Copyright 2011 AIA MasterSpec Premium 02/11 PRODUCT MASTERSPEC LICENSED BY ARCOM TO BRISTOLITE DAYLIGHTING SYSTEMS, INC. This Product MasterSpec Section is licensed by ARCOM to Bristolite Daylighting Systems, Inc. ("Licensee"). This Product MasterSpec Section modifies the original MasterSpec text, and does not include the full content of the original MasterSpec Section. Revisions made to the original MasterSpec text are made solely by the Licensee and are not endorsed by, or representative of the opinions of, ARCOM or The American Institute of Architects (AIA). Neither AIA nor ARCOM are liable in any way for such revisions or for the use of this Product MasterSpec Section by any end user. A qualified design professional should review and edit the document to suit project requirements. For more information, contact Bristolite Daylighting Systems, Inc. 401 E Goetz Avenue, Santa Ana, CA 92707; Phone: (714) 540-8950; Fax: (714) 540-5415; Website: www.bristolite.com; Email: info@bristolite.com. For information about MasterSpec contact ARCOM at (800) 424-5080 or visit www.MasterSpec.com. SECTION 086300 - METAL-FRAMED SKYLIGHTS TIPS: To view non-printing Editor's Notes that provide guidance for editing, click on Masterworks/Single-File Formatting/Toggle/Editor's Notes. To read detailed research, technical information about products and materials, and coordination checklists, click on Masterworks/Supporting Information. PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. 1.2 Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. SUMMARY A. Section includes skylights with metal framing. B. Related Sections: 1. 2. Section 084433 "Sloped Glazing Assemblies" for glazed curtain walls in which the glazed panels are primarily on a sloped plane. Section 084513 "Structured-Polycarbonate-Panel Assemblies" for translucent structuredpolycarbonate-panel assemblies used as skylights. METAL-FRAMED SKYLIGHTS 086300 - 1 Copyright 2011 AIA MasterSpec Premium 02/11 PRODUCT MASTERSPEC LICENSED BY ARCOM TO BRISTOLITE DAYLIGHTING SYSTEMS, INC. 3. 4. 5. 1.3 Section 084523 "Fiberglass-Sandwich-Panel Assemblies" for translucent fiberglasssandwich-panel assemblies used as skylights. Section 086100 "Roof Windows" for operable and non-operable roof windows framed of wood, aluminum, or vinyl. Section 086200 "Unit Skylights" for skylights without framing except at the perimeter of the glazing. ACTION SUBMITTALS A. Product Data: For each type of product indicated. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for metal-framed skylights. B. LEED Submittals: 1. 2. C. Product Data for Credit IEQ 4.1: For sealants used inside the weatherproofing system, documentation including printed statement of VOC content. Laboratory Test Reports for Credit IEQ 4: For sealants used inside the weatherproofing system, documentation indicating that they comply with the testing and product requirements of the California Department of Health Services' "Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small-Scale Environmental Chambers." Shop Drawings: For metal-framed skylights. Include plans, elevations, sections, details, and attachments to other work. 1. 2. Include details of provisions for assembly expansion and contraction and for draining moisture within the assembly to the exterior. Include full-size isometric details of each vertical-to-horizontal intersection of assembly, showing the following: a. b. c. d. e. 3. Joinery including concealed welds. Anchorage. Expansion provisions. Glazing. Flashing and drainage. Include laboratory mockup Shop Drawings, prepared by a qualified preconstruction testing agency, showing details of laboratory mockup. a. Resubmit Shop Drawings with changes made to details of mockup to successfully complete preconstruction testing. D. Samples for Initial Selection: For units with factory-applied color finishes. E. Samples for Verification: For each type of exposed finish required, in manufacturer's standard sizes. METAL-FRAMED SKYLIGHTS 086300 - 2 Copyright 2011 AIA MasterSpec Premium 02/11 PRODUCT MASTERSPEC LICENSED BY ARCOM TO BRISTOLITE DAYLIGHTING SYSTEMS, INC. F. Fabrication Sample: Of each framing intersection of assemblies, made from 12-inch (305-mm) lengths of full-size components and showing details of the following: 1. 