ANSI /ASHRAE /ASHE Standard 170-2008 Table 6-1 Minimum Filter Efficiencies Space Designation (According to Function) Filter Bank Number 1 (MERV)a Filter Bank Number 2 (MERV)a Classes B and C Surgery, inpatient and ambulatory diagnostic and therapeutic radiology, inpatient delivery and recovery services 7 14 In patient care, treatment, and diagnosis, and those spaces providing direct service or clean supplies and clean processing (except as noted below); AII rooms 7 14 Protective environment (PE) rooms 7 (HEPA)c,d 13b N/R* Laboratories; class A surgery and associated semi-restricted spaces * NR= not required Note a: The minimum efficiency reporting value (MERV) is based on the method of testing described in ANSI/ASHRAE Standard 52.2-2007, Method of Testing General Ventilation Air-Cleaning Devices for Removal Efficiency by Particle Size (see Informative Annex B: Bibliography). Note b: Additional prefilters may be used to reduce maintenance for filters with efficiencies higher than MERV 7. Note c: As an alternative, MERV-14 rated filters may be used in Filter Bank No. 2 if a tertiary terminal HEPA filter is provided for these spaces. Note d: High-Efficiency Particulate Air (HEPA) filters are those filters that remove at least 99.97% of 0.3 micron-sized particles at the rated flow in accordance with the testing methods of IEST RP-CC001.3 (see Informative Annex B, Bibliography). Design Temperature (I), F/C RH (k), % Air recirculated by means of room units (a) AII Room Air Exhausted Directly to Outdoors (j) Minimum Total ACH Minimum Outdoor ACH Pressure relationship to Adjacent Areas (n) ANSI /ASHRAE /ASHE Standard 170-2008 Table 7-1 Design Parameters— From ANSI/ASHRAE/ASHE Standard 170-2008 Surgery and Critical Care Positive 4 20 N/R No 20-60 Operating/Surgical cystoscopic rooms (m), (n), (o) Delivery room (Caesarean) (m), (n), (o) Positive 4 20 N/R No 20-60 Positive 4 20 N/R No 20-60 Substerile service area N/R 2 6 N/R No N/R Recovery Room N/R 2 6 N/R No 20-60 Critical and intensive Care N/R 2 6 N/R No 30-60 Intermediate care (s) N/R 2 6 N/R N/R Max 60 Wound Intensive care (burn unit) N/R 2 6 N/R No 40-60 Newborn Intensive care Positive 2 6 N/R No 30-60 Treatment room (p) N/R 2 6 N/R N/R 20-60 Classes B and C operating rooms (m), (n), (o) -1- 68-75 / 20-24 68-75 / 20-24 68-75 / 20-24 N/R 70-75 / 21-24 70-75 / 21-24 70-75 / 21-24 70-75 / 21-24 72-78 / 22-26 70-75 / 21-24 Design Temperature (I), F/C RH (k), % Air recirculated by means of room units (a) AII Room Air Exhausted Directly to Outdoors (j) Minimum Total ACH Minimum Outdoor ACH Pressure relationship to Adjacent Areas (n) Table 7-1 Design Parameters— From ANSI/ASHRAE/ASHE Standard 170-2008 (continued) Surgery and Critical Care (cont.) Trauma room (crisis or shock) ( c) Positive 3 15 N/R No 20-60 70-75 / 21-24 N/R Medical/anesthesia gas storage ( r) Negative N/R 8 Yes N/R N/R Laser Eye room Positive 3 15 N/R No 20-60 ER waiting rooms (q) Negative 2 12 Yes N/R Max 65 Triage (q) Negative 2 12 Yes N/R Max 60 ER decontamination Negative 2 12 Yes No N/R Radiology Waiting Rooms(q), (w) Negative 2 12 Yes N/R Max 60 Class A Operating/Procedure room(o), (d) Positive 3 15 N/R No 20-60 Patient Room N/R 2 6 N/R N/R Max 60 Toilet Room Negative N/R 10 Yes No N/R Newborn Nursery Suite N/R 2 6 N/R No 30-60 Protective Environment Room (t) Positive 2 12 N/R No max 60 Protective Environment Anteroom (t) ( e) N/R 10 N/R No N/R AII room (u) Negative 2 12 Yes No max 60 AII anteroom (u) N/R N/R ( e) 10 Yes No N/R Combination AII/PE Room Positive 2 12 Yes No max 60 Combination AII/PE Anteroom ( e) N/R 10 Yes No N/R Labor/Delivery/Recovery/Postpartu m (LDRP) (s) Labor/Delivery/Recovery (LDR) (s) N/R 2 6 N/R N/R max 60 N/R 2 6 N/R N/R max 60 Nourishment Area or Room N/R N/R 2 N/R N/R N/R 70-75 / 21-24 70-75 / 21-24 N/R Patient Corridor