Carleton University Joint Health and Safety Committee - Workplace Inspection Report Building: Area Inspected: Date: Mackenzie bldg # 10 Building 3rd, 4th and 5th Inspected by: floors. 20/Jan/11 Commenced at 0900hrs completed at 1100hrs Ron Brunet Area Supervisor or Designated Contact to Complete Department Room Hazard Mech. Aero. Eng. Wind Tunnel 3224 Fire extinguisher not inspected. Electrical cords running along floor at doorway. 3230B Bookshelf next to door not secured to wall. Graduate Students room Mech. & Aerospace Eng. 3230A 3254 Corrective Action Taken or Planned Date Date Done Inspect extinguisher and remove cords Initial March 2011 or cover over to prevent tripping. Secure bookshelf Done Soldering in room with no fume hood or proper ventilation. No fire extinguisher Remove soldering unit or place proper in room. Large amounts of electrical fume hood and ventilation. Have wiring and harnesses in room. Very assessment conducted for confined Lab is moving to the Canal Building small area not adequate for working in workspace with electrical and fire confined space could cause electrical issues. Place fire extinguisher in room. shocks or fires. Complaint from occupant air flow vent in hallway blowing particles or small debris in area. Adjacent to mechanical room 3260. Energy and Combustion Air Emissions lab 3284 ENG SOC Project 3338 Fire extinguisher not inspected. Leonardo’s Lounge 3342 Fire extinguishers not inspected. Milk cartons placed in hallway blocking escape route in emergency access. 3346 Occupant complaint of cold air draft coming from windows. May cause illness from direct contact to cold air. Graduate Students Recommended Corrective Action Check ventilation ducts for possible airborne matter or debris. Initial MY March 2011 MY March 2011 MY Dust coming from inside CCS’s POP room. Email has been sent for them to Mar 23, 2011 AC get the room cleaned. Fire extinguisher not inspected. Inspect extinguisher. Have eyewash Eyewash station not inspected and may station inspected and checked for any Done not be functioning properly. damage. March 2011 MY March 07, 2011 WH Inspect extinguishers and remove milk Inspected. OK. No milk cartons in cartons from hallway. hallway at this time. March 07, 2011 WH Inspected .Will return in warmer Block air from window or relocate work weather to repair condition of draft station. work order has been made for later date March 22/11 SW Inspect fire extinguisher. 1 Inspected. OK. 4370 Occupant complaint of room being too cold. Block draft from windows or relocate worker in room. Check heat ventilation Removed window and repaired in ceiling may not be functioning properly. March 22/11 SW WH Board room 4356 Electrical wires and cables running along floor to equipment secured with scotch tape. Not adequate enough. Secure properly or place cable cover over lines to prevent tripping. Inspected. OK. Wires placed in cable channel. March 07, 2011 Undergraduate Facility Systems & Computer Engineering 4324 Fire extinguisher not inspected. Inspect fire extinguisher. Checked and signed extinguisher tag Mar 31/2011 dl. Computer lab 4390 Fire Extinguisher not inspected. Inspect extinguisher. Inspected. OK. March 07, 2011 WH Possible injury by cable falling on Large electrical ground cable running someone and causing tripping or injury along floor from mechanical room 4495 in hallway. Remove or relocate by and over top of hallway doors. attaching to wall and securing to floor. Gound cable had been removed when May 2011 I inspected the area Fire extinguisher not inspected. Inspect fire extinguisher. Checked and signed extinguisher tag Mar 31/2011 dl. Boxes should be two high remove two boxes to prevent falling or injury. Inspect fire extinguisher. Boxes have been removed Apr 04/2011 dl. 4463 Boxes piled up four high on top of cabinet. Fire extinguisher not inspected. dl. Eng. Soc. 5324 Fire extinguisher not inspected. Inspect fire extinguisher. Eng. Soc. 5326 Fire extinguisher not inspected. Inspect Fire extinguisher. 4275 Fire Extinguisher not inspected. Inspect fire extinguisher. Checked and signed extinguisher tag Mar 31/2011 No fire extinguisher located in this area March 07, to inspect. 