Division 7 – Thermal & Moisture Protection Flashing and Sheet Metal - 07600 Refer to Samet Corporation standard details and standards. Delivered material is of approved type, shape, gauge, metal, fabrication, priming, etc., as required, and all accessories are provided. Isolation provisions are made for dissimilar metals. Do not allow copper and aluminum flashings to be in contact with each other or with ferrous metal. Copper or aluminum flashings are to be fastened with non-ferrous nails or screws. Ferrous equipment bases are not to be set on copper flashings. Flanges embedded in plastic cement or asphalt is asphalt primed. Expansion joints are provided and installed as required or as specified. Note location of joints with respect to drains, downspouts, scuppers, corners, and other outlets. Observe methods of installation – nailing and cleating types for spacing and location; also soldering, welding, bolting, and riveting. Flashing does not interfere with structural requirements. Generally see that edge metal is lapped a minimum of 4 inches with 12 inches staggered nailing or fastening through the back flange unless otherwise required. All edge metal laps are coated with sealant on horizontal flange and vertical rise. Coating covers entire lap and is sandwiched between. Lengths are as long as practical or specified. Installation is coordinated with roofing and/or siding installation. Nailer or cant strip is provided for fastening flashing to roof deck; is of proper material, well secured, and allows venting if required or specified. Flashing is embedded and installed over roof membrane assembly with additional roofing membrane material. Method of anchoring lower edge of fascia is as required. Observe alignment, stiffness, etc. Gravel stops are to be flush with deck unless otherwise required. GUTTERS Gutters are adequately supported and allow for movement. Observe attachment size, type, location, and spacing of hangers and supports. Gutters are pitched if required and provide for drainage to outlets. Factors of settlement of wood and concrete cantilevered overhangs sometimes affect drainage pattern. Gutter joints are lapped in direction of flow. Expansion joints, concealed or standing, are provided midway between outlets or downspouts and/or as required. Scuppers are installed low enough not to dam water on roof. Overflow drains and scuppers if indicated or required by code are provided, located properly, i.e., low point of roof, are of size required and have correct inlet flow elevation. Accessories are provided if required – basket strainer, bird screens, covers, etc. Samet Corporation | Building Structures. Building Relationships. Division 7 – Thermal & Moisture Protection Flashing and Sheet Metal - 07600 DOWNSPOUTS Lengths are as long as practical and in accordance with specifications. Slip joints in direction of flow or allowance for movement is provided. Hangers or straps as required are provided. Spacing and location are as required or specified, and each section is supported. Connections of hangers does not damage finish wall material. Contact is not made with wall surfaces except for supports. Downspouts are installed plumb, without excessive lateral or angled joints, unless indicated or if required to conduct drainage. Special items are furnished: heads, scuppers, linings, etc. Downspouts that are indicated to terminate in drainage lines are nearly fitted and are cleaned and free of building debris or other materials. BASE AND CAP FLASHINGS Flashing is provided to suit conditions; cant, size, gauge, and fabrication. Base flashing extends up sufficiently; flange is properly secured and embedded at least 4 inches in roofing membrane and is installed similarly to gravel stops. Mopped felt or suitable membrane covering flashings or cleats is provided. It is good practice to cover as much as practical to avoid movement from temperature variations. Seams are lapped, locked, and soldered as required. Secure anchorage is provided for size, spacing, and fixing of cleats or other equipment mountings. Cap flashings are of shapes, sizes, and gauges required and are installed to provide secure anchorage, allow movement, and have sufficient laps and spacing. Counter flashing is extended sufficiently into masonry walls or into reglet and is securely anchored and caulked, if necessary. OTHER ROOF FLASHING Hip and ridge flashing and venting is provided as required. Check fabrication, size, gauge, anchorage, and lap. Observe caulking and painting procedures. Valley flashing is provided as required: open or closed, width, gauge, anchorage, and lap. Stepped flashing is provided as required: depth of insertion into wall, and length of material attached to deck and lap. Plastic cement or approved material is filled into joints between edges of shingles and flashing as required. Reglets are provided at required areas: observe the setting in concrete or masonry to assure firm anchorage. Reglets are protected to prevent deformation or filling during installation. Observe installation of sheet metal into reglets for tightness, weatherproofness, caulking, and lap. Samet Corporation | Building Structures. Building Relationships. Division 7 – Thermal & Moisture Protection Flashing and Sheet Metal - 07600 WALL AND THROUGH WALL FLASHING Locations for flashings fabrication and design are understood. Lap, turn up, location in wall, depth in masonry, length, etc., are as required. Sill flashing and pans extend full depth, are turned up, extend beyond horns or 4 inches, and are installed for proper drainage. MISCELLANEOUS Louvers and vents have adequate flanges and connections for anchorage and flashings are watertight against driving rains after installation. Insect screen, bird screen, shutters, etc., are providing as required. Review drawings and specifications for sheet metal items called for in one and not the other. Items such as skylight, roof, hatches, and fans may be suited for installation with or without flashing. Installation must meet manufacturers’ specifications when required. Plastic flashing is of type required and is installed in accordance with requirements. Sheet metal termite shields are provided as required. COMMENTS: Samet Corporation | Building Structures. Building Relationships.