IFC –12/13 Reference F-CAC ITEM 97

advertisement
5003.1.1(1)T-F-ZUBIA-FCAC
PUBLIC CODE CHANGE PROPOSAL FORM
FOR PUBLIC PROPOSALS TO THE INTERNATIONAL CODES
2013 CODE DEVELOPMENT CYCLE
Name: Adolf Zubia
Date: November 26, 2012
Jurisdiction/Company: IAFC Fire and Life Safety Section
Submitted on Behalf of: ICC Fire Code Action Committee
Address: 3545 Cave Creek Manor
City: Las Cruces
State:NM Zip Code: 88011
Phone: 575-642-8589
Ext.
Fax:
E-mail address (see # 4 below): azumiamia@yahoo.com
Code: IFC –12/13
Reference F-CAC ITEM 97
Code Tables Proposed for Revision: IFC Tables 5003.1.1(1), 5003.1.1(2)
IBC Tables 307.1(1), 307.1(2)
Proponent: Adolf Zubia. Chairman IAFC Fire and Life Safety Section, representing ICC Fire Code Action
Committee
Revise IFC Table 5003.1.1(1) as follows:
1. Editorial Revision: Replace all entries in table which state “Not Applicable” with “N/A”.
2. Editorial Revision: Replace all entries in table which state “Not Limited” with “NL”.
3. Editorial Revision: Add the following line at the bottom of the table above the Footnotes:
“N/A = Not Applicable; NL = Not Limited; UD = Unclassified Detonable”
4. Further revise IFC Table 5003.1.1(1) as follows:
MATERIAL
Combustible
dust
Combustible
fiber
Combustible
liquidc,i
Consumer
fireworks
Cryogenic
Flammable
TABLE 5003.1.1(1)
MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA OF HAZARDOUS MATERIALS POSING A PHYSICAL
HAZARDa, j, m, n, p
USE-OPEN
GROUP WHEN
STORAGEb
USE-CLOSED SYSTEMSb
SYSTEMSb
THE
MAXIMUM
Gas
CLASS
Solid
Liquid
Gas
Solid
Liquid
Solid
Liquid
ALLOWABLE
(cubic
pounds
gallons
(cubic feet
pounds
gallons
pounds
gallons
QUANTITY IS
feet at
(cubic feet)
(pounds)
at NTP)
(cubic feet)
(pounds)
(cubic feet)
(pounds)
EXCEEDED
NTP)
N/A
H-2
Note q
N/A
N/A
Note q
N/A
N/A
Note q
N/A
H-3
(100)
(1,000)
N/A
N/A
(100)
(1,000)
N/A
N/A
(20)
(200)
N/A
Loose
Baledo
II
IIIA
IIIB
H-2 or H-3
H-2 or H-3
N/A
N/A
120
330d, e
13,200e,f
N/A
N/A
120
330d
13,200f
N/A
N/A
30d
80d
3,300f
1.4G
H-3
125d, e, l
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
H-2
N/A
45d
N/A
N/A
45d
N/A
N/A
10d
d, e
d
5003.1.1(1)T-F-ZUBIA-FCAC
Consumer
fireworks
Cryogenic
Inert
Cryogenic
Oxidizing
Explosives
Flammable
gas
Flammable
liquidc
Flammable
liquid,
combination
(1A, 1B, 1C)
Flammable
solid
Inert gas
Cryogenic
