DESIGN OF SHELL AND TUBE HEAT EXCHANGER USING SPECIFIED PRESSURE DROP Vimalkumar B. Bilimoria B.E., Pune University, India, 2005 PROJECT Submitted in partial satisfaction of the requirements for the degree of MASTER OF SCIENCE in MECHANICAL ENGINEERING at CALIFORNIA STATE UNIVERSITY, SACRAMENTO FALL 2010 DESIGN OF SHELL AND TUBE HEAT EXCHANGER USING SPECIFIED PRESSURE DROP A Project by Vimalkumar B. Bilimoria Approved by: __________________________________, Committee Chair Akihiko Kumagai, Ph.D. ____________________________ Date ii Student: Vimalkumar B. Bilimoria I certify that this student has met the requirements for format contained in the University format manual, and that this project is suitable for shelving in the Library and credit is to be awarded for the Project. __________________________, Graduate Coordinator Kenneth S. Sprott, Ph.D. Department of Mechanical Engineering iii ________________ Date Abstract of DESIGN OF SHELL AND TUBE HEAT EXCHANGER USING SPECIFIED PRESSURE DROP by Vimalkumar B. Bilimoria The pressure drops used in heat exchange of shell and tube type, the situations are particular and put ahead of the design exercise. In such situations, it is very desirable to make full use of the acceptable pressure drops in order to minimize the size of the heat exchanger. Heat exchanger design is Complex due to large number of design variables like shell diameter, tube pitch, baffle cut, tube diameter, baffle spacing, tube layout etc. in shell and tube type of heat exchanger. This design method is a taking time and intervening procedure. This is mandatory to design thermal and hydro mechanical procedure for this project performance. While fulfilling heat transfer requirements, it has anticipated to estimate the minimum heat transfer area and resultant minimum cost for a heat exchanger for given pressure drops. Effectiveness-NTU approach is the way developed for the design of shell-and-tube heat exchanger. The total number of transmit units, NTU, is scattered between shell and tube side. The methodology accounts for full use of given pressure drops on both sides of exchanger to yield the smallest exchanger for a given duty. _______________________, Committee Chair Akihiko Kumagai, Ph.D. _______________________ Date iv ACKNOWLEDGMENTS It is my distinct honor and proud privilege to acknowledge with gratitude to keen interest taken by Professor Akihiko Kumagai, his ever-inspiring suggestions; constant supervision and encouragement that made it possible to pursue and complete this project efficiently. Here I also thank to the department of Mechanical Engineering and graduate coordinator Professor Kenneth sprott who always guide me on proper way. Finally I thank all the people who extended their support directly or indirectly to make this project a complete success. In addition, it is a great pleasure to acknowledge the help of many individuals without whom this project would not have been possible. v TABLE OF CONTENTS Page Acknowledgments..................................................................................................................... v List of Tables ......................................................................................................................... viii List of Figures .......................................................................................................................... ix Chapter 1. INTRODUCTION ..................... ………………………………………………………… 1 2. LITERATURE REVIEW ................................................................................................... 3 3. SHELL AND TUBE HEAT EXCHANGER .................................................................... 23 3.1 Construction Details of Shell and Tune Heat Exchanger .......................................... 23 3.2 Design Method of Shell and Tube Heat Exchanger .................................................. 27 3.3 Log Mean Temperature Difference Method ............................................................. 28 3.4 Effectiveness – NTU Method.................................................................................... 30 3.5 Calculation of Heat Transfer Coefficient and Pressure Drops .................................. 31 3.6 Heat Transfer Efficient.............................................................................................. 33 3.7 Pressure Drop ............................................................................................................ 36 4. DESIGN OF SHELL AND TUBE HEAT EXCHANGER USING SPECIFIED PRESSURE DROP........................................................................................................... 40 4.1 Input Date................................................................................................................ 40 4.2 Formulation of Design Procedure ........................................................................... 41 4.3 Shell Side Procedure ............................................................................................... 43 4.4 Tube Side Procedure ............................................................................................... 46 4.5 Optimization of Shell and Tube Heat Exchanger.................................................... 48 4.6 Mechanical Design of Shell and Tube Heat Exchanger ......................................... 51 vi 4.7 Tube Sheet .............................................................................................................. 52 4.8 Channel Cover......................................................................................................... 53 4.9 End Flanges and Bolting ......................................................................................... 53 4.10 Baffle Design .......................................................................................................... 53 4.11 Costing of Shell and Tube Heat Exchanger ............................................................ 56 4.12 Shell Cost ................................................................................................................ 56 4.13 Tube Costs............................................................................................................... 56 4.14 Installed Nozzle Cost .............................................................................................. 58 4.15 Front and Rear Head Cost ........................................................................................ 58 4.16 Miscellaneous Cost ................................................................................................. 60 5. DEVELOPMENT OF ALGORITHEM AND OPTIMIZATION FOR DESIGN OF SHELL AND TUBE HEAT EXCHANGER ................................................................... 61 6. RESULT, DISCUSSION, CONCLUSION AND FUTURE SCOPE OF WORK.......... 63 6.1 Area Targeting .......................................................................................................... 67 6.2 Optimization Results of Components of Shell and Tube Heat Exchanger ............... 68 6.3 Cost Analysis ............................................................................................................ 69 6.4 Conclusion ................................................................................................................. 70 6.5 Future Scope of Work ............................................................................................... 71 References ............................................................................................................................... 