2. 3. 4. 5. G. 1.4 Joinery including concealed welds. Anchorage. Expansion provisions. Glazing. Flashing and drainage. Delegated-Design Submittal: For metal-framed skylights indicated to comply with performance requirements and design criteria, including analysis data signed and sealed by the qualified professional engineer responsible for their preparation. INFORMATIONAL SUBMITTALS A. Qualification Data: For qualified [Installer] [testing agency]. B. Welding certificates. C. Preconstruction Test Reports: Prepared by a qualified preconstruction testing agency. D. Compatibility and Adhesion Test Reports: For structural-sealant-glazed skylights, test reports from sealant manufacturer indicating that joint sealants have been tested for each material that will come in contact with sealants. E. Product Test Reports: Based on evaluation of comprehensive tests performed by a qualified testing agency, for metal-framed skylights. F. Field quality-control reports. G. Warranties: Sample of special warranties. 1.5 QUALITY ASSURANCE A. Installer Qualifications: Manufacturer's authorized representative who is trained and approved for installation of metal-framed skylights required for this Project. B. Testing Agency Qualifications: Qualified according to ASTM E 699 for testing indicated. C. Product Options: Information on Drawings and in Specifications establishes requirements for skylights' aesthetic effects and performance characteristics. Aesthetic effects are indicated by dimensions, arrangements, alignment, and profiles of components and assemblies as they relate to sightlines, to one another, and to adjoining construction. Performance characteristics are indicated by criteria subject to verification by one or more methods including testing conducted by an independent testing agency and in-service performance. METAL-FRAMED SKYLIGHTS 086300 - 3 Copyright 2011 AIA MasterSpec Premium 02/11 PRODUCT MASTERSPEC LICENSED BY ARCOM TO BRISTOLITE DAYLIGHTING SYSTEMS, INC. 1. Do not modify intended aesthetic effects, as judged solely by Architect, except with Architect's approval. If modifications are proposed, submit comprehensive explanatory data to Architect for review. D. Welding Qualifications: Qualify procedures and personnel according to AWS D1.2/D1.2M, "Structural Welding Code - Aluminum." E. Structural-Sealant Glazing: Comply with recommendations in ASTM C 1401, "Guide for Structural Sealant Glazing," for joint design and quality-control procedures. 1. 2. 3. F. Joint designs are reviewed and approved by structural-sealant manufacturer. Quality-control program development and reporting comply with ASTM C 1401 recommendations for material qualification procedures, preconstruction sealant-testing program, and procedures and intervals for fabrication and installation reviews and checks. Perform manufacturer's standard tests for compatibility and adhesion of sealants with each material that will come in contact with sealants. Provide metal-framed skylights that comply with test-performance requirements indicated, as evidenced by reports [of tests performed on manufacturer's standard assemblies] [based on Project-specific preconstruction testing] by a qualified independent testing agency. 1. 2. 3. 4. 