inert
Organic
peroxide
Oxidizer
Oxidizing gas
Pyrophoric
Unstable
(reactive)
Water reactive
1.4G
H-3
125d, e, l
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
NL
N/A
N/A
NL
N/A
N/A
N/A
H-3
N/A
45d
N/A
N/A
45d
N/A
N/A
10d
Division 1.1
Division 1.2
Division 1.3
Division 1.4
Division 1.4G
Division 1.5
Division 1.6
Gaseous
Liquefied
1A
1B and IC
H-1
H-1
H-1 or H-2
H-3
H-3
H-1
H-1
1e, g
1e, g
5e, g
50e, g
125d,e,l
1e, g
1e, g
N/A
N/A
N/A
N/A
N/A
N/A
N/A
1,000 d,e
N/A
(0.25) g
(0.25) g
(1) g
N/A
N/A
(0.25) g
N/A
N/A
N/A
H-2 or H-3
N/A
N/A
N/A
(0.25) g
(0.25) g
(1) g
(50) g
N/A
(0.25) g
N/A
N/A
(150) d,e
30 d
120 d
0.25 g
0.25 g
1g
N/A
N/A
0.25 g
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
1,000 d,e
N/A
0.25g
0.25 g
1g
50 g
N/A
0.25 g
N/A
H-2
(1)e, g
(1) e, g
(5) e, g
(50) e, g
N/A
(1) e, g
N/A
N/A
(150)d,e
30d, e
120 d, e
N/A
N/A
10 d
30 d
N/A
H-2 or H-3
N/A
120 d, e, h
N/A
N/A
120 d, h
N/A
N/A
30 d, h
N/A
H-3
125 d, e
N/A
N/A
125 d
N/A
N/A
25 d
N/A
Gaseous
Liquefied
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
NL
NL
NL
N/A
N/A
N/A
N/A
N/A
N/A
NL
NL
NL
N/A
N/A
N/A
N/A
N/A
N/A
UD
I
II
III
IV
V
4
3k
2
1
Gaseous
Liquefied
N/A
4
3
2
1
3
2
1
H-1
H-2
H-3
H-3
N/A
N/A
H-1
H-2 or H-3
H-3
N/A
1e, g
5 d, e
50 d, e
125 d, e
NL
NL
1e, g
10 d, e
250 d, e
4,000 e, f
N/A
N/A
4 e, g
1 e, g
5 d, e
50 d, e
NL
5 d, e
50 d, e
NL
(1) e, g
(5) d, e
(50) d, e
(125) d, e
NL
NL
(1) e, g
(10) d, e
(250) d, e
(4,000)e, f
N/A
(150) d, e
(4) e, g
(1) e, g
(5) d, e
(50) d, e
NL
(5) d, e
(50) d, e
NL
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
1,500 d, e
N/A
50 e, g
10 g
50 d, e
250 d, e
NL
N/A
N/A
N/A
0.25 g
1d
50 d
125 d
NL
NL
0.25 g
2d
250 d
4,000 f
N/A
N/A
1g
0.25 g
1d
50 d
NL
5d
50 d
NL
(0.25) g
(1) d
(50) d
(125) d
NL
NL
(0.25) g
(2) d
(250) d
(4,000) f
N/A
(150) d, e
(1) g
(0.25) g
(1) d
(50) d
NL
(5) d
(50) d
NL
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
1,500 d, e
N/A
10 e, g
2 e, g
10 d, e
250 d, e
NL
N/A
N/A
N/A
0.25 g
1d
10 d
25 d
NL
NL
0.25 g
2d
50 d
1,000 f
N/A
N/A
0
0.25 g
1d
10 d
NL
1d
10 d
NL
(0.25) g
(1) d
(10) d
(25) d
NL
NL
(0.25) g
(2) d
(50) d
(1,000) f
N/A
N/A
0
(0.25) g
(1) d
(10) d
NL
(1) d
(10) d
NL
H-3
H-2
H-1
H-1 or H-2
H-3
N/A
H-2
H-3
N/A
N/A
For SI: 1 cubic foot = 0.02832 m3, 1 pound = 0.454 kg, 1 gallon = 3.785 L.