72 vii LIST OF TABLES Page 1. Table 3.1 Features of TEMA Type Heat Exchangers ................................................ 25 2. Table 3.2 Linear Equations for FT ............................................................................. 30 3. Table 4.1 Baffle Diameter........................................................................................... 54 4. Table 4.2 Baffle Thickness ........................................................................................ 55 5. Table 4.3 Diameter of Holes in Baffle Plate ............................................................... 55 6. Table 4.4 Preparation Cost......................................................................................... 57 7. Table 4.5 Material Cost ............................................................................................. 58 8. Table 4.6 Shell Cost Factors for Selected Shell Constructions.................................. 59 9. Table 6.1 Shell and Tube Heat Exchanger Design Problem-Physical Properties ....... 64 10. Table 6.2 Shell and Tube Heat Exchanger Design Problem-Geometry...................... 64 11. Table 6.3 Comparison of Shell and Tube Heat Exchanger Design-Geometry .......... 67 12. Table 6.4 Comparison of Shell and Tube Heat Exchanger Design-Performances .... 67 13. Table 6.5 Optimized Result of Mechanical Assembly .............................................. 68 14. Table 6.6 Cost Analysis ............................................................................................. 69 viii LIST OF FIGURES Page 1. Figure 2.1 Pressure Drop Constraints ........................................................................ 14 2. Figure 2.2 Area Requirement ..................................................................................... 15 3. Figure 2.3 Region of Feasible Design on the Pressure Drop Diagram ...................... 22 4. Figure 3.1 Fixed Tube Sheet Shell and Tube Heat Exchanger .................................. 24 5. Figure 3.2 Mechanical Clearances in Shell and Tube Heat Exchanger ..................... 32 6. Figure 3.3 Flow Path on Shell Side; A Cross Flow; B Window; C Shell Baffle Leakage; D Tube Baffle Leakage; E Bundle Bypass .......................... 32 7. Figure 3.4 Jh/f Versus Re for Shell Side Flow ............................................................. 45 8. Figure 3.5 Jh/f Versus Re for Tube Side Flow…. ........................................................ 48 ix 1 Chapter 1 INTRODUCTION Heat exchangers are devices in which heat is transfer from one fluid to another. The most commonly used type of heat exchanger is a shell-and-tube heat exchanger. Shell-and-tube heat exchangers are used extensively in engineering applications like power generations, refrigeration and air-conditioning, petrochemical industries etc. These heat exchangers can be designed for almost any capacity. The main purpose in the heat exchanger design is given task for heat transfer measurement to govern the overall cost of the heat exchanger. The heat exchanger was introduced in the early 1900s to execute the needs in power plants for large heat exchanger surfaces as condensers and feed water heaters capable of operating under relatively high pressures. Both of these original applications of shell-and-tube heat exchangers continued to be used; but the design have become highly sophisticated and specialized, subject to various specific codes and practices. The broad industrial use of shell-andtube heat exchangers known today also started in the 1900s to accommodate the demands of emerging oil industry. The steadily increasing use of shell-and-tube heat exchangers and greater demands on accuracy of performance prediction for a growing variety of process conditions resulted in the explosion of research activities. These included not only shell side flow but also, equally important, calculations of true mean temperature difference and strength calculations of construction elements, in particular tube sheets. The objective of the thesis is to formulate the design algorithm and optimization procedure for a shell-and-tube exchanger in which exchanger geometry is determined from 2 required performance for fixed pressure drops. First step in the effective consideration of allowable pressure drops is to establish a quantitative relationship between velocity, friction factors, pressure drop of the stream and number of transfer units. The solution of this equation provides the core of such an algorithm. The first chapter deals with the brief introduction of shell-and-tube heat exchangers. The second chapter gives the development in the design methodology considering pressure drops as constraint over the years for shell-and-tube heat exchangers. The third chapter gives the brief outlines of various methods of design of shell-and-tube heat exchangers and constructional details of various class of shell-and-tube heat exchanger. In the fourth chapter, the design procedure is developing for a given heat exchanger specifications and pressure drops. In this design, both the thermal and mechanical design is doing for a tube and shell exchanger. Various cost equations are developing for tubes (including preparation and material), shell, nozzles, front and rear end heads, baffles, and saddle of exchanger. The algorithm for exchanger with specified pressure drops is present in the fifth chapter. In the sixth chapter, the heat exchanger design derived using the new algorithm is comparing with the original one. The results and conclusion of the present work are discussing in the sixth chapter. 3 Chapter 2 LITERATURE REVIEW Detailed design of shell-and-tube heat exchanger generally proceeds through the testing of a range of potential exchanger geometries in order to find those that satisfy three major design objectives: 1. Transfer of required heat duty 2. Specified cold side pressure drop 3. Specified hot side pressure drop The allowable pressure drops determine the operating cost of heat exchanger in the process; they also determine the capital requirement of the installed heat exchanger surface area. Different authors have long recognized the importance of considering pressure drops during heat exchanger analysis. McAdams [1] was one of the earliest workers to quantitatively demonstrate this. His analysis was simple and based on tubular heat exchanger. By taking into account the cost of power and fixed cost of the exchanger, per unit heat transferred, simple expressions for estimating the optimum mass velocities for both inside tubes and outside tube fluids are developed. However, his equations are deriving on the basis that each side of the exchanger can be treating independently of the other. It is assume that the streams do not interact and the effect of opposing resistance is neglecting. This is an erroneous assumption. 