SECTION 26 09 43 NETWORK LIGHTING CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. 1.2 The work covered in this section is subject to all of the requirements in the General Conditions of the Specifications. Contractor shall coordinate all of the work in this section with all of the trades covered in other sections for the specification to provide a complete and operable system. All labor, materials, appliances, tools, equipment, facilities, transportation and services necessary for and incidental to performing all operations in connecting with furnishing, delivery and installation of the work of this Section. DESCRIPTION OF WORK A. Furnish and install a complete system for the control of lighting and other equipment as indicated on the plans, detailed in the manufacturer submittal and as further defined herein. Contractor is solely responsible to verify quantity, installation lo0cations and wiring requirements for this project. Specific manufacture’s catalog numbers, when listed in this section are for reference only. It is the responsibility of the contractor to verify with lighting control manufacturer all catalog information and specific product acceptability. B. The system shall include by not be limited by the following list: Pre-wired, microprocessor controlled relay or dimming panels with latching relays controlled via switches, photocells, occupancy sensors, Time based control, building automation systems, thermostats, and other control devices. 1.3 SUBMITTALS A. Shop Drawings 1. B. Product Data 1. C. Submit dimensioned drawings of lighting control system and accessories including, but not necessarily limited to, relay panels, switches, photocells, occupancy sensors, and other interfaces. Shop drawings shall indicate exact location of each device or a RFI to confirm location. Plans are diagrammatical. EC to verify all lighting control material requirements from approved shop drawings. Submit for approval manufacturer’s data on the specific lighting control system and components. One Line Diagram. 1. Submit a one-line diagram of the system configuration indicating the type, size and number of conductors between each. Submittals showing typical riser diagram are not acceptable. CRESTRON: GREEN LIGHT NETWORK LIGHTING CONTROLS 26 09 43 - 1 1.4 QUALITY ASSURANCE A. Manufacturer Qualification: Product shall be manufactured by manufacturer listed below. Manufacturer of network lighting controls with minimum five years record of satisfactory manufacturing and support of components comparable to basis of design system. Any product other than one made by manufacturer listed below must be pre-approved a minimum of ten days before bid time. 1. 2. 3. Lighting Control & Design (Basis of Design) Crestron Lutron B. Source Requirements: Provide Network Lighting Controls through a single source from a single manufacturer. C. Lighting Control Panels 1. D. Electrical Components, Devices, and Accessories: 1. 2. 1.5 Panels shall be UL 916 listed. LCP’s controlling emergency circuits shall be ETL listed to UL 924. Panels shall be listed to comply with CSA C22.2#205. Emergency source circuits controlled in normal operation by a relay panel shall fully comply with NEC 7009(b). Electrical contractor is responsible for verifying compliance All Devices: UL Listed and labeled per NFPA 70 Control Wiring: shall be in accordance with the NEC requirements for class 2 remote control systems, Article 725 and manufacturer specifications. WARRANTY A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace components of modular dimming controls system the fail in materials or workmanship within the specified warranty period following substantial completion. 1. B. 1.6 Warranty Period: 3 years. Manufacturer's Extended Support Service: Extended telephone support: Unlimited period. SYSTEM DESCRIPTION A. The lighting control system is a networked system that communicates via communication wire. The system must be able to communicate with digital centralized relay panels, small distributed relay panels, fully distributed fixture level control by relays or dimmers, digital switches, photocells, occupancy sensors, building management control, and other system interfaces. The intent is to centralize all lighting control into one system. Lighting control systems shall have the capability to be remotely controlled via the intent or building wide Ethernet Lan. B. System software shall provide real time status of each relay, each zone, and each group. C. Lighting control system shall be able to be monitored by and take commands from a remote PC. At any time, should the remote PC go off-line all system programming uploaded to the lighting control system shall continue to operate as intended. CRESTRON: GREEN LIGHT NETWORK LIGHTING CONTROLS 26 09 43 - 2 D. System shall be capable of warning of an impending off sweep by flashing lights Off/On once or twice by relay or by zone prior to the lights being turned off. The warning interval times between flash and the final lights off signal shall be definable for each zone. Occupants shall be able to override any scheduled Off sweep using local controls. E. System Components: components: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. System includes, but is not limited to, the following addressable Keypad controls. Touch panel controls. Window treatment controls. Remote occupancy sensors. Room-combining partition sensor. Lighting load shedding. Timed room lighting. Daylight compensating lighting controls. Audio visual equipment controls. Interface to facility-wide room management. Interface to building automation system interface. PART 2 - PRODUCTS 2.1 SYSTEM CHARACTERISTICS A. Web-accessible, network-connected programmable lighting control system that receives digital or analog signals from addressable input devices, assembles signals at central signal processor, and distributes operating signals to addressable control devices that effect a change in state. 1. 