5. Preconstruction Testing: [Owner will engage] [Engage] a qualified testing agency to perform preconstruction testing on laboratory mockups of assemblies. Build laboratory mockups at testing agency facility using personnel, materials, and methods of construction that will be used at Project site. Before performing testing on structural-sealant-glazed assemblies, remove at least one of every type of glazing lite from each laboratory mockup and replace them using reglazing procedures required for in-use skylight assembly. Notify Architect seven days in advance of the dates and times when laboratory mockups will be constructed. Preconstruction Testing Sequence: Test laboratory mockups according to AAMA 501, using the following sequence of tests: a. b. c. d. e. f. g. h. G. Structural-performance preloading at one-half of the specified maximum test load (ASTM E 330). Air infiltration (ASTM E 283). Water penetration under static pressure (ASTM E 331). Water penetration under dynamic pressure (AAMA 501.1). Structural performance at design load (ASTM E 330). Repeat air filtration (ASTM E 283). Repeat water penetration under static pressure (ASTM E 331). Structural performance at specified maximum test load (ASTM E 330). Mockups: Build mockups to verify selections made under sample submittals and to demonstrate aesthetic effects and set quality standards for fabrication and installation. 1. Build mockup of typical metal-framed skylights as shown on Drawings. METAL-FRAMED SKYLIGHTS 086300 - 4 Copyright 2011 AIA MasterSpec Premium 02/11 PRODUCT MASTERSPEC LICENSED BY ARCOM TO BRISTOLITE DAYLIGHTING SYSTEMS, INC. 2. 3. H. 1.6 Approval of mockups does not constitute approval of deviations from the Contract Documents contained in mockups unless Architect specifically approves such deviations in writing. Approved mockups may become part of the completed Work if undisturbed at time of Substantial Completion. Preinstallation Conference: Conduct conference at [Project site] <Insert location>. WARRANTY A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace components of metal-framed skylights that fail in materials or workmanship within specified warranty period. 1. Failures include, but are not limited to, the following: a. b. c. d. e. 2. B. Structural failures including, but not limited to, excessive deflection. Noise or vibration caused by thermal movements. Deterioration of metals[, metal finishes,] and other materials beyond normal weathering. Adhesive or cohesive sealant failures. Water leakage. Warranty Period: [Two] [Five] [10] <Insert number> years from date of Substantial Completion. Special Finish Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace components on which finishes fail within specified warranty period. Warranty does not include normal weathering. 1. 2. Failures include, but are not limited to, checking, crazing, peeling, chalking, and fading of finishes. Warranty Period: [Five] [10] [20] <Insert number> years from date of Substantial Completion. PART 2 - PRODUCTS 2.1 MANUFACTURERS A. Basis-of-Design Product: Subject to compliance with requirements, provide Bristolite Daylighting Systems, Inc.; Custom Metal Framed Skylight or comparable product by one of the following: 1. 2. 3. 4. Acralight International Skylights. Architectural Glazing Technologies. CPI Daylighting, Inc. Exarc Skylights, Inc. METAL-FRAMED SKYLIGHTS 086300 - 5 Copyright 2011 AIA MasterSpec Premium 02/11 PRODUCT MASTERSPEC LICENSED BY ARCOM TO BRISTOLITE DAYLIGHTING SYSTEMS, INC. 5. 6. 7. 8. 9. 10. 2.2 Kawneer North America; an Alcoa company. Major Industries, Inc.; Auburn Skylights Division. Schuco USA, LP. Super Sky Products, Inc. J. Sussman, Inc. <Insert manufacturer's name>. PERFORMANCE REQUIREMENTS A. General: Metal-framed skylights shall withstand the effects of the following without failure due to defective manufacture, fabrication, installation, or other defects in construction: 1. 2. 3. 4. 