N/R N/R 2 N/R N/R N/R N/R Resident Room N/R 2 2 N/R N/R N/R Resident gathering/activity/dining N/R 4 4 N/R N/R N/R Physical Therapy Negative 2 6 N/R N/R N/R Occupational Therapy N/R 2 6 N/R N/R N/R Bathing Room Negative N/R 10 Yes N/R N/R 70-75 / 21-24 70-75 / 21-24 70-75 / 21-24 70-75 / 21-24 70-75 / 21-24 X-Ray (diagnostic and treatment) N/R 2 6 N/R N/R Max 60 X-Ray (surgery/critical care and catheterization) Darkroom (g) Positive 3 15 N/R No Max 60 Negative 2 10 Yes No N/R 70-75 / 21-24 70-75 / 21-24 70-75 / 21-24 N/R 70-75 / 21-24 70-75 / 21-24 Inpatient Nursing 70-75 / 21-24 N/R 72-78 / 22-26 70-75 / 21-24 N/R 70-75 / 21-24 N/R 70-75 / 21-24 N/R Nursing Facility Radiology (v) –2– 72-78 / 22-26 70-75 / 21-24 N/R Design Temperature (I), F/C RH (k), % Air recirculated by means of room units (a) AII Room Air Exhausted Directly to Outdoors (j) Minimum Total ACH Minimum Outdoor ACH Pressure relationship to Adjacent Areas (n) Table 7-1 Design Parameters— From ANSI/ASHRAE/ASHE Standard 170-2008 (continued) Diagnostic and Treatment Bronchoscopy, sputum collection, and pentamidine administration (n) Laboratory, general (v) Negative 2 12 Yes No N/R Negative 2 6 N/R N/R N/R Laboratory, bacteriology (v) Negative 2 6 Yes N/R N/R Laboratory, biochemistry (v) Negative 2 6 Yes N/R N/R Laboratory, cytology (v) Negative 2 6 Yes N/R N/R Laboratory, glasswashing Negative 2 10 Yes N/R N/R Laboratory, histology (v) Negative 2 6 Yes N/R N/R Laboratory, microbiology (v) Negative 2 6 Yes N/R N/R Laboratory, nuclear medicine (v) Negative 2 6 Yes N/R N/R Laboratory, pathology (v) Negative 2 6 Yes N/R N/R Laboratory, serology (v) Negative 2 6 Yes N/R N/R Laboratory, sterilizing Negative 2 10 Yes N/R N/R Laboratory, media transfer (v) Positive 2 4 N/R N/R N/R Autopsy room (n) Negative 2 12 Yes No N/R Nonrefrigerated body-holding room Negative N/R 10 Yes No N/R Pharmacy (b) Positive 2 4 N/R N/R N/R Examination Room N/R 2 6 N/R N/R Max 60 Medication Room Positive 2 4 N/R N/R Max 60 Gastrointestinal endoscopy procedure room Endoscope cleaning Positive 2 6 N/R No 30-60 Negative 2 10 Yes No N/R Treatment room N/R 2 6 N/R N/R Max 60 Hydrotherapy Negative 2 6 N/R N/R N/R Physical Therapy Negative 2 6 N/R N/R Max 65 Negative N/R 10 Yes No N/R N/R Soiled or decontamination room Negative 2 6 Yes No N/R Clean workroom Positive 2 4 N/R No Max 60 Sterile Storage Positive 2 4 N/R N/R Max 60 72-78 / 22-26 72-78 / 22-26 72-78 / 22-26 (h) 68-73 / 20-23 70-75 / 21-24 70-75 / 21-24 70-75 / 21-24 70-75 / 21-24 N/R 70-75 / 21-24 70-75 / 21-24 70-75 / 21-24 70-75 / 21-24 70-75 / 21-24 70-75 / 21-24 70-75 / 21-24 68-75 / 20-24 70-75 / 21-24 N/R 70-75 / 21-24 70-75 / 21-24 68-73 / 20-23 N/R 70-75 / 21-24 72-80 / 22-27 72-80 / 22-27 Sterilizing Sterilizer Equipment Room Central Medical and Surgical Supply -3- Design Temperature (I), F/C RH (k), % Air recirculated by means of room units (a) AII Room Air Exhausted Directly to Outdoors (j) Minimum Total ACH Minimum Outdoor ACH Pressure relationship to Adjacent Areas (n) Table 7-1 Design Parameters— From ANSI/ASHRAE/ASHE Standard 170-2008 (continued) Service Food Preparation Center (i) N/R 2 10 N/R No N/R 72-78 / 22-26 N/R Ware Washing Negative N/R 10 Yes No N/R Dietary Storage N/R N/R 2 N/R No N/R Laundry, general Negative 2 10 Yes No N/R 72-78 / 22-26 N/R Soiled Linen (Sorting and Storage) Negative N/R 10 Yes No N/R N/R Clean Linen Storage Positive N/R 2 N/R N/R N/R Linen and Trash Chute Room Negative N/R 10 Yes No N/R 72-78 / 22-26 N/R Bedpan Room Negative N/R 10 Yes No N/R N/R Bathroom Negative N/R 10 Yes No N/R Janitor's Closet Negative N/R 10 Yes No N/R 72-78 / 22-26 N/R Soiled Workroom or soiled holding Negative 2 10 Yes No N/R N/R Clean workroom or clean holding Positive 2 4 N/R N/R N/R N/R Hazardous material storage Negative 2 10 Yes No N/R N/R Support Space