Question 1: [7marks] Objective: This question related to power system transformers A single-phase transformer rated 1.2kV/120V, 7.2kVA has the following winding parameters: r1=0.8Ω, x1=1.2Ω, r2=0.01Ω and x2=0.01Ω. Determine: a) The combination winding resistance and leakage reactance referred to the primary side. b) The values of the combined parameters referred to secondary side. c) The voltage regulation of the transformer when it is delivering 7.5 kVA to a load at 120V and 0.8 power factor lagging. Solution: a )The turn ratio a V 1 V2 1.2 103 10 120 Resistance referred to the primary side R1 r1 a 2 .r2 0.8 (102 0.01) 1.8 X 1 x1 a 2 .x2 1.2 (102 0.01) 2.2 R 1.8 b) Resistance referred to the secondry side R2 21 0.018 a 100 X 2.2 Reactance referred to the secondry side X 2 21 0.022 a 100 V2( NL ) V2( FL ) c) voltage regulation of the transformer is Regulation (%) V2( FL ) Reactance referred to the primary side Z1 ( R1 jX 1 ) 1.8 j 2.2 cos 1 (0.8) 36.9o I 2( FL ) a S2 7200 60 36.9o o V2 12036.9 I 2( FL ) I1( FL ) I1( FL ) I 2( FL ) a A 60 36.9o 6 36.9o 10 A a.V2( FL ) 10 120 1200V V1( FL ) a.V2( FL ) I1( FL ) .Z1 1200 6 36.9o (1.8 j 2.2) 1216.570.19o percentage Regulation Dr.Audih alfaoury V2( NL ) V2( FL ) V2( FL ) V1( FL ) V2( FL ) a 121.6.57 120 (%) (%) 1.38% 120 V2( FL ) Philadelphia university Question2: Objective: This question related to short module of TL a) [10marks] Find the ABCD constants of a π circuit having a 600Ωresistor for shunt branch al sending end, a 1kΩ resistor for the shunt branch at the receiving end and an 80Ω resistor for series branch. Solution: IL Is IR 80Ω Vs 1000Ω 600Ω VR Vs VR V VR (80 I L ) V I L I R I (1000 ) I R ( R ) 1000 V Vs VR (80 I L ) Vs VR (80 ( I R ( R )) 1000 80VR 1VR 80 I R 1VR 0.08VR 80 I R 1.08VR 80 I R 1000 from KCL Vs 1.08VR 80 I R and since A 1.08 and And for C and D from KCL Vs AVR BI R then; B 80 I s I L I 600 VR V V 1.08VR 80 I R ) ( s ) (I R R ) ( ) 1000 600 1000 600 (0.001 0.0018) VR (1 0.133) I R I s I L I 600 ( I R And since I s CVR DI R 0.0028VR 1.133I R C 0.0028 and b) D 1.133 The ABCD constant of a three phase short length of TL are: A D 0.936 j 0.016 0.9360.98o B 33.5 j138 14276.4o C (5.18 j 914) x106 S Dr.Audih alfaoury Philadelphia university The load at the receiving end is 50MW at 220kV with a power factor of 0.9 lagging. Find the magnitude of the sending end voltage and the voltage regulation. Assume the magnitude of the sending end voltage remains constant. Solution: P 50 106 IR 145.8 25.84o [A] 3 3.VLL .cos 3 220 10 0.9 cos 1 (0.9) 25.84o and since its lagging then the angle is negative,thus; I R 145.8 25.84o [ A] VLL 220 103 1270o kV and 3 3 Vs AVR BI R (0.9360.98o (1270o ) 103 ) ((14276.4o ) (145.8 25.84o )) VR (118,855 j 2,033) (13,153 j15,990) 1332337.77 o V or 133.237.77o kV Vs 3 3 133.23 230.8 kV VR ( nL ) Vs 3 A 230.8 246.5 kV 0.9361 (%)regulation VR ( nL ) VR (FL) VR (FL) .% 246.5 220 100 12% 220 Question 3: [6marks] Objective: This question related to TL inductance calculation Find the inductance in each side and total inductance for a circuit of a single-phase TL is composed of three solid 0.25cm radius wires and return circuit is composed of 0.5cm radius wires. The arrangement of conductors is showing in figure. Dr.Audih alfaoury Philadelphia university Solution: L Lx Ly GMD GMD 7 Lx 2 107 ln and L 2 10 ln y GMRy GMRx GMD 9 ( Dad Dae Daf ) ( Dbd Dbe Dbf ) (Dcd Dce Dcf 10.940m GMRx 9 ( Daa Dab Dac) ( Dba Dbb Dbc) ( Dca Dcb Dcc) 0.480 m GMRy 9 ( Ddd Dde Ddf ) ( Ded Dee Def ) ( Dfd Dfe Dff ) 0.606 m note Dnn r ' r for solid conductors and Dnn r for stranded conductors Daa Dbb Dcc 0.7788 (0.25 102 ) 1.947 103 m Ddd Dee Dff 0.7788 (0.5 102 ) 3.894 103 m GMD GMD 10.940 10.940 7 L Lx Ly 2 107 ln ln 2 10 ln ln 0.480 0.606 GMRx G M R y 1.2 106 ( H / m) Question4: Objective: This