmitter motor cable wentylator napowietrzający VLT®HVAC Drive Confidential / Property of Danfoss Drives A/S November, 2007 Andrzej Sokolowski PLCO 15 Fire mode – pressurization system (clouse loop) BMS system VLT HVAC Drive Fildbus LON, BACnet, ModbusRTU Fire Mode Binary signal start/stop Analogue signals Mains 3x400V+PE Smoke sensor Pressure Transmitter Sevice circuit breaker Pressure Transsmitter motor cable air supply fan VLT®HVAC Drive Confidential / Property of Danfoss Drives A/S November, 2007 Andrzej Sokolowski PLCO 16