5. Structural loads. Thermal movements. Movements of supporting structure. Dimensional tolerances of support system and other adjacent construction. Failure includes, but is not limited to, the following: a. b. c. d. e. f. g. Deflection exceeding specified limits. Thermal stresses transferring to building structure. Framing members transferring stresses, including those caused by thermal and structural movements to glazing. Glazing-to-glazing contact. Noise or vibration created by wind and by thermal and structural movements. Loosening or weakening of fasteners, attachments, and other components. Sealant failure. B. Delegated Design: Design metal-framed skylights, including comprehensive engineering analysis by a qualified professional engineer, using performance requirements and design criteria indicated. C. Structural Loads: 1. Wind Loads:[ As indicated on Drawings.] a. b. c. 2. D. Basic Wind Speed: [85 mph (38 m/s)] [90 mph (40 m/s)] [100 mph (44 m/s)] [110 mph (49 m/s)] <Insert value>. Importance Factor: <Insert factor>. Exposure Category: [A] [B] [C] [D]. Seismic Loads: [As indicated on Drawings] <Insert loads>. Deflection of Framing Members: At design wind pressure, as follows: 1. Deflection Normal to Glazing Plane: Limited to [edge of glass in a direction perpendicular to glass plane not exceeding L/175 of the glass edge length for each individual glazing lite] [1/175 of clear span for spans up to 13 feet 6 inches (4.1 m) and to 1/240 of clear span plus 1/4 inch (6.35 mm) for spans more than 13 feet 6 METAL-FRAMED SKYLIGHTS 086300 - 6 Copyright 2011 AIA MasterSpec Premium 02/11 PRODUCT MASTERSPEC LICENSED BY ARCOM TO BRISTOLITE DAYLIGHTING SYSTEMS, INC. 2. inches (4.1 m)] <Insert deflection limit> or an amount that restricts edge deflection of individual glazing lites to 3/4 inch (19.1 mm), whichever is less. Deflection Parallel to Glazing Plane: Limited to [L/360 of clear span or 1/8 inch (3.2 mm), whichever is smaller] [amount not exceeding that which reduces glazing bite to less than 75 percent of design dimension and that which reduces edge clearance between framing members and glazing or other fixed components to less than 1/8 inch (3.2 mm)] <Insert deflection limit>. E. Lateral Bracing of Framing Members: Compression flanges of flexural members are laterally braced by cross members with minimum depth equal to 50 percent of flexural member that is braced. Glazing does not provide lateral support. F. Structural-Test Performance: Provide metal-framed skylights tested according to ASTM E 330, as follows: 1. 2. 3. G. When tested at positive and negative wind-load design pressures, assemblies do not evidence deflection exceeding specified limits. When tested at [150] <Insert number> percent of positive and negative wind-load design pressures, assemblies, including anchorage, do not evidence material failures, structural distress, and permanent deformation of main framing members exceeding [0.2] <Insert number> percent of span. Test Durations: As required by design wind velocity, but not less than [10] <Insert number> seconds. Windborne-Debris-Impact-Resistance Performance: Provide metal-framed skylights that pass missile-impact and cyclic-pressure tests when tested according to ASTM E 1886 and testing information in ASTM E 1996 for Wind [Zone 1] [Zone 2] [Zone 3] [Zone 4]. 1. 2. Large-Missile Test: For glazed openings located within 30 feet (9.1 m) of grade. Small-Missile Test: For glazed openings located more than 30 feet (9.1 m) above grade. H. Air Infiltration: Provide metal-framed skylights with maximum air leakage through fixed glazing and framing areas of [0.06 cfm/sq. ft. (0.03 L/s per sq. m)] <Insert value> of fixed wall area when tested according to ASTM E 283 at a minimum static-air-pressure difference of [1.57 lbf/sq. ft. (75 Pa)] [6.24 lbf/sq. ft. (300 Pa)] <Insert value>. I. Water Penetration under Static Pressure: Provide metal-framed skylights that do not evidence water penetration through fixed glazing and framing areas when tested according to ASTM E 331 at a minimum static-air-pressure difference of 20 percent of positive wind-load design pressure, but not less than [6.24 lbf/sq. ft. (300 Pa)] <Insert value>. J. Water Penetration under Dynamic Pressure: Provide metal-framed skylights that do not evidence water leakage through fixed glazing and framing areas when tested according to AAMA 501.1 under dynamic pressure equal to 20 percent of positive wind-load design pressure, but not less than [6.24 lbf/sq. ft. (300 Pa)] <Insert value>. 