Title 24: Lighting and Lighting Controls (presented July 1, 2014)

advertisement

Webinar: Title 24 Lighting and Lighting Controls

Slide 1: Title 24 Lighting and Lighting Controls

Script: This training session is brought to you by Southern California Edison (SCE).

Content: Presented by PECI

Slide 2: Welcome! Meet your hosts

Script: Today’s training is presented by PECI, a third party consulting firm.

My name is Eric Mullendore and I’ll be your presenter today. Joining me on the chat function in WebEx is my colleague, Phil Jordan.

For the past two years, we’ve both been providing technical support services to SCE’s Customer’s

Authorized Agents. I’ll be providing some contact information at the end of the session in case you are interested in taking advantage of these services.

After today’s webinar we will provide a copy of the presentation to attendees.

All phones are muted so please use the chat function to communicate and Phil will respond.

Content: PECI - Technical Support Services for Customer’s Authorized Agents

Slide 3: Agenda

Script: The training will start with a discussion of the LPD requirements in Title 24 and how these requirements are used in to set the code baseline for Customized Solutions lighting applications.

The version of Title 24 that takes effect on July 1, 2014 has a number of new requirements for lighting controls so the bulk of today’s presentation will focus on those updates and how they impact eligibility for incentives through Express and Customized Solutions.

In the last couple slides we’ll take a look at the resources available to help you understand Title 24 requirements in more detail and how to follow up on questions about how the code is used in Incentives

Applications.

Content:

• Title 24 Impact on Lighting Power Density (LPD)

• Title 24 Impact on Lighting Controls

• Resources

Slide 4: Learning Objectives

Script: Every training we do, we present the learning objectives within the first couple slides. Hopefully after the presentation you’ll be able to:

• Identify which components of a lighting project exceed Title 24 requirements

• Locate resources to ensure retrofit projects comply with Title 24 requirements

Content: At the end of this session, you will be able to:

• Identify which components of a lighting project exceed Title 24 requirements

• Locate resources to ensure retrofit projects comply with Title 24 requirements

Slide 5: Lighting Power Density (LPD)

Slide 6: Lighting Power Density Definition

Script: Define LPD and scope within Title 24

From the 2013 standards Section 100.1, an Enclosed Space is “space that is substantially surrounded by solid surfaces, including walls, ceilings or roofs, doors, fenestration areas, and floors or ground”

(basically a room or corridor).

Content: Lighting Power Density (LPD) is the amount of electrical power used to illuminate a space, expressed in Watts per unit of area (W/ft 2 ).

Title 24 defines a maximum allowable LPD for:

• New construction, and

• Lighting retrofits impacting ≥10% of fixtures per enclosed space

Slide 7:

Script: Under Title 24, there are three approaches to establishing the maximum allowable LPD: whole building, area/category or tailored.

These same methods can be used to establish the Code LPD baseline for calculated lighting projects.

Most projects will use either the whole building or area method. The tailored method is used to account for spaces with special lighting needs and is available only when the other two methods aren’t available.

If you think your project may require the tailored method please contact the CAA Technical Support team to discuss.

Content:

1) Whole Building

• Only used when one type of occupancy makes up ≥90% of the entire building

• Retail, wholesale stores, hotel/motels, and high-rise residential buildings may not use this method

2) Area/Category

• Used when there is a need to exclude areas, such as main entry areas, lobbies, corridors, restrooms, & support functions

• Used when the project does not fit one of the Title 24 building type definitions

3) Tailored Method

• Includes special power allowances

• Contact CAA Technical Support if this method is to be used

Slide 8: Impact on Applications to SCE

Script: There are a few types of projects that don’t require Lighting Power Density calculations.

There is a separate training focused on the LPD Calculator, which is a tool SCE’s engineering team has developed to assist with custom lighting retrofits. It’s not required but I’d recommend at least reviewing how it works as it includes not only the LPD values from Title 24 but also the CDF and HVAC Interactive

Effects Factors, which are required by SCE for most interior lighting retrofits.

Content: SCE requires LPD calculations for all lighting retrofits, except:

• Express Solutions

• Exterior lighting

• Lamp only

• Dimming ballast only

SCE’s LPD Calculator is not required but recommended, and includes:

• Title 24 LPD Baselines

• Coincident Diversity Factors (CDF)

• HVAC Interactive Effects Factors

Slide 9: Lighting Controls

Slide 10: Policy

Script: See Table 141.0-E (p. 212) in Title 24 for details

To qualify as a modification-in-place, the modification to a luminaire must be limited to one or more of the following methods:

• Replacing lamps and ballasts with like type or quantity in a manner that preserves the original luminaire listing.

