SECTION 227000 SOLAR HOT WATER SYSTEM 1.1 GENERAL A. Submittals: Product Data, Shop Drawings, and Samples for each item specified. 1.2 PRODUCTS A. COLLECTORS Collectors: Frame and Battens – Extruded aluminum frame and battens with architectural bronze powder coated finish. Back Sheet – 0.019” stucco embossed aluminum sheet (bronze) pop-rivited to aluminum frame. Corner Bracket – Architectural aluminum angles inside with aircraft grade pin grip rivets. Insulation – Polyiscyanurate foam board insulation. Foil-faced glass fiber-reinforced, rigid foam thermax sheathing ( 1 ¼”in bed / ¾ “ in sidewalls ) Absober Plate – 100% copper absorber plate, high frequency force welded to create a crystalline homogeneous connection between the fin and riser tube. Thermafin or equal absorber coating – Thermafin Manufacturing selective crystal clear coating a = 0.96 E = 0.08 Glazing – Low iron tempered glass with a total solar energy transmission of 90%. Gasket, Grommets- UV durable EPDM, U-channel gasket with molded corners. Extruded silicone grommet 11/8 “ bore. Fasteners – 5056 aluminum rivets secure with backseat. Batten screws are 18-8 SS, 10-24x 3/8,” hex head screws black oxide coated. Working Pressure: 1.165 PSI Flow Rate: 0.5 to 1.8 GPM (recommended) Warranty 1.10 year – full with 30 year design life. Certifications1. Frame wall and mount shall be certified to withstand 180 mph winds. Mounting System 1. Flush mount system Collector Thermal Performance Rating 1. Megajoules per panel per day Durham Fire Station # 15 System Section 227000 Solar Hot Water a. Category 1. C (20 cC) b. Clear day (23 MJ/ M2d) – 42 c. Mildly cloudy (17 MJ/M2d) -29 d. Cloudy Day (11 MJ/M2d) -16 2. Thousands of BTU per Panel a. Category (Ti-Ta) – C (36 degrees F) b. Clear day (2000BTU /ft 2 d) - 40 c. 3. Mildly Cloudy (1500 BTU / ft 2d) – 27 d. . Cloudy Day (1000 BTU / ft 2 d) – 15 B. STORAGE TANK 1. 2. 3. 4. 5. 6. 7. Meets or exceeds ASHRAE 90.1b – 1999 Insulated Glass Lined Heavy –Gauge Steel Jacket with baked enamel finish Threaded openings Anode Rod Five – Year Warranty C. STAINLESS STEEL DRAINBACK TANK 1. Stainless steel construction from type 304 alloy 2. Seams and fittings to be TIG welded 3. Female connection fittings, NPT 4. Vertical sight gauge 5. Insulation – rigid foam insulation (poured and molded in place) 6. White ABS outer steel with ABS vacuum molded end caps 7. White polyethylene moldings around all fittings 8. Heat Exchangers – coil connections at top of tank, standard internal heat exchangers (copper). D. CONTROLLER 1. STECA TR 0301 U or equal E. CIRCULATORS Circulator shall be of standard high capacity output (compact design) with direct drive – low power consumption. Unit shall be self-lubricating with no mechanical seal. Unit shall be equipped with an anti-condensate baffle (ACB), internal flow check (IFC) priority zone relay and plumbing plug. Pre-wired timer control shall be by TACO or EQUAL. Materials: A. Sensor housing- bronze B. Cartridge – Steel C. Impeller- Stainless steel D. Shaft- Ceramic. End of Section Durham Fire Station # 15 System Section 227000 Solar Hot Water Durham Fire Station # 15 System Section 227000 Solar Hot Water