5003.1.1(1)T-F-ZUBIA-FCAC PUBLIC CODE CHANGE PROPOSAL FORM FOR PUBLIC PROPOSALS TO THE INTERNATIONAL CODES 2013 CODE DEVELOPMENT CYCLE Name: Adolf Zubia Date: November 26, 2012 Jurisdiction/Company: IAFC Fire and Life Safety Section Submitted on Behalf of: ICC Fire Code Action Committee Address: 3545 Cave Creek Manor City: Las Cruces State:NM Zip Code: 88011 Phone: 575-642-8589 Ext. Fax: E-mail address (see # 4 below): azumiamia@yahoo.com Code: IFC –12/13 Reference F-CAC ITEM 97 Code Tables Proposed for Revision: IFC Tables 5003.1.1(1), 5003.1.1(2) IBC Tables 307.1(1), 307.1(2) Proponent: Adolf Zubia. Chairman IAFC Fire and Life Safety Section, representing ICC Fire Code Action Committee Revise IFC Table 5003.1.1(1) as follows: 1. Editorial Revision: Replace all entries in table which state “Not Applicable” with “N/A”. 2. Editorial Revision: Replace all entries in table which state “Not Limited” with “NL”. 3. Editorial Revision: Add the following line at the bottom of the table above the Footnotes: “N/A = Not Applicable; NL = Not Limited; UD = Unclassified Detonable” 4. Further revise IFC Table 5003.1.1(1) as follows: MATERIAL Combustible dust Combustible fiber Combustible liquidc,i Consumer fireworks Cryogenic Flammable TABLE 5003.1.1(1) MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA OF HAZARDOUS MATERIALS POSING A PHYSICAL HAZARDa, j, m, n, p USE-OPEN GROUP WHEN STORAGEb USE-CLOSED SYSTEMSb SYSTEMSb THE MAXIMUM Gas CLASS Solid Liquid Gas Solid Liquid Solid Liquid ALLOWABLE (cubic pounds gallons (cubic feet pounds gallons pounds gallons QUANTITY IS feet at (cubic feet) (pounds) at NTP) (cubic feet) (pounds) (cubic feet) (pounds) EXCEEDED NTP) N/A H-2 Note q N/A N/A Note q N/A N/A Note q N/A H-3 (100) (1,000) N/A N/A (100) (1,000) N/A N/A (20) (200) N/A Loose Baledo II IIIA IIIB H-2 or H-3 H-2 or H-3 N/A N/A 120 330d, e 13,200e,f N/A N/A 120 330d 13,200f N/A N/A 30d 80d 3,300f 1.4G H-3 125d, e, l N/A N/A N/A N/A N/A N/A N/A N/A H-2 N/A 45d N/A N/A 45d N/A N/A 10d d, e d 5003.1.1(1)T-F-ZUBIA-FCAC Consumer fireworks Cryogenic Inert Cryogenic Oxidizing Explosives Flammable gas Flammable liquidc Flammable liquid, combination (1A, 1B, 1C) Flammable solid Inert gas Cryogenic inert Organic peroxide Oxidizer Oxidizing gas Pyrophoric Unstable (reactive) Water reactive 1.4G H-3 125d, e, l N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A NL N/A N/A NL N/A N/A N/A H-3 N/A 45d N/A N/A 45d N/A N/A 10d Division 1.1 Division 1.2 Division 1.3 Division 1.4 Division 1.4G Division 1.5 Division 1.6 Gaseous Liquefied 1A 1B and IC H-1 H-1 H-1 or H-2 H-3 H-3 H-1 H-1 1e, g 1e, g 5e, g 50e, g 125d,e,l 1e, g 1e, g N/A N/A N/A N/A N/A N/A N/A 1,000 d,e N/A (0.25) g (0.25) g (1) g N/A N/A (0.25) g N/A N/A N/A H-2 or H-3 N/A N/A N/A (0.25) g (0.25) g (1) g (50) g N/A (0.25) g N/A N/A (150) d,e 30 d 120 d 0.25 g 0.25 g 1g N/A N/A 0.25 g N/A N/A N/A N/A N/A N/A N/A N/A N/A 1,000 d,e N/A 0.25g 0.25 g 1g 50 g N/A 0.25 g N/A H-2 (1)e, g (1) e, g (5) e, g (50) e, g N/A (1) e, g N/A N/A (150)d,e 30d, e 120 d, e N/A N/A 10 d 30 d N/A H-2 or H-3 N/A 120 d, e, h N/A N/A 120 d, h N/A N/A 30 d, h N/A H-3 125 d, e N/A N/A 125 d N/A N/A 25 d N/A Gaseous Liquefied N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A NL NL NL N/A N/A N/A N/A N/A N/A NL NL NL N/A N/A N/A N/A N/A N/A UD I II III IV V 4 3k 2 1 Gaseous Liquefied N/A 4 3 2 1 3 2 1 H-1 H-2 H-3 H-3 N/A N/A H-1 H-2 or H-3 H-3 N/A 1e, g 5 d, e 50 d, e 125 d, e NL NL 1e, g 10 d, e 250 d, e 4,000 e, f N/A N/A 4 e, g 1 e, g 5 d, e 50 d, e NL 5 d, e 50 d, e NL (1) e, g (5) d, e (50) d, e (125) d, e NL NL (1) e, g (10) d, e (250) d, e (4,000)e, f N/A (150) d, e (4) e, g (1) e, g (5) d, e (50) d, e NL (5) d, e (50) d, e NL N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 1,500 d, e N/A 50 e, g 10 g 50 d, e 250 d, e NL N/A N/A N/A 0.25 g 1d 50 d 125 d NL NL 0.25 g 2d 250 d 4,000 f N/A N/A 1g 0.25 g 1d 50 d NL 5d 50 d NL (0.25) g (1) d (50) d (125) d NL NL (0.25) g (2) d (250) d (4,000) f N/A (150) d, e (1) g (0.25) g (1) d (50) d NL (5) d (50) d NL N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 1,500 d, e N/A 10 e, g 2 e, g 10 d, e 250 d, e NL N/A N/A N/A 0.25 g 1d 10 d 25 d NL NL 0.25 g 2d 50 d 1,000 f N/A N/A 0 0.25 g 1d 10 d NL 1d 10 d NL (0.25) g (1) d (10) d (25) d NL NL (0.25) g (2) d (50) d (1,000) f N/A N/A 0 (0.25) g (1) d (10) d NL (1) d (10) d NL H-3 H-2 H-1 H-1 or H-2 H-3 N/A H-2 H-3 N/A N/A For SI: 1 cubic foot = 0.02832 m3, 1 pound = 0.454 kg, 1 gallon = 3.785 L. N/A = Not Applicable; NL = Not Limited; UD = Unclassified Detonable a. For use of control areas, see Section 5003.8.3. b. The aggregate quantity in use and storage shall not exceed the quantity listed for storage. c. The quantities of alcoholic beverages in retail and wholesale sales occupancies shall not be limited providing the liquids are packaged in individual containers not exceeding 1.3 gallons. In retail and wholesale sales occupancies, the quantities of medicines, foodstuffs, consumer or industrial products, and cosmetics containing not more than 50 percent by volume of water-miscible liquids with the remainder of the solutions not being flammable shall not be limited, provided that such materials are packaged in individual containers not exceeding 1.3 gallons. d. Maximum allowable quantities shall be increased 100 percent in buildings equipped throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.1. Where Note e also applies, the increase for both notes shall be applied accumulatively. e. Maximum allowable quantities shall be increased 100 percent when stored in approved storage cabinets, day boxes, gas cabinets, exhausted enclosures, or in listed safety cans. Listed safety cans shall be in accordance with Section 5003.9.10. Where Note d also applies, the increase for both notes shall be applied accumulatively. f. Quantities shall not be limited in a building equipped throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.1. g. Allowed only in buildings equipped throughout with an approved automatic sprinkler system. 5003.1.1(1)T-F-ZUBIA-FCAC h. Containing not more than the maximum allowable quantity per control area of Class IA, Class IB or Class IC flammable liquids. i. The maximum allowable quantity shall not apply to fuel oil storage complying with Section 603.3.2. j. Quantities in parenthesis indicate quantity units in parenthesis at the head of each column. k. A maximum quantity of 200 pounds of solid or 20 gallons of liquid Class 3 oxidizers is allowed when such materials are necessary for maintenance purposes, operation or sanitation of equipment when the storage containers and the manner of storage are approved. l. Net weight of pyrotechnic composition of the fireworks. Where the net weight of the pyrotechnic composition of the fireworks is not known, 25 percent of the gross weight of the fireworks including packaging shall be used. m. For gallons of liquids, divide the amount in pounds by 10 in accordance with Section 5003.1.2. n. For storage and display quantities in Group M and storage quantities in Group S occupancies complying with Section 5003.11, see Table 5003.11.1. o. Densely-packed baled cotton that complies with the packing requirements of ISO 8115 shall not be included in this material class. p. The following shall not be included in determining the maximum allowable quantities: 1. Liquid or gaseous fuel in fuel tanks on vehicles. 2. Liquid or gaseous fuel in fuel tanks on motorized equipment operated in accordance with this code. 3. Gaseous fuels in piping systems and fixed appliances regulated by the International Fuel Gas Code. 4. Liquid fuels in piping systems and fixed appliances, regulated by the International Mechanical Code. q. Where manufactured, generated or used in such a manner that the concentration and conditions create a fire or explosion hazard based on information prepared in accordance with Section 104.7.2. 