1. Maximum Water Leakage: [According to AAMA 501.1] [No uncontrolled water penetrating aluminum-framed systems or water appearing on systems' normally exposed interior surfaces from sources other than condensation]. Water leakage does METAL-FRAMED SKYLIGHTS 086300 - 7 Copyright 2011 AIA MasterSpec Premium 02/11 PRODUCT MASTERSPEC LICENSED BY ARCOM TO BRISTOLITE DAYLIGHTING SYSTEMS, INC. not include water controlled by flashing and gutters that is drained to exterior and water that cannot damage adjacent materials or finishes. K. Thermal Movements: Provide metal-framed skylights that allow for thermal movements resulting from the following maximum change (range) in ambient and surface temperatures. Base engineering calculations on surface temperatures of materials due to both solar heat gain and nighttime-sky heat loss. 1. Temperature Change (Range): [120 deg F (67 deg C), ambient; 180 deg F (100 deg C)] <Insert temperature range>, material surfaces. L. Condensation Resistance: Provide metal-framed skylights with fixed glazing and framing areas having condensation-resistance factor (CRF) of not less than [45] [53] <Insert number> when tested according to AAMA 1503. M. Structural Sealant: Capable of withstanding tensile and shear stresses imposed without failing adhesively or cohesively. When tested for preconstruction adhesion and compatibility, cohesive failure of sealant shall occur before adhesive failure. N. Energy Performance: Provide metal-framed skylights with performance properties specified, as indicated in manufacturer's published test data, based on procedures indicated below[ and certified and labeled according to NFRC]: 1. 2. 2.3 Thermal Transmittance (U-Factor): Fixed glazing and framing areas shall have U-factor of not more than [0.80 Btu/sq. ft. x h x deg F (4.54 W/sq. m x K)] [0.65 Btu/sq. ft. x h x deg F (3.69 W/sq. m x K)] <Insert value> as determined according to NFRC 100. Solar Heat Gain Coefficient: Fixed glazing and framing areas shall have a solar heat gain coefficient of no greater than [0.6] [0.7] <Insert value> as determined according to NFRC 200. FRAMING SYSTEMS A. Aluminum: Alloy and temper recommended in writing by manufacturer for type of use and finish indicated. 1. 2. 3. 4. 5. B. Pressure Caps: Manufacturer's standard aluminum components that mechanically retain glazing. 1. C. Sheet and Plate: ASTM B 209 (ASTM B 209M). Extruded Bars, Rods, Profiles, and Tubes: ASTM B 221 (ASTM B 221M). Extruded Structural Pipe and Tubes: ASTM B 429/B 429M. Structural Profiles: ASTM B 308/B 308M. Welding Rods and Bare Electrodes: AWS A5.10/A5.10M. Include snap-on aluminum trim that conceals fasteners. Brackets and Reinforcements: Manufacturer's standard high-strength aluminum with nonstaining, nonferrous shims for aligning skylight components. METAL-FRAMED SKYLIGHTS 086300 - 8 Copyright 2011 AIA MasterSpec Premium 02/11 PRODUCT MASTERSPEC LICENSED BY ARCOM TO BRISTOLITE DAYLIGHTING SYSTEMS, INC. D. Fasteners and Accessories: Manufacturer's standard, corrosion-resistant, nonstaining, nonbleeding fasteners and accessories compatible with adjacent materials. 1. 2. 3. 4. At pressure caps, use ASTM A 193/A 193M stainless-steel screws. Use self-locking devices where fasteners are subject to loosening or turning out from thermal and structural movements, wind loads, or vibration. Reinforce members as required to receive fastener threads. Use exposed fasteners with countersunk Phillips screw heads[, finished to match framing system] [, fabricated from Series 300 stainless steel]. E. Concrete and Masonry Inserts: Hot-dip galvanized cast-iron, malleable-iron, or steel inserts complying with ASTM A 123/A 123M or ASTM A 153/A 153M requirements. F. Anchor Bolts: ASTM A 307, Grade A (ASTM F 568M, Property Class 4.6), galvanized steel. G. Concealed Flashing: [Manufacturer's standard, corrosion-resistant, nonstaining, nonbleeding flashing compatible with adjacent materials] [Dead-soft, 0.018-inch- (0.457mm-) thick stainless steel, ASTM A 240/A 240M of type recommended in writing by manufacturer]. H. Exposed Flashing and Closures: Manufacturer's standard aluminum components not less than [0.030 inch (0.762 mm)] [0.040 inch (1.016 mm)] [0.060 inch (1.524 mm)] <Insert dimension> thick. I. Framing Gaskets: [Manufacturer's standard] <Insert requirements>. J. Framing Sealants: As [recommended in writing by manufacturer.] [specified in Section 079200 "Joint Sealants."] 