• Changing the number or type of light source in a luminaire, including: socket renewal, removal or relocation of sockets or lampholders, and/or related wiring internal to the luminaire, including the addition of safety disconnecting devices.

• Changing the optical system (e.g. reflector) of a luminaire in part or in whole.

• Replacing whole luminaires one-for-one in which the only electrical modification involves disconnecting the existing luminaire and reconnecting the replacement luminaire

Content:

• Controls must exceed applicable Title 24 requirements to be eligible for incentives.

• Control requirements are triggered when ≥10% of the luminaires are impacted by a retrofit.

• If <40 luminaires are impacted and retrofit is categorized as modifications-in-place, then controls compliance isn’t triggered for the whole space.

Slide 11: Occupancy/Vacancy Control

Script: See Section 130.1(a) in Title 24 for details of shut-off control requirements

Content:

• Shut-off control based on occupancy control is required in most interior spaces.

• SCE retired integral fixture occupancy sensor Solutions Codes from Express Solutions (LT-41007 and LT-76101).

• All other occupancy sensor Solution Codes are limited to projects that don’t trigger code requirement for occupancy sensors (LT-58209, LT-98724, LT-38102, LT-36254, LT-10867).

Slide 12: Daylighting

Script: Daylighting controls are covered in Section 130.1 (d) of the 2013 standards.

Applicability to retrofits is covered in Section 141.0.

Content:

• Multi-level, automatic daylighting control is required for most spaces with available skylights and sidelighting (windows).

• Daylighting is not required when total lighting power in the daylit zone is < 120 watts or in rooms that have < 24 SF of glazing area.

• Daylighting is not required in retrofits where the LPD is ≤ 85% of the maximum allowable LPD.

• SCE will accept applications where the applicant is only retrofitting ballasts and controls as

Retrofit Add-on (LT-36502, LT-49584, LT-78223, LT-89432, LT-90853, LT-74751).

Slide 13: Bi-Level Switching

Script: See Section 130.1(c)6 and 130.1(c)7 of 2013 version of Title 24 for details of code requirements.

Content:

• Bi-level switching based on occupancy (Partial On/Off) is required for:

− Stairwells,

− Corridors,

− Parking garages

− Warehouses

− Library book aisles

• SCE has added requirement to Express Solution Codes for Bi-level Fluorescent Fixtures (LT-69302 and LT-48107) to clarify that they apply only to Retrofit Add-on projects.

Slide 14: Exterior Lighting Controls

Script: 2013 standards Section 130.2 (c) 1. – All installed outdoor lighting shall be controlled by photocontrol or outdoor astronomical time-switch control that automatically turns OFF the outdoor lighting when daylight is available.

For specifics regarding outdoor lighting mounted 24 ft or less above the ground refer to the 2013 standards Section 130.2 (c) 3.

Content:

• Astronomical timeclock or photocell control is required for most exterior lighting.

• If fixtures mounted 24 ft or less above the ground, bi-level or dimming control based on occupancy is required.

• SCE has expired Express Solutions for Exterior Timeclock and Photocell Control (LT-22809 and

LT-68108).

Slide 15: Pause for Questions

Images: A Questions Mark clip art.

Slide 16: Resources

Script: This webinar was only intended to give you a rough idea about what Title 24 is and how it impacts SCE’s demand-side management offerings. The resources will cover in the next section is where you want to go to learn more about how to ensure your projects are in full compliance with the standards.

Slide 17: Official Version

Script: This site includes the official PDF version of the standards as well as compliance manuals and forms.

Content: http://www.energy.ca.gov/title24/2013standards/index.html

Images: Picture of the front cover of Title 24.

Slide 18: Energy Code Ace

Script: The EnergyCodeAce.com website is an effort being supported by the CEC and the state’s Investor

Owned Utilities, including SCE. It is still under development in some places but already has a lot of great resources.

Content: www.EnergyCodeAce.com

• Tools Ace™ can help identify appropriate forms you’ll need to submit to permitting agency

• Resources Ace™ includes trigger sheets, checklists and fact sheets

• Training Ace™ includes links to information about training opportunities hosted throughout

California

Slide 19: Title 24 Hotline

Script: Title 24 Hotline and Email addresses are being maintained and staffed by the CEC.