5. Revise IFC Table 5003.1.1(2) as follows: TABLE 5003.1.1(2) MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA OF HAZARDOUS MATERIAL POSING A HEALTH HAZARD a, b, c, f, h, i MATERIAL Solid pounds d,e, Corrosive 5,000 Highly toxic 10 Toxic 500 STORAGEb Liquid gallons Gas (pounds) d,e (cubic feet at NTP)d Gaseous 810e 500 Liquefied (150) Gaseous 20g (10) Liquefied (4)g Gaseous 810e (500) Liquefied (150)e 3 USE-CLOSED SYSTEMSb Solid pounds Liquid gallons Gas (cubic feet)d (pounds)d (cubic feet at NTP)d Gaseous 810e 5,000 500 Liquefied (150) Gaseous 20g 10 (10) Liquefied (4)g Gaseous 810e 500 (500) Liquefied (150)e USE-OPEN SYSTEMSb Solid pounds Liquid gallons (cubic feet)d (pounds)d 1,000 100 3 (3) 125 (125) For SI: 1 cubic foot = 0.02832 m , 1 pound = 0.454 kg, 1 gallon = 3.785 L. a. For use of control areas, see Section 5003.8.3. bc. In retail and wholesale sales occupancies, the quantities of medicines, foodstuffs, consumer or industrial products, and cosmetics, containing not more than 50 percent by volume of water-miscible liquids and with the remainder of the solutions not being flammable, shall not be limited, provided that such materials are packaged in individual containers not exceeding 1.3 gallons. cf. For storage and display quantities in Group M and storage quantities in Group S occupancies complying with Section 5003.1.1, see Table 5003.11.1. db. The aggregate quantity in use and storage shall not exceed the quantity listed for storage. ed. Maximum allowable quantities shall be increased 100 percent in buildings equipped throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.1. Where Note f also applies, the increase for both notes shall be applied accumulatively. fe. Maximum allowable quantities shall be increased 100 percent when stored in approved storage cabinets, gas cabinets or exhausted enclosures as specified in the International Fire Code. Where Note e also applies, the increase for both notes shall be applied accumulatively. g. Allowed only when stored in approved exhausted gas cabinets or exhausted enclosures as specified in the International Fire Code. h. Quantities in parenthesis indicate quantity units in parenthesis at the head of each column. i. For gallons of liquids, divide the amount in pounds by 10 in accordance with Section 5003.1.2. 5003.1.1(1)T-F-ZUBIA-FCAC 6. Revise IBC Table [F] 307.1(1) as follows: Delete the table and replace with Table 5003.1.1(1) from the IFC. 7. Revise Footnotes to IBC Table [F] 307.1(1) as follows: For SI: 1 cubic foot = 0.02832 m3, 1 pound = 0.454 kg, 1 gallon = 3.785 L. NL = Not Limited; N/A = Not Applicable; UD = Unclassified Detonable a. For use of control areas, see Section 414.2. b. The aggregate quantity in use and storage shall not exceed the quantity listed for storage. c. The quantities of alcoholic beverages in retail and wholesale sales occupancies shall not be limited provided the liquids are packaged in individual containers not exceeding 1.3 gallons. In retail and wholesale sales occupancies, the quantities of medicines, foodstuffs, consumer or industrial products, and cosmetics containing not more than 50 percent by volume of water-miscible liquids with the remainder of the solutions not being flammable, shall not be limited, provided that such materials are packaged in individual containers not exceeding 1.3 gallons. d. Maximum allowable quantities shall be increased 100 percent in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. Where Note e also applies, the increase for both notes shall be applied accumulatively. e. Maximum allowable quantities shall be increased 100 percent when stored in approved storage cabinets, day boxes, gas cabinets or exhausted enclosures or in listed safety cans in accordance with Section 5003.9.10 of the International Fire Code. Where Note d also applies, the increase for both notes shall be applied accumulatively. f. The permitted quantities Quantities shall not be limited in a building equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. g. Permitted Allowed only in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. h. Containing not more than the maximum allowable quantity per control area of Class IA, IB or IC flammable liquids. i. The maximum allowable quantity shall not apply to fuel oil storage complying with Section 603.3.2 of the International Fire Code. j. Quantities in parenthesis indicate quantity units in parenthesis at the head of each column. k. A maximum quantity of 200 pounds of solid or 20 gallons of liquid Class 3 oxidizers is allowed when such materials are necessary for maintenance purposes, operation or sanitation of equipment. Storage containers and the manner of storage shall be approved when the storage containers and the manner of storage are approved. l. Net weight of the pyrotechnic composition of the fireworks. Where the net weight of the pyrotechnic