4 Jenssen [2] in an attempt to provide a quickly and general method for estimating the economic power consumption in plate exchangers introduced the so-called ‘J’ parameter (i.e. the specific pressure drop per heat transfer unit parameter). He produced graphs showing economic optimum based on the assumption that the streams on the either side the exchanger have the same flow rates and the same physical properties. The use of such graphs in design only requires the knowledge of the ratio of the capital cost influence to the power cost influence. The capital cost influence is given as the annual investment increment for added unit heating surface area. The power cost influence is the annual unit power cost. One major weakness in this work that has perhaps limited its practical application is the assumption that the streams have identical fluid properties and identical geometries. These are highly limiting assumptions. While the method may apply under restricted conditions to plate exchangers, its extension to shell-and-tube heat exchangers appears too far from straightforward. Since the cost of heat exchanger, is usually a major item in the overall process, the design of heat exchangers based on minimum total cost. The total annual heat exchanger cost to be minimized may be represented by the following general equation: TC AK F C Ao QtCu 3.5 4.75 A T hT tKT A S tK S hS C pu T1 T2 T1 T2 FT T2 T1 Q ln T2 T1 Dt 1 RF A Dti hT hS Where Q = Heat transfer rate C Ao = Installed cost of heat exchanger per unit of outside heat transfer area (2.1) 5 K T Cost for supplying fluid through the inside of the tubes K S Cost for supplying fluid through the shell side of the exchanger C pu Cost of utility FT Correction factor on logarithmic-mean temperature difference h Film heat transfer coefficients t Hours of operation per year RF Combined resistance of tube wall and scaling or dirt factors T Temperatures on shell or tube side Lagrangian multiplier Dimensional factors for evaluation of power loss per unit heat transfer coefficients TC = Total cost Sidney and Jones [3] have developed separate programs for the price optimum design of shell-and-tube heat exchangers for four cases: (a) no phase change occurs, pumping costs of tube side and shell side is given. Estimation of inside heat transfer coefficient is accomplished by differentiating equation (2.1) w.r.t. hT and A. Addition of the two differential equations eliminated A and , yielding an equation in which hT is the only unknown. Estimation of inside heat transfer coefficient is accomplished by differentiating equation (2.1) w.r.t. h S and A. Elimination of A and the multiplier yield an equation from which h S can be computed directly., (b) no change in phase and negligible costs on tube side: Under these conditions, the outside heat transfer coefficient and the tube fluid velocity are fixed. Based on the assumptions that hT is constant and CT is equal to zero. The optimum value of h S is determined by differentiation of 6 equation (2.1)., (c) no change in phase and negligible pumping costs on shell side: Under these conditions, the outside heat transfer coefficient and shell side velocity are fixed. Estimation film heat transfer coefficient on shell side is accomplished in a similar manner to that used in case (b) but using a Nusselt type equation and the pressure drop equation for shell side, and (d) change in phase on shell side: Under this condition, tube side power cost are significant but the pressure drop and power costs for the fluid on the shell side are assumed to be zero and shell side heat transfer coefficient is assumed to be constant. Optimum tube diameter is not obtained since the tube diameter has little effect on the total cost Steinmeyer [4, 5] has attempted to apply Jenssen’s [2] approach to shell-and-tube heat exchangers. He produced separate relationships for shell side and tube side geometries. However, in producing the relationships he, like McAdams [1], assumed that he could ignore the conditions on the opposite side of the exchanger. Again, this assumption is incorrect and application on his procedure can lead to serious errors. The result of McAdams [1], Jenssen [2] and Steinmeyer [4, 5] can be considered very useful. Their analysis on single heat exchanger at the optimum, the annual power cost ranges from 20% to 50% of the heat exchanger cost. The lower value is valid for non-viscous liquids and the higher value is valid for high viscosity liquids, with low viscosity liquids and gases being in contact. This ratio can be used to warn (both the heat exchanger designer and the process network designer), whether or not they are using reasonable coefficients. Peter and Timmerhaus [6] recognized the importance of optimizing tube side pressure drop; shell side pressure drop and heat transfer area simultaneously. Consequently, they produced the most detailed and useful work to date on a single shell-and-tube heat exchanger optimization. The problem with their method however, is that it is restricted to shell-and-tube heat exchangers fitted with plain tube. Extension to other exchanger types requires new equations. No guidance is 7 given on how to generate these equations. Their results like all other previous authors are only applicable to only pumped systems. Their method cannot be applied for shell-and-tube heat exchangers with the specified pressure drops. Kovarik [7] has formulated the design procedure as the solution of five simultaneous equations for a cross flow heat exchanger. The analysis of these equations yields general properties of optimal cross flow heat exchanger. He has developed the optimization function, which he defines J as the ratio of performance to cost, which is given as below J 1 Cs C p Q (2.2) Cs is the cost component related to the heat exchanger size, and Cp is the cost component related to the pumping power. The position of the maximum J coincides with the minimum of the first term in the denominator of the right hand side of the equation (2.2), and is independent of the value of the energy cost factor. Therefore an optimal heat exchanger is optimal for any cost of energy. A necessary condition for J to reach its maximum is the simultaneous vanishing of its partial derivative with respect to all free variables. For any variable X i , this means Q TC TC Q X i X i TC 2 0 (2.3) where TC is the total coat TC C s C p (2.4) As Q and TC are inevitably positive, equation (2.3) implies Qi X i TC TC X i (2.5) 8 Where Qi is the logarithmic derivative of Q with respect to X i : Qi X i Q QX i (2.7) Qi is defined as the sensitivity of output to variable X i . The free variables can be flow lengths and capacity rates. The model to be analyzed is a section that is rectangular and prismatic in shape, consisting of passages bordered by heat transfer surfaces of known properties. In a cross flow heat exchanger, the flow lengths are independent and the optimization scheme can be applied with greater generality than with parallel flow and counter flow cases like shell-and-tube heat exchanger. Polley, Shahi and Nunez [8] have developed the rapid design algorithm for both shelland-tube exchanger and compact heat exchanger. They are based on full use of the allowable pressure drops of both the streams being contacted. In case of shell-and-tube heat exchanger algorithm, it is assuming that the best shell side performance can be gained by making baffle window flow velocities and bundle cross flow velocities equal. This in turn leads to a ‘similarity concept’ that can be used for the derivation of simple performance equation from of shell side model. They have not shown theoretically that how much shell side performance is sensitive to the window/cross flow area ratio. They have developed and shown how simple relationship between fluid exchanger pressure drop, exchanger area and film heat transfer coefficient can be used to rapidly design. For the tube side and shell side performance, the following relationships exist: PT K T Ahio3.5 (2.8) 9 PS K 1 A K 2 hS2 (2.9) The constants appearing in the above equations are complex functions involving shell geometry, ideal friction factors and ideal heat transfer factors and are based on Delaware method. These two equations are solving together with the basic design equation: Q UAFT TLM (2.10) 1 1 1 RF U hS hT (2.11) The three simultaneous equations (2.8, 2.9 and 2.10) are then solved to yield exchanger area and heat