question related to capacitance of TL [10marks] A three phase transposed line is composed of ACSR Bobolink conductor per phase with flat horizontal spacing of 11 meters as in figure .The conductors have a diameter of 3.625 cm and GMR of 1.439cm. The line is to be placed by a three conductor bundle of ACSR Hawk conductor .The conductors have diameter of 2.1793cm and GMR of 0.8839cm .The new line will also have a flat horizontal configuration, but it is to be operated at higher voltage and therefore the phase spacing is increased to 14 m as measured from the center of the bundles as in figure .The spacing between the conductors in the bundle is 45cm .Determine the percentage change in the capacitance. Dr.Audih alfaoury Philadelphia university Solution: 11m a 11m b c The capacitance per unit length is 2 o ,( F / m) (We propose to define a capacitance C between GMD ln GMR each conductor and neutral as in figure). C From electromagnetic cours .l C Q l2 l V .l E.l l l .l 2 o r l b a l .dr 2 o r 2 o b a 1 dr r 2 o r ln b ra , ( F / m) GMD 3 Dab .Dbc .Dca 3 112 22 13.859m GMR=r (for single bundled stranding conductor), and since we have diameter of conductor is 3.625cm, then r d 3.625 1.8125 102 m 2 2 The capacitance per unit length of old conductors is 2 8.85 1012 5.5606 10 11 C 8.375 1012 F / m 6.63939 13.859 ln 2 1.8125 10 or C 8.375 1012 1000 8.375 109 F / km 0.008375 F / k m For new bundled stranded conductors with new spacing as in figure Bundled spacing 14m Dr.Audih alfaoury 14m 14m Philadelphia university 45cm The new GMD= 3 142 28 17.63889m and GMR for tree bundled stranded conductors is found by the following relation: GMRb3 3 r.d 2 Where r is radius of conductor and d is the spacing of bundled GMRb3 3 2.1793 452 13.01879 102 m 2 The new capacitance per unit length is: 2 o 2 8.85 1012 Cnew 1.1327766 1011 F / m GMD 17.63889 ln ln 2 3 13.01879 10 GMRb Or capacitance per unit length for new Cnew 1.1327766 1011 1000 1.1327766 108 F / k m or Cnew 0.01132766 F / k m The percentage change of capacitance when replacing conductor by using bundled is: percentage Cnew Cold 0.01132766 0.00837 .100% .100% 35.25% Cold 0.00837 Dr.Audih alfaoury Philadelphia university From above question we note: 2 o GMD ln( ) GMR for solid conductor GMR DS 0.7788 r C bundled stranded conductors GMR is : for one stranded conductors GMR Ds r for two stranded conductors GMR Ds 4 (r d ) 2 r d for three stranded conductors GMR Ds 9 (r d d )3 3 r d 2 for four stranded conductors GMR Ds 16 (r d d d 2) 4 1.09 4 r d 3 d distance between bundled conductor per phase is meter r conductor radius is meter Question5: Objective: This question related to symmetrical fault [10marks] A60-Hz generator is rated 500MVA,20kV with sub-transient reactance 0f 0.2pu.Supply a purely resistive load of 400MW at 20kV .The load is connected directly to generator terminals ,if all three phases of load are short-circuit simultaneously, find the initial symmetrical rms current in the generator in per unit on base of 500MVA and 20kV. Solution: I '' g Eg'' Z '' g where E g'' Vt I L .Z''L In per unit we chose 500MVA as power base and 20kV as voltage base (note always chose the source as power base and TL as voltage base since they are greater value) and we need to find the current IL in per unit. Dr.Audih alfaoury Philadelphia university I pu I actual I base P 3VLL cos S 3VLL and since the load is resistiv that means power factor is unity cos 1 and R is neglected Z '' jX '' I pu P 3VLL P 400 . 0.8 pu S 500 3VLL S and V pu Vactual 20000 1 pu Vbase 20000 E g'' Vt I L . jX '' 10o (0.8 j 0.2) 1 j0.16 pu I g'' Eg'' jX '' 1 j0.16 0.8 j 0.5 pu j 0.2 or I g'' 0.82 0.52 5.06 pu (optional ) I g'' (actual ) I g'' ( pu ) I g'' (base) 5.06 ( Dr.Audih alfaoury 500 106 ) 5.06 14433.7 73.0348kA 3 20 103 Philadelphia university