CYPS Assets Team Advice to schools Legionella Management – Holiday Periods Schools are reminded that management arrangements should continue through school holiday periods, in particular: The weekly flush through and purge to a drain of the little used outlets in school. The monthly check of hot water temperatures at a selection of taps to check the temperature reaches 50ºC after 1 minute. The monthly check of cold water sentinel taps to check the temperature reaches 20ºC after 2 minutes. If further information is required, see Section 6 of the Legionella report, contact H2O Chemicals Ltd. for technical advice (tel: 0113 3060 400) or the Assets team (tel: 0114 273 5621).