January 13, 2010
Laura Lewallen
Pb2 Architecture & Engineering
710 West Roselawn Drive
Rogers, AR 72756
WAL-MART #1599 REMODEL, 11701 METCALF, OVERLAND PARK, KANSAS, PLAN
REVIEW NUMBER PRS2009-00470
The Planning and Development Services Department reviewed the plans submitted on
December 21, 2009. The following comments are from various divisions within the
Planning and Development Services Department.
When resubmitting your plans, include a cover letter complete
with project name, address, and plan review number, and
indicate how you have addressed each plan review comment.
Please refer to the enclosed guidelines (Attachment A) and
sample cover letter (Attachment B).
Building Safety Division - Plan Review
The following comments are from the Building Safety Division-Plan Review. Direct any
questions regarding these issues to Gregory Maggiore M.C.P. at (913) 895-6248.
Code references for this review:
2006 International Building Code ............................................ 2006 IBC
2006 International Fire Code .................................................. 2006 IFC
2006 International Plumbing Code .......................................... 2006 IPC
2006 International Mechanical Code ...................................... 2006 IMC
2006 International Fuel Gas Code .......................................... 2006 IFGC
2006 International Energy Conservation Code ....................... 2006 IECC
2005 National Electric Code ................................................... 2005 NEC
Americans with Disabilities Act Accessibility Guidelines ......... ADAAG
Overland Park Municipal Code ............................................... OPMC
Building Safety Division/Plan Review  913/895-6205  Fax 913/895-5016
Laura Lewallen
January 13, 2010
Page 2 of 5
1.
Sheet D1 shows areas of demolition. Sheet D1.1 shows construction details of
proposed dust barriers and proposed security enclosure. Please provide
information for the placement and staging of these structures so as to not create
means of egress deficiencies as per 2006 IBC Chapter 10 and cause a
deficiency in fire sprinkler coverage as per NFPA 13.
2.
Sheet D1 shows front entry doors 098A and 099A to be removed. Please clarify
what exits, egress, and accessible means of egress will be maintained during
this part of the project as required by Chapter 10 and 11 of the 2006 IBC. How
will patrons and employees enter and exit the store?
3.
Sheet A1 shows front entry doors 098A/B and 099A/B to egress an
unconditioned vestibule. The Door Schedule on Sheet A8 does not specify
tempered thermal glass with a U Value of .85 or better as required by Table
502.3 of the 2006 IECC; please clarify.
4.
Sheet A1 and A8 show front entry doors 098A and 099A with glazing over head.
Please clarify what type of glazing will be used in this location in compliance with
Chapter 24 of the 2006 IBC and Table 502.3.
5.
Please clarify where Temporary Dust Partition D shown on Sheet TC1 will be
implemented to separate adjacent conditioned space to maintain 68F at 3 feet
above floor as required by 2006 IMC (B) 309.1.
6.
Sheet TC1 details call for plywood, wood studs and polyethylene plastic. This
proposed structure is incongruous with Section 603 of the 2006 IBC; please
clarify.
7.
Sheet D1 Demolition Plan shows public toilet facilities to be removed. Please
provide information on how patrons and employees will be provided with
adequate toilets and accessible toilet facilities. Specification 01500 lacks
information requiring accessible toilets; please clarify.
8.
Sheet SP1 and SP2 show new ramps to be constructed. Please provide high
point and low point elevation dimensions to verify no ramp exceeds 30” in height
as required by Section 106.1.1 of the 2006 IBC and Section 4.8.2 of the ADAAG.
9.
Sheet SP2 Details show hand rail extensions at the bottom of the ramps and
stairs (not attach to building). The details do not provide the 27” maximum from
the bottom of the hand rail extension to the top of landing as required by Section
4.8.5 Fig 27 of the ADAAG. The delineation shown is mathematically correct,
however not showing the 27” can lead to confusion in the field and require
revision by Section 106.1.1 of the 2006 IBC.
Laura Lewallen
January 13, 2010
Page 3 of 5
10.
Sheet SP2 Details show a 4” gap between the bottom of handrail/guard and the
top of the ramp and top of the landing. Ramps and landings with a drop off are
required to have a minimum 2” edge protection as required by Section 4.8.7, Fig.
27 of the ADAAG.
11.
Sheet A1 Partition Legend calls for plywood wainscot in various locations. This
proposed construction is incongruous with Section 603 of the 2006 IBC; please
clarify.
12.
Sheet A1 and Door Schedule on A8 show new roll up doors to be installed in
various locations. Neither Division 8 (08332) in the specifications or the
drawings required the roll up doors to comply with DASMA 107 (a 90 MPH rated
door) as required by Section 2603.4.1.9 of the 2006 IBC; please clarify.
13.
Sheet A4.1 calls for installing a new roofing system over the existing roof. This
application is not permitted under Section 1510.3 of the 2006 IBC with
exceptions; please clarify.