N/A = Not Applicable; NL = Not Limited; UD = Unclassified Detonable
a. For use of control areas, see Section 5003.8.3.
b. The aggregate quantity in use and storage shall not exceed the quantity listed for storage.
c. The quantities of alcoholic beverages in retail and wholesale sales occupancies shall not be limited providing the
liquids are packaged in individual containers not exceeding 1.3 gallons. In retail and wholesale sales occupancies,
the quantities of medicines, foodstuffs, consumer or industrial products, and cosmetics containing not more than
50 percent by volume of water-miscible liquids with the remainder of the solutions not being flammable shall not
be limited, provided that such materials are packaged in individual containers not exceeding 1.3 gallons.
d. Maximum allowable quantities shall be increased 100 percent in buildings equipped throughout with an approved
automatic sprinkler system in accordance with Section 903.3.1.1. Where Note e also applies, the increase for both
notes shall be applied accumulatively.
e. Maximum allowable quantities shall be increased 100 percent when stored in approved storage cabinets, day
boxes, gas cabinets, exhausted enclosures, or in listed safety cans. Listed safety cans shall be in accordance with
Section 5003.9.10. Where Note d also applies, the increase for both notes shall be applied accumulatively.
f. Quantities shall not be limited in a building equipped throughout with an approved automatic sprinkler system in
accordance with Section 903.3.1.1.
g. Allowed only in buildings equipped throughout with an approved automatic sprinkler system.
5003.1.1(1)T-F-ZUBIA-FCAC
h. Containing not more than the maximum allowable quantity per control area of Class IA, Class IB or Class IC
flammable liquids.
i. The maximum allowable quantity shall not apply to fuel oil storage complying with Section 603.3.2.
j. Quantities in parenthesis indicate quantity units in parenthesis at the head of each column.
k. A maximum quantity of 200 pounds of solid or 20 gallons of liquid Class 3 oxidizers is allowed when such
materials are necessary for maintenance purposes, operation or sanitation of equipment when the storage
containers and the manner of storage are approved.
l. Net weight of pyrotechnic composition of the fireworks. Where the net weight of the pyrotechnic composition of
the fireworks is not known, 25 percent of the gross weight of the fireworks including packaging shall be used.
m. For gallons of liquids, divide the amount in pounds by 10 in accordance with Section 5003.1.2.
n. For storage and display quantities in Group M and storage quantities in Group S occupancies complying with
Section 5003.11, see Table 5003.11.1.
o. Densely-packed baled cotton that complies with the packing requirements of ISO 8115 shall not be included in
this material class.
p. The following shall not be included in determining the maximum allowable quantities:
1. Liquid or gaseous fuel in fuel tanks on vehicles.
2. Liquid or gaseous fuel in fuel tanks on motorized equipment operated in accordance with this code.
3. Gaseous fuels in piping systems and fixed appliances regulated by the International Fuel Gas Code.
4. Liquid fuels in piping systems and fixed appliances, regulated by the International Mechanical Code.
q. Where manufactured, generated or used in such a manner that the concentration and conditions create a fire or
explosion hazard based on information prepared in accordance with Section 104.7.2.
5. Revise IFC Table 5003.1.1(2) as follows:
TABLE 5003.1.1(2)
MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA OF HAZARDOUS MATERIAL POSING A HEALTH HAZARD a, b, c,
f, h, i
MATERIAL
Solid pounds
d,e,
Corrosive
5,000
Highly toxic
10
Toxic
500
STORAGEb
Liquid gallons
Gas
(pounds) d,e
(cubic feet at NTP)d
Gaseous 810e
500
Liquefied (150)
Gaseous 20g
(10)
Liquefied (4)g
Gaseous 810e
(500)
Liquefied (150)e
3
USE-CLOSED SYSTEMSb
Solid pounds
Liquid gallons
Gas
(cubic feet)d
(pounds)d
(cubic feet at NTP)d
Gaseous 810e
5,000
500
Liquefied (150)
Gaseous 20g
10
(10)
Liquefied (4)g
Gaseous 810e
500
(500)
Liquefied (150)e
USE-OPEN SYSTEMSb
Solid pounds
Liquid gallons
(cubic feet)d
(pounds)d
1,000
100
3
(3)
125
(125)
For SI: 1 cubic foot = 0.02832 m , 1 pound = 0.454 kg, 1 gallon = 3.785 L.
