A 02.05.2007 IMPLEMENTATION OF REGULATION (EC) N° 842/2006 ON CERTAIN FLUORINATED GREENHOUSE GASES STANDARD LEAKAGE CHECKING REQUIREMENTS Stationary Refrigeration, Air-Conditioning and Heat Pump Applications According to Article 3 (7) Regulation (EC) 842/2006, the Regulatory Committee shall adopt these requirements by 4 July 2007. In order to prepare these decisions, the Commission contracted out a study (“The establishment of technical inspection requirements for refrigeration, air conditioning, heat pump equipment and fire protection systems which contain fluorinated greenhouse gases controlled by the Kyoto Protocol”, ICF Consulting, March 2006) and had consultations with experts from the sector After discussing with these stakeholders, the Commission services came to the conclusion that the following scheme could be a basis for the standard leakage checking requirements for the stationary refrigeration, air-conditioning and heat pump applications. STANDARD LEAKAGE CHECKING REQUIREMENTS Legal provisions Article 3 (2) requires operators to ensure that stationary refrigeration, air-conditioning and heat pumps applications containing fluorinated greenhouse gases are checked by certified personnel according to the following schedule: Applications containing 3 kg or more of F-gases (6 kg in the case of hermetically sealed systems) should be checked at least once every 12 months; Applications containing 30 kg or more of F-gases should be checked at least once every 6 months (12 months if there is a permanent leak detector); Applications containing 300 kg or more of F-gases should be checked at least once every 6 months and be fitted with a permanent leak detector. The checks should be carried out by direct or indirect methods. Direct and indirect methods should be defined in the standard leakage checking requirements to be established in pursuance to Article 3 (7). Direct checking for leakage is defined as a method which consists in moving a portable leak detector or similar device along the refrigeration circuit and principally around the components that present a risk for leakage. This leak detector will be adapted to the refrigerant in the system Indirect checking for leakage is defined as a method which requires a regular monitoring of the characteristics showing good containment of the refrigerant. Data on the operation of the application and of the condition of the refrigerant must be regularly taken and analysed and intervention procedures must be specified. Indirect checking will not be allowed if the refrigeration system is directly connected to a refrigerant container that automatically refills the refrigeration circuit. If the application is a cascade system, the parameters referred to above will be checked for each stage. Article 3(2) says checked for leakage" means that the equipment or system is examined for leakage using direct or indirect measuring methods, focusing on those parts of the equipment or system most likely to leak. The direct and indirect measuring methods of checking for leakage shall be specified in the standard inspection requirements Article 3(3) says "Operators of the applications referred to in paragraph 1, containing 300 kg or more of fluorinated greenhouse gases, shall install leakage detection systems. These leakage detection systems shall be inspected at least once every twelve months to ensure their proper functioning. In the case of fire protection systems installed before 4 July 2007, leakage detection systems shall be fitted by 4 July 2010 Article 3 (6) requires operators of applications with charge above 3 kg to maintain records on: Quantities and types of F-gases installed Quantities added Quantities recovered during servicing, maintenance and final disposal Identification of company or technician who performed the servicing and maintenance Dates and results of checks for leakage Relevant information specifically identifying the separate stationary equipment of applications containing more than 30 kg of F-gases. Article 3 (7) requires the Regulatory Committee to adopt standard leakage checking requirements by 4 July 2007. Objective The objective of setting standard checking requirements for refrigeration, airconditioning and heat pump applications containing fluorinated greenhouse gases controlled by the Kyoto Protocol is to ensure that the leakage of these gases from these applications is prevented and minimised Scope The standard leakage checking requirements should only apply to those categories of equipment for which the Regulation foresees regular checks for leakage: applications with charge above 3 kg (6 kg for hermetically sealed systems). 2 STANDARD CHECKING REQUIREMENTS FOR STAIONARY REFRIGERATION, AIRCONDITIONING AND HEAT PUMP APPLICATIONS SUBJECT TO THE PROVISIONS OF ARTICLE 3 OF REGULATION (EC) No 842/2006 3 Standard Leakage Checking Procedures These checking requirements shall apply to working and transitionally out-of-operation, stationary refrigeration, air conditioning and heat pump applications containing 3kg or more of fluorinated greenhouse gases. These checking procedures do not apply to hermetically sealed systems that are labelled as such which contain 6kg or less of fluorinated greenhouse gases. The refrigerant charge will be the standard refrigerant charge indicated in the manufacturer's technical specifications and/or indicated on the label. Without prejudice to the provisions of Article 7 of Regulation (EC) No. 842/2006, if the refrigerant charge is neither specified in the manufacturer's technical specifications nor on the label, the operator shall ensure that this is determined and specified in the logbook by certified personnel. The Fluorinated Greenhouse Gases are those set out in Annex I of Regulation (EC) No 842/2006 and any preparations as defined in Article 2 (5) of this Regulation used in any refrigeration circuit in refrigeration, air conditioning or heat-pump applications. Indirect methods for leak checking means analysing certain parameters of the refrigeration system, such as pressure, temperature, compressor current, liquid levels and recharge volume and the visual methods to identify the leaking points. Abnormalities indicated by the above parameters (deviations from normal operation conditions) may constitute a presumption of leak, loss of refrigerant. In this case, the existence and exact location of a possible leak shall be confirmed by a direct check using a mobile leak detector. Direct method means moving a portable leak detector along the circuit and principally around the components that present a risk for leakage. This leak detector will be adapted to the refrigerant in the system. A permanent leak detection system which is mandatory for stationary installations with a refrigerant charge of 300kg or more, is permanently monitoring the existence of F-Gases in the air from a possible leak. This detection system should be installed in the machinery room or – if no machinery room exists – as close as possible to the compressor. Any presumption of F-gas leakage indicated by the permanent leak detection system shall be followed by a check of the system. EN 378, EN 13313, EN 14276, EN 12178, EN 13136, EN 1861 and EN 12284 standards as well as national regulations could be taken into consideration. 