composition of the fireworks is not known, 25 percent of the gross weight of the fireworks, including packaging, shall be used. m.For gallons of liquids, divide the amount in pounds by 10 in accordance with Section 5003.1.2 of the International Fire Code. n. For storage and display quantities in Group M and storage quantities in Group S occupancies complying with Section 414.2.5, see Tables 414.2.5(1) and 414.2.5(2). o. Densely packed baled cotton that complies with the packing requirements of ISO 8115 shall not be included in this material class. p. The following shall not be included in determining the maximum allowable quantities: 1. Liquid or gaseous fuel in fuel tanks on vehicles. 2. Liquid or gaseous fuel in fuel tanks on motorized equipment operated in accordance with this codeInternational Fire Code. 3. Gaseous fuels in piping systems and fixed appliances regulated by the International Fuel Gas Code. 4. Liquid fuels in piping systems and fixed appliances regulated by the International Mechanical Code. q. Where manufactured, generated or used in such a manner that the concentration and conditions create a fire or explosion hazard based on information prepared in accordance with Section 414.1.3. 8. Revise IBC Table 307.1(2) as follows: Delete the table and replace with Table 5003.1.1(2) from the IFC. 5003.1.1(1)T-F-ZUBIA-FCAC 9. Revise Footnotes to IBC Table [F] 307.1(2) as follows: For SI: 1 cubic foot = 0.02832 m3, 1 pound = 0.454 kg, 1 gallon = 3.785 L. a. For use of control areas, see Section 414.2. bc. In retail and wholesale sales occupancies, the quantities of medicines, foodstuffs, consumer or industrial products, and cosmetics, containing not more than 50 percent by volume of water-miscible liquids and with the remainder of the solutions not being flammable, shall not be limited, provided that such materials are packaged in individual containers not exceeding 1.3 gallons. cf. For storage and display quantities in Group M and storage quantities in Group S occupancies complying with Section 414.2.5, see Tables 414.2.5(1) and 414.2.5(2). db. The aggregate quantity in use and storage shall not exceed the quantity listed for storage. ed. Maximum allowable quantities shall be increased 100 percent in buildings equipped throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.1. Where Note f also applies, the increase for both notes shall be applied accumulatively. fe. Maximum allowable quantities shall be increased 100 percent when stored in approved storage cabinets, gas cabinets or exhausted enclosures as specified in the International Fire Code. Where Note e also applies, the increase for both notes shall be applied accumulatively. g. Allowed only when stored in approved exhausted gas cabinets or exhausted enclosures as specified in the International Fire Code. h. Quantities in parenthesis indicate quantity units in parenthesis at the head of each column. i. For gallons of liquids, divide the amount in pounds by 10 in accordance with Section 5003.1.2 of the International Fire Code. REASON: Correlation between these sets of tables in the IFC and IBC is critical. There is no reason that the tables need to be formatted differently or contain different wording. This proposal does not change any requirements in the codes. It is editorial in nature and is designed to provide uniformity and consistency for the requirements found in the sets of tables. Parts 1 and 2 are editorial and only simplify the table. Part 3 is needed to correlate with revisions made in Parts 1 and 2. Part 4 alphabetizes the listings in the table and provides consistency in the header of the table. The revisions in the footnotes provide identical wording to the wording in the IBC. Part 5 restructures the footnotes to provide consistency for both the Health Hazard table and the Physical Hazard table. Part 6 duplicates the table from the IFC into the IBC. Part 7 provides identical wording for the footnotes in the IBC as is found in the IFC. Part 8 duplicates the table from the IFC into the IBC. Part 9 provides identical wording for the footnotes in the IBC as is found in the IFC. Cost Impact: The code change proposal will not increase the cost of construction. Public Hearing: Committee: AS Assembly: AM ASF D AMF DF