transfer coefficient for given pressure drop on both sides of shell-and-tube heat exchanger. This in turn allows the calculation of velocities and shell diameter and baffle cut. The shell side friction factor, heat transfer j factor, baffle cut and shell diameter are all set at standard initial value. This allows the initial estimate of tube count and baffles spacing, and subsequently leakage and bypass areas and correction factors to be made. From detailed geometry actual friction factors and j factor are estimated and initial assumption are tested and updated if necessary. However, the method is restricted. The first restriction is that the pressure drops referred to in the above equations is that associated with the flow through the exchanger bundle. No account is taken of any nozzle or header pressure drops. Allowance for these must be made ahead of design and checked after design. This restriction is not considered here a serious impediment. The second restriction is the use of the Kern’s correlations, which are generally considered too inaccurate for use in modern exchanger design. In the derivation of relationship on shell side performance (equation (2.9)), the assumptions made have not tested in theory. When designing shell-and-tube heat exchangers, achieving the full use of the allowable pressure drops from experience can be both difficult and dangerous. There is always the 10 possibility that it is not utilized properly. The allowable pressure drops of a stream will vary from one system to another since it is dependent on the interaction between the streams. It will also vary from one economic scenario to another. It is important that the full utilization of allowable pressure drops be achieved for the streams in a shell-and-tube heat exchanger design as far as possible. Furthermore, it is also important that once the allowable pressure drops of the stream have been set, full advantage must be taken of them in order to obtain optimum heat exchanger area in the design. Jegede and Polley [9] have considered the trade-offs involved in the optimum design of shell-and-tube heat exchanger. They have shown how full use can be made of the allowable pressure drops and shown how the optimum heat exchanger size can be determined. The procedure is based on Kern’s correlations. For the tube side of the exchanger the pressure drop relationship takes the form given by the equation (2.8). Similarly, for the shell side flow the relationship takes the form given by PS K PS AhS5.1 (2.12) The constants are given below: KT K1t Dti 4V0 Dt l K 2t 3.5 (2.13) K1t 0.092 Dti Dti (2.14) K 2t 0.023k Dti Pr 0.33 Dti (2.15) K PS K1S K 2 S K 3S (2.16) 0.2 0.8 1.79 S De 2 De 3.81 K 1S 1.8 K 2 S 4Ltp Ltp D0 2 D0V0 (2.17) (2.18) 11 K 3S 0.36k De Pr 0.33 De S 0.55 (2.19) ∆PT, ∆PS, Q and ∆TLM are specifying in the design requirements. Three equations (2.8, 2.10, and 2.12) with only three unknowns (hT, hS and A) are solved simultaneously and as such rapid solution is possible. The procedure is independent of whether the streams involved are pumped liquids, compressed gases, or a combination of these. A general procedure for heat exchanger design has been presented in the Heat exchanger Design Handbook (HEDH), but no precise criteria for determining the baffle spacing has been offered, and the emphasis is only on its permissible range of application. Saffar-Avval and Damangir [10] have established the optimization procedure to calculate the optimum baffle spacing and the number of sealing strips for all types of shell-and-tube heat exchangers. Here the objective function J is defined as: J W1 A W2W (2.20) W1 is the heat transfer area weight factor, W2 is the pumping power weight factor, and W is power. The weight factors are defined as: W1 Cp Cs , W2 Cs C p Cs C p (2.21) It is concluded that, non-dimensional value of ReS.PrS.exp(Dr/Dti) for each optimization design is well correlated with heat transfer area weight factor, W1. These results for each type of exchanger are presented as follows: E-Type shell-and-tube heat exchanger: Re S . PrS .e Dr / Dt 8.89756 12.23475W1 6.24858W1 2 (2.22) 12 Floating head type shell-and-tube heat exchanger: Re S . PrS .e Dr / Dt 6.48571 23.67138W1 6.08711W1 2 (2.23) U-tube shell-and-tube heat exchanger: Re S . PrS .e Dr / Dt 5.98419 28.88928W1 14.13602W1 2 (2.24) Where the shell-side Reynolds number is . M D Re S S t S Sm (2.25) Where S m is the cross flow area, given as: D S m Lbc Lbb DS Lbb Dt 1 t L tp Where Dr Reference diameter [25.4mm] DS Shell diameter Lbb Inside shell diameter to bundle clearance Dt Tube outside diameter Lbc Baffle spacing Ltp Tube pitch . M Mass flow rate (2.26) 13 Once the Reynolds number is obtained, the cross flow area S m is calculated and hence also optimum baffle spacing. They have studied the effect of baffle spacing on heat transfer area and pressure drops, and conclude that baffle spacing has a decisive effect on pumping power and noticeable on required heat transfer area. Poddar and Polley [11] present a new design heat exchanger through parameter plotting. It can be used with any existing state-of-the-art exchanger-rating program. Rather than systematically exploring the whole of the available exchanger sizes (diameters and tube length), it determines the relationship between duty and tube length, pressure drop and tube length, etc. for a range of diameters. This information is then used to clearly indicate the full range of geometries that are suitable for a given duty and given constraints. Most state-of-the-art programs for the rating of shell-and-tube heat exchangers present a wealth of information on exchanger performance. Virtually all of these programs will inform the user of the effective mean temperature difference, the overall heat transfer coefficient, the tube side pressure drop and the shell side pressure drop for a single baffle space. By running a rating program for a series of shell diameters with a selected baffle configuration all of the performance information can be related to shell diameter. The importance of maximum allowable pressure drop can be determined as follows. First, allowance is made for exchanger nozzles. Normal design practice is to design the exchanger nozzles such that they absorb just a small percentage of the total allowable value. So, for each shell diameter studied, the tube side pressure drop is per unit length is determined. By dividing the allowable tube side pressure drops by this value, the length of shell-and-tube heat exchanger that coincides with the absorption of the allowable pressure drop is determined. The relationship between shell diameter and the tube length for maximum pressure drops is shown in Figure 2.1. Acceptable design lie above and to the left of this line; the design space has now been 14 reduced to EFIJH. The data generated on shell side pressure drop per unit length of exchanger can be treated in exactly the same way. The result is also incorporated in Figure 2.1 Figure 2.1 Pressure Drop Constraints [11] Finally, the information on overall heat transfer coefficient and effective mean temperature difference can be used to determine the area needed for the given duty as a function of shell diameter. For each diameter, this can be related to tube length necessary for the heat transfer duty. This relationship can now be placed on the plot. The result could be that shown in Figure 2.2. Acceptable designs are those that are above and to the right of this line, the design space finally reduced to MFKN. The procedure is a graphical technique and lays bare the influence of the ‘secondary constraints’ on design. This