Design of Electrical Power Systems for Nuclear Power Plants (DS430) Reviewer: Date: 17.10.2013 COMMENTS BY REVIEWER WNA RESOLUTION Com ment No. Para/Line No. Proposed new text Reason Acce pted Accepted, but modified as follows 1 Fig 1,3,4 Add the following note, in a similar manner to that of figure 2 “This figure is only an example for illustration purpose of the described relationship” Otherwise, the figures may be interpreted as a requirement to separate safety from non safety in the single line diagram 2 1.7, 1.10 There should be no requirements in a safety guide, only recommendations. x 1.7 Accepted. 1.10 wording will be modified to … the recommended design requirements… 3 5.42 1.7. It might not be practicable to apply all the requirements recommendations of this Safety Guide to nuclear power plants that are already in operation or under construction. For the “5.42. When it is impractical to provide adequate physical separation and isolation from electrical faults between a safety The current text reads as if physical separation is the usual practice. This is in fact only reflecting a particular national x This clause is related to electrical separation 5.42. When it is impractical to provide adequate Rejec ted Reason for modification/rejection Current wording: 1.12. Figures 1, 2 and 3 show examples of the electrical power systems of nuclear power plants to illustrate the scope of this Safety Guide and terminology used. Further explanation is provided in the list of definitions. Fig 1. This figure provides only an example. Fig 2. This figure provides only an example. Fig 3. Schematic representation of the different parts of the electrical power supplies for a nuclear power plant, as discussed in this Safety Guide, with their boundaries. (Typical for one train.) See “Design and construction rules for electrical equipment of nuclear islands” RCC-E (AFCEN, December 2012), Volume D circuit and a circuit of a lower class function, is not provided the lower class circuit (associated circuit) should be: (a) Analysed or tested to demonstrate that the association does not unacceptably degrade the safety class circuits with which it is associated, (b) Identified as part of the safety division with which it is associated, and (c) Physically separated from other components in the same manner as the circuits of the safety division with which it is associated. […]” 4 5.117 “5.117. The approach for cable separation should be justified. If needed to fulfill safety functions, Physical separation by use of appropriate methods (e.g. distance or physical barrier) should be provided, as practice. In Europe, it is not the case. The proposed modification reflects this matter of fact and his therefore more consensual and not excluding practices in place on 1/3 of NPPs worldwide, at least. Same as it is recommended in 5.129 for example, the approach should be justified. The objective is that the safety functions are fulfilled. It is up to the designer to justify what is the most appropriate method that will allow fulfilling the physical separation and isolation from electrical faults between a safety circuit and a circuit of a lower class function, the lower class circuit (associated circuit) should be: (a) Analysed or tested to demonstrate that the association does not unacceptably degrade the safety class circuits with which it is associated, (b) Identified as part of the safety division with which it is associated, and (c) Electrically Physically separated from other components in the same manner as the circuits of the safety division with which it is associated. x 5.117. Physical separation by use of appropriate methods (e.g. distance or a physical barrier) should be provided between: a. Cables classified as safety and cables without safety 7500 Electrical Separation D 7530 Separation of equipment with different classifications in the same safety train With regard to the electrical supply, separation is achieved by selective protection (C 2300), which prevents an electrical fault on a non-C1 classified outgoing feeder from causing a loss of supply to a piece of equipment with a higher classification. However, under certain conditions specific to each project, it is acceptable for nonC1 classified equipment not to be separated electrically from equipment with a higher classification. In this case, the non-C1 equipment is considered to be associated with the higher classification equipment and is subject to the same separation rules. See “Design and construction rules for electrical equipment of nuclear islands” RCC-E (AFCEN, December 2012), Volume D 7300 Physical separation: D 7310 Separation between different safety trains The cables in, or associated relevant, between: safety function. The guide can neither impose design solutions a. Cables classified as nor specific national practices. safety and cables Otherwise, this would suggest without safety that other practices which are classification; […] recognized as best practices by experienced regulatory bodies are not acceptable. It may be that a combination of a) and / or b) and / or c) might be sufficient to fulfil the safety functions and not necessarily a + b + c. This is why 5.117 cannot be left as currently written. classification; b. Cables belonging to different safety divisions; c. Cables of different voltage classes. 5.118. Separation by safety classification is intended to avoid damage to safety classified cables as a result of failures in systems or cables without safety classification. Separation between cables of different safety divisions is intended to prevent a single hazard from affecting more than one redundant item in a safety system. Separation by voltage classes is intended to prevent the electromagnetic interference expected in higher energy circuits from unacceptably affecting lower energy circuits. This is already contained in revised version before the NUSSC meeting. The objective is to distinguish between safety cables and cables without safety classification. We have deleted “lover safety classifications”. with, a safety train shall not be installed on the same cable tray as the cables in, or associated with, another safety train. Furthermore, the minimum distance between the two cable trays shall be 10 cm. This protects the cables in one train from damage caused by a short circuit in a cable, or the overheating of a power cable, in the other train (with the exception of a fire30 that may be caused by these faults). D 7320 Separation between different safety classifications (in the same train) In this case, no physical separation is required. D 7330 Separation between safety-classified and nonclassified cables Non-classified cables can be routed along cable trays in a safety train. They are then considered to be associated with this safety train and are subject to the requirements in D 7310. 5 6.23 Delete “6.23. It is preferable if A charged auxiliary transformer with few operational load which at least one off-site power circuit failure do not endanger the safety power supply and do not is directly connected to each lead to unwell transient on the core ease the monitoring of the division of the safety power grid connection. Additionally the note on figure 2 systems without intervening precise that this is an example. connections to non-safety buses. See Figs 1, 2, and 3 for examples.” x