2.2 Electronic power switching modules and relays process signals and effect circuit on-off switching, emergency switching, and 0 – 10V fluorescent dimming where indicated. Emergency switching overrides preset state and puts each circuit to the programmed emergency condition. Buttons on the module provide manual disconnect and manual circuit testing. NETWORK LIGHTING CONTROL PANELS A. All relay panels shall be in a NEMA 1 rated enclosure with screw cover or hinged locking door. Other NEMA rated types optional. B. A barrier shall spate the high voltage and low voltage compartments of the panel and separate 120V and 277V. C. Control electronics shall be capable of driving 8 to 42 relays, control any individual or group of relays, provide individual relay overrides, provide a master override for each panel, store all programming in non-volatile memory, after power is restored return system to the correct state for time of day, provide programmable dual blink warn timers for each relay or zone of relays, and be abel to control Normally Open Latching or Normally Closed Latching Relays. D. All system components shall connect and be controlled via control wire, 4 twisted pair cable with connectors, providing real time two-way communication with each system component. E. Feed-Through Network Lighting Control Panels: CRESTRON: GREEN LIGHT NETWORK LIGHTING CONTROLS 26 09 43 - 3 1. 2. 3. 2.3 Branch Circuit Protection: Pass through type utilizing separate branch circuit protection indicated on Drawings. Switching Relay Types: Standard modular high inrush, lifetime rated minimum 1,000,000 on/off cycles, with air gap off protection. Cabinet Capacity: As required for circuits indicated. CENTRAL SIGNAL PROCESSOR A. A control processor shall control and program the entire lighting control system and supply all time functions and accept modem (RS232) inputs B. Shall be capable of a minimum of 32 schedules. Each schedule shall consist of one set of on/off times per day for each day of the week and for each of two holidays lists. Scheduling shall apply to any individual relay or group of relays. C. Shall be capable of controlling a minimum of 127 address on a single bus and be capable of interfacing digitally with other buses using manufacturer supplied interface cards. D. Control Processor: Network connected dual bus programmable control processor for low voltage controls, devices, and subsystems through multiple control interfaces. SNMP support, with built-in firewall, NAT, and router. 4-wire bus providing 24 VDC power to network devices, with two independent sensing inputs. In separate enclosure. 2.4 SYSTEM ACCESSORIES A. All switches shall be digital and communicate via control wire. Contract closure style switches, shall not be acceptable. B. Digitial low voltage switch shall be a device that sits on the lighting control system bus. Digital switch shall connect to the system bus using the same cable and connection method required for relay panels. C. Keypad shall be configurable in multiple button combinations. D. Remote Keypad Controls: Remote keypad with auto-adjusting backlight illuminating replaceable, engravable programmable buttons in number indicated, with white LED indicators, configured to fit in standard single-gang box. 1. 2.5 Color: As selected from manufacturer's full range of minimum 12 colors. CONDUCTORS AND CABLING A. UTP Cable: 100-ohm, UTP. Listed and labeled by an NRTL acceptable to authorities having jurisdiction as complying with UL 444 and NFPA 70 for the following types: 1. Communications Control Cable, Plenum Rated: 22 AWG data pair, stranded bare copper and 18 AWG power pair, stranded bare copper, Type CMP, complying with NFPA 262. a. Basis of Design Product: Crestron CRESNET-P. CRESTRON: GREEN LIGHT NETWORK LIGHTING CONTROLS 26 09 43 - 4 PART 3 - EXECUTION 3.1 EXAMINATION A. 3.2 Prior to installation, examine work area to verify measurements, and that commencing installation complies with manufacturer's requirements. INSTALLATION A. Comply with requirements of Division 26 Sections "Common Work Results for Electrical." B. Do not install network power controls until space is enclosed, HVAC systems are running, and overhead and wet work in space are complete. C. Install network power switching controls in accordance with manufacturer's instructions. D. Grounding: Provide electrical grounding in accordance with NFPA 70. E. Provide panelboard schedule in pocket provided in panel doors. F. Any damage done to electronic components due to failure to protect them shall be the sole responsibility of the installing contractor. G. Do not mix low voltage and high voltage conductors in the same conduit. No exceptions. 3.3 SOFTWARE A. 3.4 Install and program software to meet the Owner's requirements. Provide current licenses. And backup copies of the software for the Owner's records. SYSTEM STARTUP A. Provide manufacturer's system startup and adjustment. EC shall contact control manufacturer at least 7 days before turnover of project. EC shall be available during factory commissioning. B. Switch each load on and off with manual line test feature of the power switching module before installing processors. C. Perform operational testing to verify compliance with Specifications. Adjust as required. D. Provide a factory technician for on-site training of the owners’ representatives and maintenance personnel. Coordinate timing with General Contractor. 3.5 ADJUSTING A. 3.6 Within 12 months of the date of Substantial Completion provide onsite service to adjust the system to account for actual occupied conditions. DEMONSTRATION A. Factory authorized service representative to instruct owner's staff to adjust, operate and maintain network power switching systems; and provide instruction using the system software. CRESTRON: GREEN LIGHT NETWORK LIGHTING CONTROLS 26 09 43 - 5 3.7 CLOSEOUT ACTIVITIES A. Demonstration: Schedule demonstration with Owner. B. Training: Train Owner's personnel to operate, maintain, and program network power switching systems. Allow for a minimum of trips to the jobsite to provide additional training as needed. 1. Furnish set of approved submittals, and record drawings of actual installtion for Owner's personnel in attendance at training session. END OF SECTION 26 09 43 CRESTRON: GREEN LIGHT NETWORK LIGHTING CONTROLS 26 09 43 - 6