a. For use of control areas, see Section 5003.8.3.
bc. In retail and wholesale sales occupancies, the quantities of medicines, foodstuffs, consumer or industrial
products, and cosmetics, containing not more than 50 percent by volume of water-miscible liquids and with the
remainder of the solutions not being flammable, shall not be limited, provided that such materials are packaged in
individual containers not exceeding 1.3 gallons.
cf. For storage and display quantities in Group M and storage quantities in Group S occupancies complying with
Section 5003.1.1, see Table 5003.11.1.
db. The aggregate quantity in use and storage shall not exceed the quantity listed for storage.
ed. Maximum allowable quantities shall be increased 100 percent in buildings equipped throughout with an
approved automatic sprinkler system in accordance with Section 903.3.1.1. Where Note f also applies, the
increase for both notes shall be applied accumulatively.
fe. Maximum allowable quantities shall be increased 100 percent when stored in approved storage cabinets, gas
cabinets or exhausted enclosures as specified in the International Fire Code. Where Note e also applies, the
increase for both notes shall be applied accumulatively.
g. Allowed only when stored in approved exhausted gas cabinets or exhausted enclosures as specified in the
International Fire Code.
h. Quantities in parenthesis indicate quantity units in parenthesis at the head of each column.
i. For gallons of liquids, divide the amount in pounds by 10 in accordance with Section 5003.1.2.
5003.1.1(1)T-F-ZUBIA-FCAC
6. Revise IBC Table [F] 307.1(1) as follows:
Delete the table and replace with Table 5003.1.1(1) from the IFC.
7. Revise Footnotes to IBC Table [F] 307.1(1) as follows:
For SI: 1 cubic foot = 0.02832 m3, 1 pound = 0.454 kg, 1 gallon = 3.785 L.
NL = Not Limited; N/A = Not Applicable; UD = Unclassified Detonable
a. For use of control areas, see Section 414.2.
b. The aggregate quantity in use and storage shall not exceed the quantity listed for storage.
c. The quantities of alcoholic beverages in retail and wholesale sales occupancies shall not be limited provided the
liquids are packaged in individual containers not exceeding 1.3 gallons. In retail and wholesale sales occupancies,
the quantities of medicines, foodstuffs, consumer or industrial products, and cosmetics containing not more than
50 percent by volume of water-miscible liquids with the remainder of the solutions not being flammable, shall not
be limited, provided that such materials are packaged in individual containers not exceeding 1.3 gallons.
d. Maximum allowable quantities shall be increased 100 percent in buildings equipped throughout with an automatic
sprinkler system in accordance with Section 903.3.1.1. Where Note e also applies, the increase for both notes shall
be applied accumulatively.
e. Maximum allowable quantities shall be increased 100 percent when stored in approved storage cabinets, day
boxes, gas cabinets or exhausted enclosures or in listed safety cans in accordance with Section 5003.9.10 of the
International Fire Code. Where Note d also applies, the increase for both notes shall be applied accumulatively.
f. The permitted quantities Quantities shall not be limited in a building equipped throughout with an automatic
sprinkler system in accordance with Section 903.3.1.1.
g. Permitted Allowed only in buildings equipped throughout with an automatic sprinkler system in accordance with
Section 903.3.1.1.
h. Containing not more than the maximum allowable quantity per control area of Class IA, IB or IC flammable
liquids.
i. The maximum allowable quantity shall not apply to fuel oil storage complying with Section 603.3.2 of the
International Fire Code.
j. Quantities in parenthesis indicate quantity units in parenthesis at the head of each column.
k. A maximum quantity of 200 pounds of solid or 20 gallons of liquid Class 3 oxidizers is allowed when such
materials are necessary for maintenance purposes, operation or sanitation of equipment. Storage containers and
the manner of storage shall be approved when the storage containers and the manner of storage are approved.
l. Net weight of the pyrotechnic composition of the fireworks. Where the net weight of the pyrotechnic composition
of the fireworks is not known, 25 percent of the gross weight of the fireworks, including packaging, shall be used.