1. 2. K. 2.4 Sealants used inside the weatherproofing system shall have a VOC content of [250] <Insert value> g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24). Sealants used inside the weatherproofing system shall comply with the testing and product requirements of the California Department of Health Services' "Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small-Scale Environmental Chambers." Corrosion-Resistant Coating: Cold-applied asphalt mastic, compounded for 15-mil (0.4-mm) dry film thickness per coat. Provide inert-type noncorrosive compound free of asbestos fibers, sulfur components, and other deleterious impurities. GLAZING A. Glazing: As specified in [Section 088000 "Glazing."] [Section 088400 "Plastic Glazing."] B. Spacers, Setting Blocks, and Gaskets: [Manufacturer's standard elastomeric types.] [As specified in Section 088000 "Glazing."] [As specified in Section 088400 "Plastic Glazing."] METAL-FRAMED SKYLIGHTS 086300 - 9 Copyright 2011 AIA MasterSpec Premium 02/11 PRODUCT MASTERSPEC LICENSED BY ARCOM TO BRISTOLITE DAYLIGHTING SYSTEMS, INC. C. Bond-Breaker Tape: [Manufacturer's standard tetrafluoroethylene-fluorocarbon or polyethylene material to which sealants will not develop adhesion] <Insert requirements>. D. Glazing Sealants: As [recommended in writing by manufacturer.] [specified in Section 079200 "Joint Sealants."] 1. 2. 3. Sealants used inside the weatherproofing system shall have a VOC content as indicated when calculated according to 40 CFR 59, Subpart D (EPA Method 24). Sealants used inside the weatherproofing system shall comply with the testing and product requirements of the California Department of Health Services' "Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small-Scale Environmental Chambers." Structural Sealant: ASTM C 1184, neutral-curing silicone formulation compatible with system components with which it comes in contact, specifically formulated and tested for use as structural sealant, and approved by structural-sealant manufacturer for use in metal-framed skylights indicated. a. b. 4. Weatherseal Sealant: ASTM C 920 for Type S, Grade NS, Class 25, Uses NT, G, A, and O; neutral-curing silicone formulation compatible with structural sealant and other components with which it comes in contact; and recommended in writing by structuraland weatherseal-sealant and metal-framed skylight manufacturers for this use. a. b. 2.5 VOC Content: [100] <Insert value> g/L or less. Color: [Black] [As selected by Architect from manufacturer's full range]. VOC Content: [250] <Insert value> g/L or less. Color: Matching structural sealant. FABRICATION A. Where practical, fit and assemble metal-framed skylights in manufacturer's plant. To ensure proper assembly at Project site, clearly identify work that cannot be permanently factory assembled before shipment. B. Fabricate aluminum components before finishing. C. Fabricate aluminum components that, when assembled, have the following characteristics: 1. 2. 3. 4. 