2011 March 07, Inspected. OK. 2011 Inspected by Khi Kong Chiv 11/3/11 Electronics 5124 Fire extinguisher not inspected. Inspect fire extinguisher. Innovative Organics Technologies Lab. 5190 4th Fl Hallway next to center stairwell Systems & Computer Eng. 4485 Storage Room 4466 Photonics Lab. AC WH WH BP Inspected by Khi Kong Chiv 11/3/11 BP S. Bruce sent request to R. Percival for new inspection tag; current one is full; Fire extinguisher not inspected. MSDS Inspect fire extinguisher. Update MSDS. request sent January 2011. January 2011 BP not updated. Tags delivered to new FSW as per BA (entered May 30th RP) 5177 Fire extinguisher not inspected. Inspect fire extinguisher. S. Bruce sent request to R. Percival for new inspection tag; current one is full; January 2011 BP request sent January 2011. Tags delivered to new FSW as per BA (entered May 30th RP) 2 Electronics Microwave lab. 5131 Fire extinguisher not inspected. Inspect fire extinguisher. CITO lab 5128 Fire extinguisher not inspected. Inspect fire extinguisher. Building: Area Inspected: Machining Lab Mackenzie bldg # 10 Building 2nd and 3rd floors 2463 2481 Inspected January 2011 but S. Bruce January 2011 BP mistakenly wrote 2010. Inspected January 2011 but S. Bruce January 2011 BP mistakenly wrote 2010. Date: 19/Jan/11 Commenced at 0900hrs completed at 1100hrs Inspected by: Inspect fire extinguishers once a month A check list has been developed for and eyewash stations once a week. the fire extinguishers and the eye wash Fire extinguisher and eye wash station Inspect extinguishers once a month Done not inspected regularly and eyewash stations weekly. Fire extinguishers and eye wash station not inspected regularly Modelling Lab 2460A Extinguishers and eyewash station not inspected regularly Inspect extinguishers once a month and eyewash stations weekly. Spray Booth 2464 Fire extinguisher not inspected regularly Inspect on monthly basis Mech. & Aero Eng. Metallography 2455 Book case not secured to wall Secure bookcase to prevent falling Metal Lab 2448 Fire extinguisher not inspected Inspect regularly once a month 2447 Fire extinguisher and eyewash to be inspected. Centrifuge out of date for inspection 2007. MSDS not updated. Inspect extinguisher monthly, eyewash station weekly, centrifuge yearly, and MSDS chemicals/ products to be current every three years. 2432 Centrifuge in room not inspected and not being used. Eyewash and fire extinguishers to be inspected. MSDS to be updated. Remove centrifuge or have it inspected. Inspect extinguishers and eyewash stations. Update MSDS. Mech. Aero. Structures 2360 MSDS not updated. Eyewash stations and extinguishers not inspected regularly. Drill press on table not secured. Update MSDS. Inspect extinguishers and eyewash stations. Secure drill press. UAV Room 2362 Fire extinguishers not inspected Advanced water and wastewater Engineering Lab Environmental Engineering Lab Ron Brunet Inspect once a month 3 A check list has been developed for the fire extinguishers and the eye wash A check list has been developed for the fire extinguishers 04/04/11 WZ March 2011 MY 04/04/11 WZ 04/04/11 Done March 2011 A check list has been developed for the fire extinguishers 04/04/11 Fire extinguishers inspected by FED, we have setup a log to check eyewash stations weekly, we are having our centrifuges inspected and if not being used, they will be tagged and properly stored until they are needed and inspected, MSDSs are being updated WZ MY WZ March 23 PV March 23 PV March 2011 MY March 2011 MY Done Done 2335 Bookcase behind door not secured to wall. MSDS not updated. Mech. Aero. Eng. Graduate students 2350 Electrical outlet on upper wall no cover Replace cover plate to prevent shock plate electrical wiring showing. or fire. Mech. & Aero. Eng. Patient Simulation 2328 Fire extinguisher not inspected. Inspect extinguisher and remove cable Computer cable running along floor at Done to prevent tripping. doorway entrance. Mech. Aero. Eng. Simulator Project Room 2324 Fire extinguisher not inspected. Too much clutter in room. Water Channel Room 2268 Secure bookcase. Update MSDS. Inspect extinguisher remove clutter or find proper storage. ME Lab Mech. & aero. Eng. Thermodynamics Lab Heat transfer room Sustainable building Energy Systems Heat pipe lab Metallography & Thermal Analysis Mech. & Aero. Eng. High Temp Materials Mech. & Aero. Eng. Wind Tunnel 2256 Fire extinguisher not inspected. Portable eyewash station not inspected. Fire extinguisher not inspected and bookcase not secured to wall. Fire extinguisher not inspected. 