Content: Phone

• Toll-Free in California: (800) 772-3300

• Outside California: (916) 654-5106

Email

• Title 20: Appliances@energy.ca.gov

• Title 24: Title24@energy.ca.gov

Blueprint Newsletter

• Sign Up: www.energy.ca.gov/efficiency/listservers.html

• Archive: www.energy.ca.gov/efficiency/blueprint/

Slide 20: Training

Script: Resources for identifying additional training opportunities related to Title 24 and the 2013 update.

Content:

• SCE Energy Education Centers: Tulare and Irwindale

• CEC Website: http://www.energy.ca.gov/title24/training/

• Decoding Talks™: Interactive Online Events

Slide 21: Pause for Questions

Images: A Questions Mark clip art.

Slide 22: Successful Applications Start here!

Script: The latest version of the Solutions Directory is always available at: https://sceonlineapp.com/forms/Solutions%20Directory%20Q1%202013.pdf

The Online Application Tool can be found at: https://www.sceonlineapp.com/

For technical support on your projects pre-application submittal, contact the Customer’s Authorized

Agent Technical Support team (CAASupport-Projects@sce.com). Our team is here to answer your eligibility questions so that you can proceed with a project with confidence. We can also be a resource when you are trying to design a more comprehensive project for your customer.

Regular editions of the Energy Solutions E-News are distributed monthly. This is a great resource for ongoing changes to SCE Offerings, and also includes articles covering frequently asked questions and announcements about training and education opportunities. To sign up for the Energy Solutions E-News, email

CAASupport-News@sce.com.

Lastly, you can view previous training sessions through this Online Learning Center, and send questions, suggestions or other feedback regarding trainings such as this one to CAASupport-Training@sce.com.

This concludes our presentation of Customized Solutions. Thank you for your time.

Content:

1.

SCE’s Customer’s Authorized Agent Website www.CAASupport.com

2.

CAA Application Checklist www.caasupport.com/documents/scecaa-application-checklist.pdf

3.

Online Application Tool www.sceonlineapp.com

4.

Technical Support Service CAASupport-

Projects@sce.com

or call (800) 935-5112

5.

Energy Solutions E-News CAASupport-

News@sce.com

6.

Training and Education Opportunities

– Questions and Feedback: CAASupport-Training@sce.com

– Recordings and upcoming events: www.caasupport.com/training/

Slide 23: Additional Training Opportunities

Script: Additional Trainings scheduled for July:

Incentives Applications: Submitting Through the Online Application Tool (Beginner’s version)

This webinar will introduce SCE’s Online Application Tool. We’ll describe how to register for and use the

Tool to submit Incentives Applications for Express Solutions, noting specific benefits and additional resources.

When: Tuesday, July 15th, 12:00pm – 1:00pm (webinar)

Incentives Applications: Submitting Through the Online Application Tool (Advanced version)

This webinar is intended for CAAs that already have familiarity with the Online Application Tool but would like to like learn more about its advanced features, like utilizing the Tool’s “engineering calculations” option and built-in calculators to submit Incentives Applications for Customized Solutions.

When: Tuesday, July 22nd, 12:00pm – 1:00pm (webinar)

Updates to Lighting Power Density Calculator

This webinar will cover updates made to the Lighting Power Density (LPD) Calculator as a result of recent updates to Title 24. We’ll also provide an overview of how to use the LPD Calculator, focusing on the new changes. Attendance is strongly recommended for Customer’s Authorized Agents who intend to apply for lighting project incentives through Customized Solutions.

When: Tuesday, July 29th, 11:30am – 1:00pm (webinar)

You can send questions, suggestions or other feedback regarding trainings such as this one to

CAASupport-Training@sce.com.

Content:

Online Application Tool (Beginner)

July 15, 2014, 12:00pm – 1:00pm

Online Application Tool (Advanced)

July 22, 2014, 12:00pm – 1:00pm

Updates to Lighting Power Density Calculator

July 29, 2014, 11:30am – 1:00pm

For more details, email CAASupport-Training@sce.com

or watch for updates in The Energy Solutions E-

Newsletter!

Slide 24: SCE Demand-side Management Offerings

Script: Check out SCE’s web site for details on these additional demand-side management offerings.

Content:

Express Solutions

Customized Solutions

HVAC Optimization

Retrocommissioning Program

Demand Response Solutions

Image: Image of a green circle with EE in the middle next to Express Solutions, Customized Solutions,

HVAC Optimization , Retrocommissioning Program. Image of a yellow circle with DR in center next to

Demand Response Solutions.

Slide 25: Title 24 Lighting and Lighting Controls

Content: Thank you for your time.

Please complete your online evaluation.

Download