5. Profiles that are sharp, straight, and free of defects or deformations. Accurately fitted joints with ends coped or mitered. Internal guttering systems or other means to drain water passing joints, condensation occurring within framing members, and moisture migrating within skylight to exterior. Physical and thermal isolation of glazing from framing members. Accommodations for thermal and mechanical movements of glazing and framing to maintain required glazing edge clearances. D. Fabricate aluminum sill closures with weep holes and for installation as continuous component. E. Reinforce aluminum components as required to receive fastener threads. METAL-FRAMED SKYLIGHTS 086300 - 10 Copyright 2011 AIA MasterSpec Premium 02/11 PRODUCT MASTERSPEC LICENSED BY ARCOM TO BRISTOLITE DAYLIGHTING SYSTEMS, INC. F. Weld aluminum components in concealed locations to greatest extent possible to minimize distortion or discoloration of finish. Remove weld spatter and welding oxides from exposed surfaces by descaling or grinding. G. Factory-Glazed, Metal-Framed Skylights: 1. 2. H. 2.6 Factory install glazing to comply with requirements in [Section 088000 "Glazing."] [Section 088400 "Plastic Glazing."] Prepare surfaces that will contact structural sealant according to structural-sealant manufacturer's written instructions to ensure compatibility and adhesion. Preparation includes, but is not limited to, cleaning and priming surfaces. After fabrication, clearly mark components to identify their locations in Project according to Shop Drawings. ALUMINUM FINISHES A. Clear Anodic Finish: AAMA 611, [AA-M12C22A41, Class I, 0.018 mm] [AA-M12C22A31, Class II, 0.010 mm] or thicker. B. Color Anodic Finish: AAMA 611, [AA-M12C22A42/A44, Class I, 0.018 mm] [AAM12C22A32/A34, Class II, 0.010 mm] or thicker. 1. 2. C. Baked-Enamel or Powder-Coat Finish: AAMA 2603 except with a minimum dry film thickness of 1.5 mils (0.04 mm). Comply with coating manufacturer's written instructions for cleaning, conversion coating, and applying and baking finish. 1. D. Color and Gloss: [As indicated by manufacturer's designations] [Match Architect's sample] [As selected by Architect from manufacturer's full range] <Insert color and gloss>. High-Performance Organic Finish: Two-coat fluoropolymer finish complying with [AAMA 2604] [AAMA 2605] and containing not less than [50] [70] percent PVDF resin by weight in color coat. Prepare, pretreat, and apply coating to exposed metal surfaces to comply with coating and resin manufacturers' written instructions. 1. E. Color: [Light bronze] [Medium bronze] [Dark bronze] [Champagne] [Black] <Insert color>. Color: [Match Architect's sample] [As selected by Architect from full range of industry colors and color densities]. Color and Gloss: [As indicated by manufacturer's designations] [Match Architect's sample] [As selected by Architect from manufacturer's full range] <Insert color and gloss>. High-Performance Organic Finish: [Three] [Four]-coat fluoropolymer finish complying with AAMA 2605 and containing not less than [50] [70] percent PVDF resin by weight in both color coat and clear topcoat. Prepare, pretreat, and apply coating to exposed metal surfaces to comply with coating and resin manufacturers' written instructions. METAL-FRAMED SKYLIGHTS 086300 - 11 Copyright 2011 AIA MasterSpec Premium 02/11 PRODUCT MASTERSPEC LICENSED BY ARCOM TO BRISTOLITE DAYLIGHTING SYSTEMS, INC. 1. 2.7 Color and Gloss: [As indicated by manufacturer's designations] [Match Architect's sample] [As selected by Architect from manufacturer's full range] <Insert color and gloss>. SOURCE QUALITY CONTROL A. Structural-Sealant Glazing: Perform quality-control procedures complying with ASTM C 1401 recommendations including, but not limited to, material qualification procedures, sealant testing, and fabrication reviews and checks. PART 3 - EXECUTION 3.1 EXAMINATION A. Examine areas and conditions, with Installer present, for compliance with requirements for installation tolerances and other conditions affecting performance of the Work. B. Proceed with installation only after unsatisfactory conditions have been corrected. 3.2 INSTALLATION A. General: 1. 2. 3. 4. 5. 6. 