2230 2232 Fire extinguisher not inspected and MSDS not up to date. Inspect extinguisher and update MSDS. 2250 Fire extinguisher not inspected. Inspect extinguisher. Fire extinguisher not inspected and communications lines strung from light fixture to metal tank. Fire extinguisher not inspected. Fire extinguisher and eyewash station not inspected. Inspect extinguisher and replace cables correctly along wall with cable cover. Inspect extinguisher. Inspect extinguisher and eyewash station on regular basis. 2224 Fire extinguisher not inspected. Inspect extinguisher. 2140 Eyewash station and fire extinguisher not inspected. Inspect eyewash and fire extinguisher on regular basis. Machining Lab 2159 MSDS not updated. Fire extinguisher not inspected. Update MSDS and inspect fire extinguisher. 2260 Done March 2011 MY Done 02/03 AC March 2011 MY March 2011 MY March 2011 MY March 2011 MY March 2011 MY March 2011 MY March 2011 MY March 2011 MY March 2011 MY March 2011 MY March 2011 MY March 2011 MY March 2011 MY Fire extinguisher inspected – clutter issue will be resolved with the availability of new lab space in the Canal Building Inspect fire extinguisher and eye wash Done station on regular basis. Inspect extinguisher and secure bookcase. Inspect fire extinguisher. Done Done Done 2258 2233 2228 Done Done Done Done Done 4 Done Done Welding room & Wood shop Fluid Mechanics Room Done 2195 Fire extinguishers not inspected. Inspect extinguishers. 2180 Fire extinguisher not inspected. Inspect extinguishers. 2194 Bookcase not secured behind door. Secure bookcase to wall prevent tipping/falling. 2196 Occupant complaint of breaker tripping Check electric breaker boxes for with too much overload when kettles possible overloading and fire or and other items plugged in from electrical hazards. opposite rooms. Breakers checked and in good working order. Occupants should not May 5/11 overload breaker. Find alternative location for kettle. KG Mech. & Aero. Eng. Plasma Spray Coating Lab 2195 Fire extinguisher not inspected. Done MY Computer Support room 3170 MMO Lab 3166 3160 Mechanical Design lab 3149 Graduate Students room 3129 Computer Lab 3124 Inspect fire extinguisher. Done Done March 2011 MY March 2011 MY March 2011 MY March 2011 Place fire extinguisher in room and find No fire extinguisher in room. Too much suitable storage area for equipment not equipment and electrical hazards. in use. No fire extinguisher Place fire extinguisher in lab. Complaint from occupant water leaking Repair leakage to prevent possible from ceiling when it rains. No tiles on electrical issues on equipment or mold. ceiling where leaks are coming from. Equipment in the room was placed there temporarily due to delayed March 2011 opening of the Canal Building This is an office with 8 computers in it. March 2011 Investigated by Consultant via FMPCS - Repairs Coming 02/11 KM Fire extinguisher not inspected. Inspect extinguisher. Done March 2011 MY Replace electrical box covers and remove electrical cords or reposition along wall to prevent tripping. Done 02/03 AC Inspect extinguisher Done March 2011 MY Electrical outlet boxes on walls with no plate covers electrical wiring showing. Electrical cords running along floor by adjacent room Fire extinguisher not inspected. MY MY REPORT DISTRIBUTION (within two working days following workplace inspection) Area Supervisor or Designated Contact: Susan Murat Shall provide a written response outlining corrective action taken or planned to the Manager, Environmental Health and Safety within 21 calendar days. Manager, Maintenance Services: Kevin Gallinger Shall take corrective action for maintenance items on notification of hazard by Area Supervisor. Manager, Environmental Health and Safety: Stephanie Yourth For tracking response from Area Supervisor. JHSC Worker Member: Ron Brunet For tracking completion of JHSC workplace inspections. 5 February 2008 6