14.
Sheet A4.1 calls for installing a new roofing system over the existing roof.
Please verify the existing structure is structurally capable to with stand the
additional dead load as required by Section 1510.2 of the 2006 IBC.
15.
Sheet A5.1 shows new Vestibule 711 with incomplete dimensions. Please
provide complete dimensions for this space as required by Section 106.1.1 of the
2006 IBC.
16.
Vestibule Doors 711 A and 711 B egress an unconditioned vestibule. The Door
Schedule on Sheet A8 does not specify tempered thermal glass with a U Value
of .85 or better as required by Table 502.3 of the 2006 IECC.
17.
Sheet PH1.1 shows a 4” (B9) base in Toilet 301. Please revise to provide a 6”
high base as required by Section 1210.1 of the 2006 IBC.
18.
Please provide information that the wall materials with in 24" and 48” AFF
adjacent to the water closets are to be constructed of materials (and substrate
that clad the studs) that is not adversely affected by moisture as required by
Section 1210.2 of the 2006 IBC for new toilet rooms.
19.
The Bath Room Elevations and Finish Schedule on Sheet A7 call for NRP1 paint
on walls behind and adjacent to toilets. Please provide information on paint to
be used in theses locations that comply with the requirements of Section 1210.2
of the 2006 IBC.
Laura Lewallen
January 13, 2010
Page 4 of 5
20.
Sheet S1.1 Slab Plan calls for a vapor barrier to match existing which is
incongruous with other notes requiring a 6 mil Polyethylene vapor retarder.
Please revise all notes to provide a 6 mil Polyethylene vapor retarder in
compliance with Section 1910 of the 2006 IBC.
21.
Sheet S1.1 calls out the FF EL = 100’-0” and Civil Drawings Sheet 6000 series
calls out the finished floor elevation as 992.0. Please coordinate drawings as
required by Section 106.1.1 of the 2006 IBC. (Sheet P1 notes condition.)
22.
Sheet S6 calls out ½” Plywood Sheathing on Pharmacy Framing Plan. This
proposed construction is incongruous with Section 603 of the 2006 IBC; please
clarify.
23.
Sheet E1.2 shows that there will be new exterior lighting. Please provide
information that exterior lighting is in compliance with Section 505.6.2 of the
2006 IECC.
24.
Electrical Drawings and Section 16100 2.2 E calls out for allowed conductors
such as THHN conductors to be installed underground or under concrete slabs
which the NEC designates as wet locations. THHN is not rated to be installed in
a wet location as per Table 310.13 of the 2005 NEC; please clarify.
25.
Civil Drawings show an accessible parking space that is not van accessible in
the separate parking lot next to the garden center. This space is required to be
van accessible by Section 1106.5 of the 2006 IBC.
26.
Civil Drawings show an accessible parking space that is not van accessible in
the separate parking lot next to the Garden Center. Please show the grades and
slopes of this required accessible parking and the accessible rout to the entrance
as required by Section 4.6 of the ADAAG.
27.
Obtain a building sewer and connection permit from the Johnson County
Wastewater Offices, 11811 South Sunset Drive, Suite 2500, Olathe, Kansas; or
provide information that such a permit is not required. You may reach the
Johnson County Wastewater Offices at (913) 715-8500.
Current Planning Division
The following comments are from the Current Planning Division. Questions regarding
these issues should be directed to David Dalecky at (913) 895-6218.
1.
Sheet A-2 - The elevation drawing calls for the glazed tile material to be painted.
The Planning Commission did not approve of this material to be painted when
the proposed renovations were reviewed and approved by the commission on
October 26, 2009. Coordinate any proposed color changes and materials
Laura Lewallen
January 13, 2010
Page 5 of 5
changes with the Planning Department staff prior to implementing material
changes to the building.
Provide a general description (color name) of the unique colors, i.e. what is a
common color name for the “Domino”.
2.
Sheet A 2.2 - No signage is approved with the building permit drawings.
Separate sing permits shall be submitted for review and approval by the code
enforcement specialist.
Engineering Services Division
The following comment is from the Engineering Services Division. Questions regarding
this issue should be directed to Mark Stuecheli at (913) 895-6026.
1.
As was discussed in a 12/22/09 telephone conversation with Jeff Laubach of
Phelps Engineering, increase from 25 feet to at least 30 feet the radius on the
curb return that is proposed to be reconstructed at the southwest corner of the
site where the main western drive intersects the shopping center loop road. That
change will add an extra margin of safety to the effort to increase the effective
width to the driveway to hopefully prevent the rutting in the island that currently
occurs.
If you have questions or alternatives to discuss on the above-mentioned items, please
contact the appropriate person above, or contact me at this office, (913) 895-6248.
Gregory Maggiore, M.C.P.
gmz/cdm