design procedure suffers from limitation like the one some of the constraints are not considered (e.g., on shell side velocity). It cannot be readily considered (e.g., on baffle spacing) in the approach proposed by authors, who plotted shell diameter versus tube length. In addition, they did not establish any targets for minimum area and cost. 15 Figure 2.2 Area Requirements [11] Some designers have a conceptual problem in envisioning the cost of buying a heat exchanger or the cost of paying the electricity to supply the pressure needed to overcome heat exchanger pressure drop on the same basis as the lost value of unrecovered thermal energy represented by the temperature driving force (∆T). To overcome these problems, Steinmeyer [12] establishes the development of the optimum ∆T and ∆P relationships from a single turbulent energy dissipation relationship, and the quantitative comparison of the relative “bills” of the three components of heat exchanger costs. Also unique is the comparison of the conventional shelland-tube relationships to the prediction from energy dissipation. The most remarkable statement he made in his paper is that at the optimum, the bill for pressure drop for the life of the heat exchanger is one-third the life time bill for heat transfer area. The statement is known as the “onethird rule”. The one-third rule provides a way of checking for proper allocation of pressure drop. A thermo economic optimization analysis is presented by Soylemez [13] yielding simple algebraic formulas for estimating the optimum heat exchanger area. The P1-P2 method is used in the study, together with the well-known Effectiveness-NTU method, for thermo economic 16 analyses of three different unmixed type heat exchangers. Variable parameters used in formulating the thermo economical optimum heat exchanger area are listed as: technical life of the heat exchanger N , area dependent first cost of the heat exchanger C s , annual interest rate d , present net price rate of the energy i , annual energy price rate, annual total heat transfer Q , overall heat transfer coefficient U , maximum temperature differential Tmax , and annual total operation time t . First of all for the C = 0 case, the following optimum heat exchanger area Aopt formula is as: Aopt . M Cp P2 C s min ln U UP1C e Tmax t (2.27) The P1 and P2 values are defined by the following: If i d N 1 1 i P1 1 d i 1 i If i d P1 N 1 i (2.28) (2.29) P2 1 P1 M Rv 1 d . N (2.30) If i d then, the payback period N p is P2 C s Ad i ln 1 C M. C T t e p max min Np 1 i ln 1 d (2.31) 17 If i d , then, the payback period N p is: Np P2 1 i C s A . Ce M C p Tmax t 1 e NTU C 1 min (2.32) Similarly, the optimum heat exchanger area, Aopt, and the payback period can be determined by using the same procedure for the parallel flow exchanger as: Aopt . M Cp P2 C s min ln 1 C U UP1C e Tmax t (2.33) If i d : P2 C s Ad i ln 1 C M. C T t e p max min Np 1 i ln 1 d (2.34) If i d : Np 1 i C s A1 C Ce mC p Tmax t 1 e 1C NTU min . (2.35) Finally, for countercurrent heat exchanger, C = 1, case, the following are evaluated: Aopt . M Cp min U P1Ce Tmax tU 1 P2 C s (2.36) 18 If i d : C s Ad i 1 NTU ln 1 NTUC m. C T t e p max min Np 1 i ln 1 d (2.37) If i d : Np 1 i C s Aa NTU (2.38) . C e m C p Tmax t.NTU min Murlikrishna and Shenoy [14] have proposed a methodology that graphically defines the space of all feasible designs. Given the large number of geometrical parameters, this space is quite complex in nature. It is demonstrated that this complex space can be conveniently represented on a two dimensional plot of shell side versus tubes side pressure drop. Equations are derived for the various constraints and then plotted on the pressure drop diagram to define the region of feasible design. The tube side pressure drop is given by: PT K T 1 L DS a 2 K T N tp n 2 mt 3 m t KT1 KT 2 1 DS a 2n NS 4 M T t T T mt 2 m t 2 m t (2.35) bDt n 2 m t 5 m t Dti (2.36) 19 20N tp NS M T bDt . 3 KT 2 2 2n T 2 Dti 4 (2.37) For smooth pipes, the correlations for friction factors are f T K T Re T mt (2.38) The shell side pressure drop is given by the following expression: PS K S1 K S1 Rbs L 42 ms DS (2.39) 3ms 2 K S De ms 1 . NS M S 2 ms S ms S 1 Dt Ltp 2 ms (2.40) The shell side friction factor correlation is of the form: f S K S Re S ms (2.41) where typical values of KS and ms are 0.4475 and –0.19 respectively. In a manner analogous to that used in deriving equations (2.35 and 2.39), the heat duty equation is rewritten below as function of tube length, shell diameter and the baffle spacing to shell diameter ratio. For Re T 2100 DS 1.1 Rbs 0.55 L1 / 3 DS a n / 3 LDS a K 2 K4 K1 K3 (2.42) 20 For 2100 < Re T 10000 1.1 0.55 1 DS Rbs L DS a K 2 K4 2/3 K1 D K6 K 5 1 ti2 / 3 125 2n / 3 L D a S (2.43) For Re T > 10000 D S 1.1 Rbs 0.55 DS a 0.8 n LD S a K 2 K4 K1 K7 (2.44) Where 0.36k S 1/ 3 D K1 PrS e De S . 0.55 MS 1 D t 0.55 Ltp 0.55 QbDt K2 Dt NS Ft TLM (2.45) n (2.46) 1/ 3 1/ 3 n/3 . 4 M T N tp bDt 1.86kT 1/ 3 K3 PrT Dt T 1 / 3 K4 Rf Dt Dt ln 2k Dti (2.47) (2.48) 21 K5 0.116kT 1/ 3 PrT Dt . 4MT K6 2/3 (2.49) N bD 2/3 tp 2n / 3 t (2.50) Dti T 2 / 3 0.8 0.8 0.8 n . 4 M T N tp bDt 0.023kT 1/ 3 K7 PrT Dt Dti T 0.8 (2.51) The tube side pressure drop relationship (equation 2.35), the shell side pressure drop relationship (equation 2.39) and the heat duty relationship (equations 2.42, 2.43, and 2.44) form three equations in five variables ( PT , PS , DS , L, and Rbs ). Thus, there are two degrees of freedom. The shaded region in Figure 2.3 defines the region of all possible design satisfying the constraints. The methodology presented by them is equation based. If two of the five are specified, then the remaining can be solved. Although every point in this feasible region corresponds to a unique design that satisfies all the constraints, the designer may seek optimal design, i.e., designs that meet certain objectives like minimum area or minimum cost. The minimum area design will usually require the allowable pressure drops to be utilized to the maximum extent, and the point can be readily located within the feasible region. The minimum area design corresponds to minimum capital cost of the heat exchanger; but to minimize the total annual cost, a simple techno-economic analysis is needed to determine the optimum pressure. 22 Figure 2.3 Region of Feasible Design on the Pressure Drop Diagram [14] Literature has been reviewed for design of shell-and-tube heat exchangers where pressure drop is considered as main constraint. All of the methods have some essential limitations, like use of Kern’s correlation, less use of specified pressure drops. The methods discussed above proceeds through the examination of the performance of a range of potential geometries. This leads to the longer execution of program. To reduce the execution time, a quantitative relationship must be derived to arrive at the initial size of a heat exchanger. 23 Chapter 3 SHELL AND TUBE HEAT EXCHANGER By far the most common type of heat exchangers to be encountered in the thermal applications is shell-and-tube heat exchangers. These are available in a variety of configurations with numerous construction features and with differing materials for specific applications. This chapter explains the basics of exchanger thermal design, covering such topics as: shell-and-tube heat exchanger components; classification of shell-and-tube heat exchangers according to constructions. 3.1 Constructional Details of Shell and Tube Heat Exchanger It is essential for the designer to have a good knowledge of the mechanical features of shell-and-tube heat exchangers and how they influence thermal design. The principal components of shell-and-tube heat exchangers are: Shell Shell cover Tubes Channel Channel cover Tube sheet Baffles Nozzles 24 Other components include tie-rods and spacers, pass partition plates, impingement Plate, longitudinal baffles, sealing strips, supports, and foundation. The Tubular Exchanger Manufacturer is Association, TEMA, has introduced a standardized nomenclature for shell-andtube heat exchangers. A three-letter code has been used to designate the overall configurations. The three important elements of any shell-and-tube heat exchangers are front head, the shell and rear head design respectively. The Standards of Tubular Exchanger Manufacturers Association (TEMA) [15] describes the various components of various class of shell-and-tube heat exchanger in detail. Figure 3.1-Fixed Tube Sheet Shell and Tube Heat Exchanger [15, 16] 25 Type Type P Type S Type T Type U Type L,M,N Outside Floating Pull U Tube W fixed Packed Head with Through Bundles Externa tube Floating Backing Floating -lly sheet Head Device Head Sealed Floating Tube sheet Relative cost 2 4 5 6 1 3 Provision for Expansi Floating Floating Floating Individual Floatin- Thermal. on Joint Head Head Head Tubes Free g Head Expansion in Shell Bundle Rem- No Yes Yes Yes Yes Yes Yes Yes Yes Yes Outside Yes 1=Least cost to Expand ovable Tubes Replaceable Tube side Mechanically Cleanable Row Only Yes Yes Yes Yes No Yes 26 Shell side No Yes Yes Yes Yes Yes Yes No No Yes Yes No No Yes Yes Yes Yes Yes No No Yes Yes No No Possible Tube Any Any Any Any Any Even One or side Passes Number Number Number Number Number Two Mechanically Cleanable Double Tube sheet Possible Bundle Replaceable Internal Gaskets Table 3.1 Features of TEMA Type Heat Exchangers [17] Use of multiple tubes because of that is increasing the heat transfer area. Reason of increasing heat transfer area is increase the velocity of fluid and lower effective ∆T. There is different type of shell available, all shell are identified regarding the diameter .Basically sizes of the shell are 8, 10, 12 inches. We find 2 inches of increment every step start from 13 inches to 25.From 25 to 39 we find 2 inches increment and after 39 to 72 we find 3 inches increment in shell. Tube size, which type of materials and array are primary criteria of designing of tube and shell type of mat exchanger. After done this step hydraulic design will be done on automatically. 27 Small tube gives less cost with good thermal conductivity and Use of multiple tubes because of that is increasing the heat transfer area. Reason of increasing heat transfer area is increase the velocity of fluid and lower effective ∆T. It will create less shell area and size. Normally two arrays are available, triangular array produces the more tube with lower cost for particular heat transfer unit. We can control the pressure difference in square type of array so it is more preferable rather than the triangular type of array. When the cleaning require because of mechanical work, on that time square type of array are preferable. Wide pitch is used in this type of array and 60o and 90o arrays have a tendency to create a channeled flow. So that way fluid have a tendency to pass between two row of tube so there si not need to complete the full round of flow. This is happen in each tube so it is big gain for evaporators and condensers for vapor distributions. With the close type of temperature, difference and tube side of pressure difference generally start to design the heat exchanger with two or more tube passes. The way is to established lot of heat exchanger with normal way. Front and rear end the pass particles are installed in the tube side. For the multi-pass tube arrangement the stress are developed at high joint. With the pressure and temperature difference, high tensile and compressive load located the tube side. 3.2 Design Methods of Shell and Tube Heat Exchangers First step in designing of heat exchanger, there is two way to design heat exchanger. 1. LMTD 2. NTU Method. General equation of heat exchanger is Q UA0 FT TLM (3.1) 28 Where ∆T is the Temperature difference between hot and cold fluid In terms of energy flow for heat exchanger, we can use this equation for hot fluid, . Q M C p Th (3.2) Where ∆T is the Temperature difference between hot fluids In terms of energy flow for heat exchanger, we can use this equation for cold fluid, . Q M C p Tc (3.3) Where ∆T is the Temperature difference between hot fluids 3.3 Log Mean Temperature Difference Method Heat flows between the hot and cold streams due to the temperature difference across the tube acting as a driving force. The difference will vary with axial location. Average temperature or effective temperature difference for either parallel or counter flow may be written as: TLM LMTD T1 T2 T ln 1 T2 (3.4) Normal practice is to calculate the LMTD for counter flow and to apply a correction factor FT, such that TLM FT .TLM ,CF (3.5) 29 The correction factors, FT, can be found theoretically and presented in analytical form. The equation given below has been shown to be accurate for any arrangement having 2, 4, 6… 2n tube passes per shell pass. R2 1 1 P ln R 1 1 PR 2 P 1 R R2 1 ln 2 P 1 R R 2 1 F1 2 (3.6) Where the capacity ratio, R, is defined as: R T1 T2 t 2 t1 (3.7) The parameter P may be given by the equation: P 1 X 1 / N SHELL R X 1 / N SHELL (3.8) Provided that R 1 in the case that R 1 , the effectiveness is given by: P N Shell P0 P0 .N Shell 1 (3.9) P0 t 2 t1 T1 t1 (3.10) X P0 .R 1 P0 1 (3.11) Gulyani and Mohanty [18] give alternate equations for the calculation of temperature correction factors. They have derived linear equations for the same and established that the factor is below 0.5 % error. They are given in Table 3.1. 30 NShell FT 1 1.208 G + 0.8037 2 0.237 G + 0.961 3 0.1202 G + 0.9835 4 0.0661 G + 0.991 5 0.0429 G + 0.994 Table 3.2 Linear Equations for FT [18] Note: G 1 P0 1 R (3.12) 3.4 Effectiveness-NTU Method In the thermal analysis of shell-and-tube heat exchangers by the LMTD method, an equation (3.1) has been used. This equation is simple and can be used when all the terminal temperatures are known. The difficulty arises if the temperatures of the fluids leaving the exchanger are not known. In such cases, it is preferably to utilize an altogether different method known as the effectiveness-NTU method. Effectiveness of shell-and-tube heat exchanger is defined as: The group C S TSi TSo C T TTi T To Cmin TSi TTi Cmin TSi TTi UA is called number of transfer units, NTU. C min Effectiveness for shell-and-tube heat exchanger can also be expressed as: (3.13) 31 UA C , min C min C max Where (3.14) Cmin C S CT (depending upon their relative magnitudes). or C max CT CS Kays and London [19] have given expressions for shell-and-tube heat exchangers. Some of their relationships for effectiveness are given below: For one shell pass, 2, 4, 6 tube passes 2 1 exp NTU 1 1 C min 2 1 21 C min 1 C min 2 1 exp NTU 1 1 C min (3.15) For two shell pass, any multiple of 4 tubes 1 C 1 min 2 1 1 2 1 C 1 min 1 1 1 2 C min 1 (3.16) 3.5 Calculation of Heat Transfer Coefficient and Pressure Drops Flow across banks of tubes is, from both constructional and physical considerations, one of the most effective means of heat transfer. However, it is recognized quite early that ideal tube bank correlations, if applied to shell-and-tube heat exchangers, needed substantial corrections. In 1951, Tinker presented what has become a classical paper on flow through the tube bundles of shell-and-tube heat exchanger. He pointed out that a number of differing paths existed for flow and argued that the assumption that all of the fluid passed through the whole of the bundle was false. This was clearly demonstrated by his observations of the performance of exchangers handling highly viscous oils. He then proceeded to propose a flow model based on 32 variety of flow paths cross flow, bundle bypass, tube-baffle leakage and shell-baffle leakage. These paths are shown in Figure 3.6 and 3.7. This contribution became watershed in shell-andtube heat exchanger technology. Up until that, simple correlations, similar to those used for tubes, had been produced and used for shell side performance. Following Tinker’s work researchers concentrated on developing the sophisticated performance model for heat exchanger, which recognized the existence of flow paths. Figure 3.2 Mechanical Clearances in Shell and Tube Heat Exchanger [8] Figure 3.3 Flow Paths on Shell Side, A Cross Flow; B Window; C Shell-Baffle Leakage; D Tube-Baffle Leakage; E Bundle Bypass [8] 33 3.6 Heat Transfer Efficient The Bell’s Delaware method uses ideal tube bank j h and f factors and then corrects directly the resulting hi and ∆Pi for derivations caused by the various split streams. The ideal tube bank factor j and f is given as: 1.33 j h a1 L D tp t a3 10.14 Re a4 1.33 Re a2 And f b1 L D tp t b3 10.14 Re b4 Re b2 (3.17) For possible computer applications, a simple set of constants is given in [20] for the curve fit of the above form. The ideal heat transfer coefficient on shell side is defined as: . hiS jC p M Pr 2 / 3 (3.18) The shell side actual heat transfer coefficient is given in equation: hS hiS jb jc jl j s j r (3.19) jc is the correction factor for baffle cut given by: DS DS Bc cos 1 2 cos 1 sin 1 D L D D L D 50 bb t S bb t S jc 1.27 1.44 180 2 Bc 1 50 jb is the correction factor for bundle bypass flow is given by: 100 N ss L pp Lbb 0.5Dt 1 jb exp 1.25 Lbb Ltp,eff DS Lbb Dt Ltp Dt 50 Bc jl is the correction factor for baffle leakage flow is given as: (3.21) 34 jl 0.441 rs 1 0.441 rs e 2.2 rlm (3.22) rs S sb S sb S tb (3.23) rs S sb S tb Sm (3.24) Where S m is the cross flow area at the bundle centerline, is given by D Lbb Dt Ltp Dt S m Lbc Lbb S Ltp,eff (3.25) S sb is the shell-to-baffle leakage area, given by B S sb 0.00436 DS Lsb 360 2 cos 1 1 c 50 (3.26) S tb is the tube-to-baffle hole leakage area, is given by 2 2 S tb Dt Ltb Dt N tt 1 Fw 4 (3.27) j s is the correction factor for variable baffle spacing is presented as: 0.4 L L N b 1 bi bo Lbc Lbc js L L N b 1 bi bo Lbc Lbc (3.28) jr is the correction factor for adverse temperature gradient, which is given as: For Re S 20 j r j r r 1.51 Nc 0.18 (3.29) 35 For 20 Re S 100 20 Re S j r j r r j r r 1 80 (3.30) For Re S 100 jr 1 (3.31) Nc is the total number of tube rows crossed in the entire heat exchanger: N c N tcc N tcw N b 1 (3.32) In addition, the shell side heat transfer coefficient is given by the following Nusselt number correlation: hS De 0.55 1/ 3 0.36 Re S PrS kS w 0.14 (3.33) Equation (3.34) is given Kern and Krauss [21, 22]. Various correction factors for heat transfer coefficient for shell side flow are calculated as per suggested in the Delaware method. The correlations for tube side Nusselt number are: For Re T 2100 hT Dti D 1.86 Re T . PrT . ti kT L 1/ 3 w 0.14 (3.34) For 2100 < Re T 10000 Dti 2 / 3 hT Dti 2/3 1/ 3 0.116 Re T 125 PrT 1 L w kT 0.14 (3.35) For Re T > 10000 hT De 0.8 1/ 3 0.023 Re T PrT kT w 0.14 (3.36) 36 3.7 Pressure Drop The shell side pressure drop [20] is calculated as a summation of the pressure drops for the inlet and exit sections Pe , the internal cross flow sections Pc , and the window sections Pw . For a shell-and-tube exchanger, the combined pressure drop is given as: PS Pc Pw Pe (3.37) The zonal pressure drops are calculated from ideal pressure drop correlations and correlation factors, which take account of bundle bypassing and leakage effects. The baffled cross flow pressure drop is given by: Pc N b 1Pci Rb Rl (3.38) The end zone pressure drop is given by: N Pe 2Pci Rb 1 tcw Nc (3.39) and, the window pressure drop by: Pw N b Pwi Rl (3.40) The correction factors for shell side pressure drop are given as: Rl exp 1.331 rs rlm L Rs bc Lbo 0.151 rs 0.8 2 n L bc Lbi (3.41) 2n (3.42) 37 S Rb exp 3.7 b Sm 100 N ss L pp 1 3 50 Bc (3.43) According to Kern and Krauss [22], the shell side pressure drop is given by the following expression: 2 f S GS DS N b 1NS 2 PS (3.44) De S w 0.14 The shell side friction factor correlation is of the form: f S 0.4475 Re S 0.19 (3.45) The tube side pressure drop is given by: 2 f T GT LN tp NS 1.25GT N tp NS PT 0.14 T Dti T w 2 2 (3.46) The first term is due to friction and the second term is due to return losses. Most of the pressure drop is due to surface friction inside the exchanger in an attempt to increase the heat transfer. Therefore, only the straight tube pressure is considered. For smooth pipes, the correlations for friction factor are of the form: f T K T Re T mt (3.47) Note that K T 16, mt = -1 for Re T 2100 , whereas K T 0.046, mt -0.2 for Re T 2100 The overall heat transfer coefficient (U) is related to individual heat transfer coefficient as: D D 1 1 1 Dt t ln t R f U hS hT Dti 2kT Dti (3.48) 38 It is essential that the designer of shell-and-tube heat exchangers becomes familiar with the principles of the various correlations and methods in numerous publications, their advantages and disadvantages, limitations and degrees of sophistication versus probable accuracy and other related aspects. All the published methods can be logically divided into several groups: 1. The early developments based on flow over ideal tube banks or even single tubes. 2. The “integral” approach, which recognizes baffled cross flow modified by the presence of window, but treats the problem on an overall basis without considerations of the modified effects of leakage and bypass. 3. The “analytical” approach based on Tinker’s multistream model and his simplified method. 4. The “stream analysis method”, which utilizes a rigorous reiterative approach based on Tinker’s model. 5. The Delaware method, which uses the principles of the Tinker’s model but interprets them on an overall basis, that is, without reiterations. 6. Numerical prediction methods. All of the methods suffer from essential drawbacks, which are given below: 1. All the “integral” methods such as Donohue and Kern cannot be recommended, as the resulting errors are potentially high. 2. Although Tinker’s flow model is accepted as a valid basis, its full usefulness is idealized in the rigorous iterative form. Even so, the crucial correlations of the flow resistance values are not in the public domain. 3. Although the numerical method has promising future, it is difficult to apply to complex cases and, for design purpose; it is not yet a substitute for the other methods listed. 39 4. The Delaware method appears to be the best available and the most suitable for design of shell-and-tube exchangers. This method has a limitation that it does not allow for interaction between the effects of the various parasitic streams. In selecting the recommended method for the design of exchanger, the considerations summarized above indicated that, of all the methods surveyed, the Delaware method is in principle the most suitable on at the present. The method based on the principles of the Tinker’s flow distribution model, and thus is more superior to “integral” methods. It should be clear, however, that this no reiterative method cannot compete for accuracy with the complex stream analysis-type methods.. Nevertheless, for a well-designed exchanger without any extremes, the results are within respectable limits of accuracy. In this project, the Delaware method is used for the forward calculations of heat transfer coefficients and pressure drops. This method has distinctive advantages on all other method. 40 Chapter 4 DESIGN OF SHELL AND TUBE HEAT EXCHANGER USING SPECIFIED PRESSURE DROP The classical approach to shell-and-tube heat exchanger design involves a significant amount of trial-and-error because an acceptable design needs to satisfy a number of constraints. Typically, a designer chooses various geometrical parameters such as tube length, shell diameter and baffle spacing based on experience to arrive at a possible design. If the design does not satisfy the constraints, a new set of geometrical parameters must be chosen. Even if the constraints are satisfied, the design may not be optimal. In this project, a methodology is proposed that calculates the approximate free flow areas on tube and shell side for specified pressure drops. Once these are obtained, geometrical dimensions can be tried to satisfy heat transfer requirements. 4.1 Input Data The inputs specified for the design of heat exchangers consists of: Process Data Type of fluids on both sides Mass flow rate of hot fluid and cold fluid Tube side ∆P Inlet pressure of tube side Shell side ∆P Inlet pressure of shell side Inlet and outlet temperatures Fouling resistances 41 Physical properties Viscosity Heat capacity Thermal conductivity Densities 4.2 Formulation of Design Procedure In this project, the problem of shell-and-tube heat exchanger is considered in which pressure drops of the streams is specified. Utilization of pressure drop gives the heat exchanger having minimum shell diameter. The pressure drop of one of the streams is given as: G 2 fL P 2 D (4.1) The characteristic length of heat exchanger is given as: rh Acc L A (4.2) In alternate form, the characteristic length of heat exchanger may be defined as: rh D 4 (4.3) Combining equations (4.2 and 4.3), pressure drop of stream of heat exchanger becomes: P G 2 fA 8 Acc (4.4) Mass flow velocity of stream is defined as: G V (4.5) 42 . M G Acc Or (4.6) Using equation (4.6) in equation (4.4), and rearranging: V 2 P 1 Acc 2 4f A (4.7) The number of transfer units of stream is defined as: NTU 0 Ah C (4.8) Stanton number is given as: St h GC p (4.9) Combining equations (4.2, 4.5, and 4.9), equation for number of transfer units of streams becomes: NTU 0 A.St Acc (4.10) Using equation (4.9) in equation (4.6), velocity of stream is given by the formula: V 2 0 P St 1 4 f NTU (4.11) Alternatively, Stanton number is defined as St jh Pr 2 / 3 Putting equation (4.11) in equation (4.10), velocity of stream is then given by: (4.12) 43 V 2 0 P j h 1 1 2 / 3 4 f Pr NTU (4.13) In equation (4.13), NTU denotes the number of transfer units of the stream. The total number of transfer unit of shell-and-tube heat exchanger is calculated from equation (3.15 or 3.16). Equations (3.15 and 3.16) are complex function of minimum heat capacity, effectiveness and total number of transfer units NTU. Hence, NTU is calculated by using any root solving methods like bisection method, false position method etc. Once total number of transfer units is available, the NTU on shell side and tube side is calculated by distributing total number of transfer units in fractions. To do this, equation (4.13) is used. 1 NTU 1 C NTU Shell Shell C min To calculate the velocity of fluid stream, value of 1 C NTU Tube Tube C min (4.14) jh should be available from chart or from f correlations. 4.3 Shell Side Procedure To determine the velocity and free flow area on shell side, the term Acc has to be A replaced as follows: The NTU on shell side is expressed as: NTU Shell 0 AhS . M Cp (4.15) 44 The heat transfer coefficient of shell side is given by equation (3.34). Rearranging equation (3.34), the heat transfer coefficient can be given as: C 2 / 3 hS . S Pr 0.45 Acc Re S w 0.36 0.14 (4.16) Putting equation (4.15) in equation (4.14), and rearranging, the number of transfer units on shell side becomes: NTU Shell 0.36 Re S 0.45 A Pr 2 / 3 Acc w 0.14 (4.17) Or Acc 1 0 j h Pr 2 / 3 A NTU Shell Where jh 0.36 Re S 0.45 w 0.14 (4.18) (4.19) Equations (3.45, 4.14 4.18, and 4.19) are used in equation (4.13) to determine the shell side velocity. Once shell side velocity is available, the free flow area is computed. The free flow area on shell side is given as: Ds C ' Lbs A fS Ltp (4.20) 45 The shell diameter is calculated from equation (4.20) for a standard tube diameter, baffle spacing, tube pitch, baffle cut and clearances and assumed jh and Reynolds number. Tube count f is determined according to the formula given in HEDH. Alternatively, the value of Reynolds number for shell side is taken from Figure 4.1. Re S Figure 3.4 jh versus Re for Shell Side Flow f jh versus f 46 4.4 Tube Side Procedure To determine the velocity and free flow area on tube side, the term Acc has to be A replaced as follows: For laminar flow, Reynolds number < 2100, (from equation (3.35)), L j h 1.86 D ti 1/ 3 Re 1 / 3 (4.21) For the transition region, Reynolds number from 2100 to 10000, (from equation (3.36)), j h 0.166Re 2/3 L 2 / 3 1251 D (4.22) For turbulent flow, Reynolds number > 10000, (from equation (3.37)), j h 0.023 Re 0.8 (4.23) The Colburn type of equation for tube side heat transfer coefficient is as: GC p C p hT j h Re k 2 / 3 w 0.14 (4.24) . M Replacing G by in equation (4.23), heat transfer coefficient on tube side is given as: Acc . M C p C p hT j h Acc Re k 2 / 3 w 0.14 (4.25) The total number of transfer units, NTU on tube side is given as: NTU Tube 0 AhT . M Cp (4.26) 47 Using equation (4.25) in equation (4.26), the total number of transfer units, NTU on tube side is given as: j A Pr 2 / 3 0 h Re T Acc w NTU Tube 0.14 (4.27) or Acc Pr 2 / 3 1 0 jh r A Re NTU Tube (4.28) Equations (3.47, 4.14 4.28, and 4.21 or 4.22 or 4.23) are used in equation (4.13) to determine the tube side velocity. Once tube side velocity is available, the free flow area is computed. The free flow area on tube side is given as: . A fT M 2 Dti NTPNS N tt tVt 4 The second and third terms in equation (4.29) should be equal. jh and Re is changed until these f terms become equal with accuracy of 2 to 5 %. Alternatively, The value of number for shell side is taken from Figure 4.2 (4.29) jh versus Reynolds f 48 Re T Figure 3.5 jh versus Re for Tube Side Flow f 4.5 Optimization of Shell and Tube Heat Exchanger The prediction about heat transfer and pressure drop optimization can be very complex – with two layers of refinements and distinctions, often buried in complex code and sometimes grossly misapplied. Several papers are present on the optimization heat exchanger. All authors are succeeded in finding out the optimum pressure drops. In this case, the pressure drop is fixed. Hence the costs due to process parameters are fixed. The cost associated with the surface is to be minimized. For such situation, the minimum heat transfer area is the objective function of optimization model. 49 The objective function is defined as: F Cs A Cs Q U 0 FT TLM (4.30) Expressing objective function in the design parameters, the objective function becomes F Cs Q FT TLM Lbc Lbb Ltp,eff DS Lbb Dt Ltp Dt 45.058Dt 0.8 Ltw 2 / 3 Prt 1 / 3 M T 0.8 Dt 2Ltw 0.2 k tw ji C pS M S Ltp,eff PrS j c jb jl j s j r The optimization on a shell-and-tube heat exchanger consists of the structure size optimization, and operating parameter optimization. For the former, the vector of the strategic variable can be expressed by X 1 x1 Where x2 x5 x6 Lto T Bc DS Lbc Nb N tt T x3 x4 Bc Lbch DS (4.33) