Scandia House, Boundary Road, Woking, Surrey GU21 5BX Tel: +44 (0) 1483 771 910 Fax: +44 (0) 1483 227 519 Email: info@sav-systems.com Web: www.sav-systems.com HIU FlatStation specification indirect (based on SAV HIU FlatStation 7 Series) Hot water and heating to each apartment shall be provided by means of wall mounted heat interface units located in each apartment and fed from the main community heating distribution system. Heat interface units shall have the following operating capabilities: Table 1: Operating limits and demands Nominal pressure Max. heating supply temp. Min. DCW pressure Max. primary pressure differential Hot water temp. settable range Heating system settable range Hot water temp. control (max.) Max. idle function by-pass temp. Energy rating for pump in sec. side Max DHW capacity Max heating capacity 7 Series BS PN10 bar 120 °C 0.5 bar 4.5 bar 20-60 °C 30-100 °C ± 2.5 °C of set value =DHW set value A level 90 kW 40 kW 7 Series DS PN10 bar 120 °C 1.0 bar 4.5 bar 45-65 °C 30-100 °C ± 2 °C of set value =DHW set value -8 °C A level 59 kW 35 kW OPTIONAL CLAUSES REGARDING APPEARANCE AND THERMAL INSULATION: Heat interface units shall have white lacquered stainless steel covers suitable for locating in occupied areas. OR Heat interface units shall have white lacquered stainless steel covers suitable for locating in occupied areas, and thermal insulation of internal components to minimise heat losses. (Available for the 7 Series DS.) July 2012 Technical specification subject to change without notice Page 1 of 3 OR Heat interface units shall have moulded thermal insulation casings suitable for locating in unoccupied areas such as cupboards. The thermal insulation casings must have a thermal conductivity around 0.039*W/m*K. (Available for the 7 Series DS.) Heat interface units shall incorporate a thermostatically controlled instantaneous hot water heater, and a branch connection for a central heating circuit with specific features as described below. Hot water heaters The instantaneous hot water heaters inside each heat interface unit shall heat incoming mains cold water via a plate heat exchanger using heated water from the community heating system. Hot water heaters shall have the following features integral to the heat interface units: Thermostatic control of hot water temperature enabling a constant, pre-settable hot water supply temperature (as specified in table 1) at all times, regardless of temperature or pressure variations in the community heating system and cold water supply. (Note: there should be no requirement for localised thermostatic mixer valves at outlets, unless required by special building types.) Thermostatically controlled by-passes to ensure a constant, low level flow of water from the community heating system through the unit, ready to cope with sudden demands in hot water (see idle function requirement in table 1). Central heating circuits Water for central heating systems shall be heated via a plate heat exchanger located inside each heat interface unit. The plate heat exchanger shall be used to transfer heat from the community heating system (the primary side) to a separate circuit capable of feeding radiators or under-floor heating within each apartment (the secondary side). The following components shall be provided as integral to the heat interface units: A strainer in the primary pipework to protect the primary side of the plate heat exchanger from circulating debris. A differential pressure control valve in the primary side pipework to maintain a constant pressure differential across the plate heat exchanger, regardless of variations in pump speed or valve closures in other parts of the community heating system. July 2012 Technical specification subject to change without notice Page 2 of 3 A 2 port on/off control valve on the return of the primary side pipework to prevent energy loss when no heating is required. A wiring box with connection to separate timer, which energises the primary control valve. The wiring box must also have a wired connection to the secondary side pump allowing for this to be switched on and off according to heating demand. An energy meter in the primary side pipework to monitor the heating energy consumption to the apartment. The measuring accuracy of the energy meter must meet the requirements of EN 1434 (MID) class 2. A two port thermostatic control valve in the primary side pipework, controlled such that the secondary side flow temperature is maintained at a fixed pre-settable value (suitable for either radiators or under-floor heating) as detected by a temperature sensor located in the secondary side flow pipe. A pump in the secondary side pipework incorporating a modulating variable speed pressure controlled operation mode, for circulation of water to the central heating system. A strainer in the secondary side pipework to protect the secondary side of the plate heat exchanger. An expansion vessel in the secondary side pipework to accommodate expansion of secondary circuit water. A safety valve and drain off cock in the secondary side pipework to provide pressure relief in the event of a malfunction. Installation Heat interface units shall be supplied with ball valves in all pipework connections to and from the units. Primary/community heating system connections shall have facility for installation of pressure test points on flow and return connections for checking of pressure differentials across the units. Primary/community heating system connections shall have a fixed full bore by-pass to allow flushing of the system pipework without having to circulate flushing water through the heat interface unit. Depending on the circumstances, pipework connections to heat interface units shall be either bottom fed, top fed, or mixed. July 2012 Technical specification subject to change without notice Page 3 of 3