CAPACITY CALCULATION SEPTEMBER 2013 ISSUE 04 1.0 1.1 Introduction The figure used for room capacity is determined by two separate factors: The maximum number of persons it is designed to hold, this can be determined by dividing the area of the room (m2) by an occupancy factor (this varies depending on the use to which the room is to be put and is summarised in table 1 below). The number, width and location of the available exits allowing occupants to escape safely. 1.2 This document summarises relevant guidance from Building Bulletin 100 and DCLG Guidance for Fire Risk Assessment to enable you to calculate occupant capacity based upon floor space and the capacity of available exit routes. 2.0 Calculating Exit Capacity 2.1 Two calculations, occupancy factor and available exit capacity should both be undertaken and the calculation which arrives at the lowest number will give the maximum permitted capacity. 2.2 Occupancy Factors Table 1 Room/Area Occupant capacity based on floor space factor (m2 /person) 1 Assembly Hall/Dual purpose area 0.45 Dining Room, Restaurant Sports Hall (not used for assembly or examinations etc) Office 0.9 Staff Common Room 1.0 1 5.0 6.0 Figures from Building Bulletin 100 Education Health and Safety Policy and Procedures Page 1 of 8 September 2013 Issue 4 2.3 Seating and Gangways As far as practicable, seating should be in regular blocks, having gangways of uniform width and allowing free and ready access to the exits. see diagram 2 Gangways to be at least 1050mm wide. In general not more than 14 seats in a row with a gangway each end, Or not more than 7 in a row with a gangway at one end. Space between rows (back of one seat to front of seat behind) of at least 305mm. Where halls are used as examinations room there is generally a requirement from exam boards for 1.25 metres between chair centres. All exits to remain unobstructed. Standing and sitting in gangways or in front of any exit should not be permitted. Seated persons will take up more space than people standing and thus as an indication of likely capacity an occupancy factor of 1.0 m2 /person can be used where persons are seated on chairs in rows. 2.4 Widths of escape routes and exits Table 2 Number of fire exits needed Maximum number of persons Minimum number of escape routes/ exits 60 1 600 2 More than 600 3 Table 3 Exit door widths The following can be used to determine the general capacities of escape routes in normal risk premises Minimum width of doors on escape Maximum number of persons route (stated in mm) 750 100 1050 200 Over 1050mm wide then every additional 75mm increases capacity by 15 persons (or part thereof) e.g. 1200 mm 230 1500 mm 290 1800 mm 350 (see p 68 of Fire safety Risk assessment –Educational premises http://www.communities.gov.uk/publications/fire/firesafetyrisk6) Education Health and Safety Policy and Procedures Page 2 of 8 September 2013 Issue 4 The DCLG recommend the minimum width of an escape route in schools should be 1,050mm (1600mm in dead ends). Notes: 1. If only one exit is available from a room then the maximum capacity is 60 persons regardless of the width of the exit (see table 2), 60 people is also the limit for an exit where the door opens inwards. 2. When calculating the exit capacity then if a room has two or more exits it has to be assumed that a fire might prevent the occupants from using one of these exits. The remaining useable exit(s) need to be wide enough to allow all occupants to leave quickly. Therefore when deciding upon the total available exit capacity the largest exit from the room must be discounted. 3. An exit consisting of double doors is regarded as one exit. 4. If escape route doors are too close to one another and are likely to be simultaneously disabled by the same fire (e.g. within 45° of each other) then they should be classed as one exit and it may be necessary to discount them both from your calculation. ( diagram 1 ) 5. Escape routes that may be classed as ‘true alternatives’ should therefore be more than 45° apart when viewed from the furthest point in the room.(diagram 1 ) 6. A number of exits which discharge into a common area cannot be regarded as alternative to each other. 2.5 You also need to be aware of any specific licensing requirements and adhere to any capacity limits set by this. 2.6 If having undertaken your capacity calculation you have any queries please contact the health and safety team healthandsafety@hertfordshire.gov.uk . 2.7 There may be additional fire protection measures in place within the school which through use of your fire risk assessment and BS 9999 (Code of Practice for fire safety in the design, management and use of buildings) allow for some acceptable variations. Education Health and Safety Policy and Procedures Page 3 of 8 September 2013 Issue 4 Worked Examples Example 1 A school hall with a usable area of 210 M2 would have a maximum occupancy of 210 /0.45 = 466 people (from table 1) Total exit capacity The hall in question has 2 sets of double doors and 1 single door all at more than 45° apart and with widths as follows. 1 @ 2.1M 1 @ 1.8M 1 @ 0.75M The widest exit route must now be excluded from all subsequent calculations. This leaves 1 Door at 1.8M with a capacity of 350 people 1 Door at 0.75M with a capacity of 100 people (from table 3) Total exit capacity based on exit widths = 450 people NB Each of the remaining exit routes must be true alternatives at more than 45° apart. Final exits must be marked as fire exits. Therefore the maximum number of persons allowed in the hall in this case is the lowest calculated figure of 450. Example 2 Should the same hall as in example 1 be set out for a production with chairs in rows then assuming each person will need approximately 1 M2 Maximum occupancy 210 /1.0 = 210 people Total exit capacity 350 + 100 = 450 people (as previously calculated) As a starting point the likely capacity that can be accommodated in the hall in this case would be 210 as the lowest calculated figure. However practically the limiting factor is more likely to be ensuring the seating layout ensures that: Gangways of 1050mm wide with direct access to exits No seat is more than 7 seats from a gangway. Space of 305mm between rows (back of one seat to front of seat behind) All exits remain unobstructed. Education Health and Safety Policy and Procedures Page 4 of 8 September 2013 Issue 4 Education Health and Safety Policy and Procedures Page 5 of 8 September 2013 Issue 4 Example 3 Hall of 165M2 From table 1 the maximum occupancy = 165 / 0.45 366 persons Total exit capacity 2 exit routes are required if over 60 people are to occupy the hall, in this example 3 routes are available. However exits 2 and 3 are within 45 degrees, see diagram 1, and also discharge into a common area and thus must be regarded as one exit. Should a fire occur as in this example both exits 2 and 3 would be disabled and both must be discounted. Therefore the total capacity is based solely upon the width of exit 1 which is 1500mm wide and thus from table 3 gives a maximum capacity of 290 persons. In the event of people being seated in chairs in rows each person will need approximately 1 M2 (allowing for space taken by chair and a 305mm distance between rows) Max capacity of 165M2 / 1 = 165 persons There may be some flexibility in this figure as detailed in example 2. Education Health and Safety Policy and Procedures Page 6 of 8 September 2013 Issue 4 Diagram 1 Doors may be counted as 2 separate exits Doors must be counted as one exit Education Health and Safety Policy and Procedures Page 7 of 8 September 2013 Issue 4 Diagram 2 Education Health and Safety Policy and Procedures Page 8 of 8 September 2013 Issue 4