7. Comply with manufacturer's written instructions. Do not install damaged components. Fit joints between aluminum components to produce hairline joints free of burrs and distortion. Rigidly secure nonmovement joints. Install anchors with separators and isolators to prevent metal corrosion and electrolytic deterioration and to prevent impeding movement of moving joints. Weld components in concealed locations to minimize distortion or discoloration of finish. Protect glazing surfaces from welding. Seal joints watertight unless otherwise indicated. B. Metal Protection: Where aluminum will contact dissimilar materials, protect against galvanic action by painting contact surfaces with protective coating or by installing nonconductive spacers as recommended in writing by manufacturer for this purpose. C. Install continuous aluminum sill closure with weatherproof expansion joints and locked and sealed or welded corners. Locate weep holes at rafters. D. Install components to drain water passing joints, condensation occurring within framing members, and moisture migrating within skylight to exterior. E. Install components plumb and true in alignment with established lines and elevations. METAL-FRAMED SKYLIGHTS 086300 - 12 Copyright 2011 AIA MasterSpec Premium 02/11 PRODUCT MASTERSPEC LICENSED BY ARCOM TO BRISTOLITE DAYLIGHTING SYSTEMS, INC. F. Install glazing as specified in [Section 088000 "Glazing."] [Section 088400 "Plastic Glazing."] 1. Structural-Sealant Glazing: a. b. G. Erection Tolerances: Install metal-framed skylights to comply with the following maximum tolerances: 1. 2. 3.3 Prepare surfaces that will contact structural sealant according to structural-sealant manufacturer's written instructions to ensure compatibility and adhesion. Preparation includes, but is not limited to, cleaning and priming surfaces. Install weatherseal sealant according to Section 079200 "Joint Sealants" and according to weatherseal-sealant manufacturer's written instructions to produce weatherproof joints. Install joint filler behind weatherseal sealant as recommended in writing by weatherseal-sealant manufacturer. Alignment: Limit offset from true alignment to 1/32 inch (0.8 mm) where surfaces abut in line, edge to edge, at corners, or where a reveal or protruding element separates aligned surfaces by less than 3 inches (76 mm); otherwise, limit offset to 1/8 inch (3.2 mm). Location and Plane: Limit variation from true location and plane to 1/8 inch in 12 feet (3.2 mm in 3.7 m) but no greater than 1/2 inch (13 mm) over total length. FIELD QUALITY CONTROL A. Testing Agency: [Owner will engage] [Engage] a qualified testing agency to perform tests and inspections. 1. 2. Water-Spray Test: Before installation of interior finishes has begun, skylights shall be tested according to AAMA 501.2 and shall not evidence water penetration. Water Penetration under Static Pressure: Before installation of interior finishes has begun, areas shall be tested according to ASTM E 1105. a. b. c. 3. Test Procedures: Test under [uniform] [and] [cyclic] static-air pressure. Static-Air-Pressure Difference: <Insert pressure>. Water Penetration: None. Structural-Sealant Compatibility and Adhesion: Structural sealant shall be tested according to recommendations in ASTM C 1401. a. Destructive test method, Method A, Hand ASTM C 1401, Appendix X2, shall be used. 1) 2) 4. Pull Tab (Destructive) in A minimum of [one] [two] <Insert number> area(s) on each skylight face shall be tested. Repair installation areas damaged by testing. Structural-Sealant Glazing Inspection: After installation of metal-framed skylights is complete, structural-sealant glazing shall be inspected and evaluated according to ASTM C 1401 recommendations for quality-control procedures. METAL-FRAMED SKYLIGHTS 086300 - 13 Copyright 2011 AIA MasterSpec Premium 02/11 PRODUCT MASTERSPEC LICENSED BY ARCOM TO BRISTOLITE DAYLIGHTING SYSTEMS, INC. B. Repair or remove work where test results and inspections indicate that it does not comply with specified requirements. C. Additional testing and inspecting, at Contractor's expense, will be performed to determine compliance of replaced or additional work with specified requirements. D. Prepare test and inspection reports. END OF SECTION 086300 METAL-FRAMED SKYLIGHTS 086300 - 14