m.For gallons of liquids, divide the amount in pounds by 10 in accordance with Section 5003.1.2 of the
International Fire Code.
n. For storage and display quantities in Group M and storage quantities in Group S occupancies complying with
Section 414.2.5, see Tables 414.2.5(1) and 414.2.5(2).
o. Densely packed baled cotton that complies with the packing requirements of ISO 8115 shall not be included in
this material class.
p. The following shall not be included in determining the maximum allowable quantities:
1. Liquid or gaseous fuel in fuel tanks on vehicles.
2. Liquid or gaseous fuel in fuel tanks on motorized equipment operated in accordance with this codeInternational
Fire Code.
3. Gaseous fuels in piping systems and fixed appliances regulated by the International Fuel Gas Code.
4. Liquid fuels in piping systems and fixed appliances regulated by the International Mechanical Code.
q. Where manufactured, generated or used in such a manner that the concentration and conditions create a fire or
explosion hazard based on information prepared in accordance with Section 414.1.3.
8. Revise IBC Table 307.1(2) as follows:
Delete the table and replace with Table 5003.1.1(2) from the IFC.
5003.1.1(1)T-F-ZUBIA-FCAC
9. Revise Footnotes to IBC Table [F] 307.1(2) as follows:
For SI: 1 cubic foot = 0.02832 m3, 1 pound = 0.454 kg, 1 gallon = 3.785 L.
a. For use of control areas, see Section 414.2.
bc. In retail and wholesale sales occupancies, the quantities of medicines, foodstuffs, consumer or industrial
products, and cosmetics, containing not more than 50 percent by volume of water-miscible liquids and with the
remainder of the solutions not being flammable, shall not be limited, provided that such materials are packaged in
individual containers not exceeding 1.3 gallons.
cf. For storage and display quantities in Group M and storage quantities in Group S occupancies complying with
Section 414.2.5, see Tables 414.2.5(1) and 414.2.5(2).
db. The aggregate quantity in use and storage shall not exceed the quantity listed for storage.
ed. Maximum allowable quantities shall be increased 100 percent in buildings equipped throughout with an
approved automatic sprinkler system in accordance with Section 903.3.1.1. Where Note f also applies, the increase
for both notes shall be applied accumulatively.
fe. Maximum allowable quantities shall be increased 100 percent when stored in approved storage cabinets, gas
cabinets or exhausted enclosures as specified in the International Fire Code. Where Note e also applies, the increase
for both notes shall be applied accumulatively.
g. Allowed only when stored in approved exhausted gas cabinets or exhausted enclosures as specified in the
International Fire Code.
h. Quantities in parenthesis indicate quantity units in parenthesis at the head of each column.
i. For gallons of liquids, divide the amount in pounds by 10 in accordance with Section 5003.1.2 of the International
Fire Code.
REASON:
Correlation between these sets of tables in the IFC and IBC is critical. There is no reason that the
tables need to be formatted differently or contain different wording. This proposal does not
change any requirements in the codes. It is editorial in nature and is designed to provide
uniformity and consistency for the requirements found in the sets of tables.
Parts 1 and 2 are editorial and only simplify the table.
Part 3 is needed to correlate with revisions made in Parts 1 and 2.
Part 4 alphabetizes the listings in the table and provides consistency in the header of the table.
The revisions in the footnotes provide identical wording to the wording in the IBC.
Part 5 restructures the footnotes to provide consistency for both the Health Hazard table and the
Physical Hazard table.
Part 6 duplicates the table from the IFC into the IBC.
Part 7 provides identical wording for the footnotes in the IBC as is found in the IFC.
Part 8 duplicates the table from the IFC into the IBC.
Part 9 provides identical wording for the footnotes in the IBC as is found in the IFC.
Cost Impact: The code change proposal will not increase the cost of construction.
Public Hearing: Committee:
AS
Assembly:
AM
ASF
D
AMF
DF
Download