4 Schematic overview of Standard Leakage Checking Procedure START OF PROCEDURE STEP 2 Visual and Manual Checking/ Identification of leaks STEP 1 Check Logbook of Application Are leaks present or suspected? YES STEP 3 Repair leaks END OF PROCEDURE STEP 5 Return Inspection Visit YES Has a leak been repaired? NO 5 STEP 4 Update Logbook NO Step 1 Check Logbook of Application Inspection of records to determine previous issues and reports. The personnel checking for leakage should pay special attention to relevant information on any repeating issues or problem areas. The specific attributes of the application and guidance contained in the operating manual of the equipment can be taken into account if relevant Step 2 Visual & Manual Checking Make a check of the application/equipment paying particular attention to: Abnormal noises or vibration, ice-formation, insufficient cooling capacity Visual corrosion, oil leaks and component or material damage in particular at possible leakage points – joints, gaskets, valves etc If used, check visual aids such as sight glasses or level indicators Visual inspection of safety switches, pressure switches, gauges and sensor connections Indications from a fixed installed leak detector Other signs that indicate refrigerant loss Following this general check of the system, the personnel checking the system shall continue with a more detailed leak check using direct leak checking methods or indirect leak checking methods or any combination thereof as follows: For direct leak checking methods: check the refrigeration circuit with gas detection devices such as portable, manual leak detectors For indirect leak checking methods: check possibility of leaks on the basis of an analysis of the operating parameters of the system. Indirect methods of checking will not be allowed if the refrigeration system is directly connected to a refrigerant container that automatically refills the refrigeration circuit. The manufacturer of the applications may give specific instructions for leakage checking and/or provide specific tools for leak checking in the manuals provided with each application Identification of Leaks Leaks may be identified by using the following methods or by an industry standard: Proprietary bubble solutions/soapsuds For direct leak methods: check the circuit and the components that represent a risk of leakage with gas detection devices adapted to the 6 refrigerant in the system such as portable manual leak detectors with a sensitivity of a minimum 5gr/yr and 10 parts per million (ppm) (measured according to EN 14624) or fixed installed leak detectors, in particular for applications where the design does not allow access by portable ones. Both portable and fixed leak detectors should have been checked during the last 12 months to ensure their proper functioning Sensitivity of portable leak detectors and area monitors are of at least 5g/yr and 10 ppm respectively. These sensitivities are measured according to EN 14624. UV detection fluid or suitable dye (may be subject to manufacturer's approval). This activity should only be undertaken by Cat. II certified personnel. The following areas should be systematically checked to find the leak: Joints Valves including stems Seals Parts of system subject to vibration Seals on replaceable driers and filters Connections to safety or operational devices The personnel undertaking the check may determine which areas should be given priority depending on the parts of the application that are most likely to leak and the history of the system (logbook and other documents). Where these measures do not identify a leak and the personnel checking the application still believe that a leak may be present it may be necessary to inspect other parts of the application. In that case, prior to pressure testing with Oxygen Free Nitrogen (OFN) or another suitable pressure testing gas, the refrigerant should be recovered from the whole system. This activity should only be undertaken by Cat. II certified personnel. Where these measures have identified a leakage and its location, the repair shall take place as soon as possible (Step 3). IF LEAKS ARE NOT PRESENT OR NOT SUSPECTED PROCEED TO STEP 4 IF LEAKS ARE PRESENT PROCEED TO STEP 3 Step 3 Repair Leaks (This activity should only be undertaken by Cat. II certified personnel.) It may be necessary to perform a pump-down or recovery prior to repairing. Repair leaks, where necessary leak test with Oxygen Free Nitrogen (OFN) or other suitable pressure testing and drying gas followed by evacuation and recharge, leakage7 test, re-commissioning. Alternatively, a leakage test using a vacuum can be used. Prior to pressure testing with dry nitrogen or another suitable pressure testing gas, the refrigerant should be recovered from the whole application. The cause of the leak shall as far as possible be identified in order to avoid recurrence Step 4 Update Logbook On completion of these steps the logbook must be filled in with the following details and signed: Date of check Inspector / Operatives Name /Certification ID Nr. Company Name / Certification ID Nr. Any Repairs carried out and date Details of type and weight of any refrigerants used or recovered for disposal / recycling in the last year/from the date of last inspections. Updated details of the leak checking procedure applied Step 5 Return Inspection Visit Where Step 3 was necessary an additional checking visit will be required within one month after repair covering those areas where leaks have been found and repaired or adjacent to these areas in case stress was applied during the repair. Standard Checking Requirements for newly commissioned equipment Leak Detection Procedure for installation of new equipment If appropriate, pressure test of whole application with inert gases according to technical specifications of manufacturer to check for possible leakage sources before filling with refrigerant Before commissioning and filling with refrigerant charge, after the pressure test, bring the pressure down to 1 Bar above atmospheric pressure and watch the manometer in combination with proprietary bubble solutions/soapsuds. 8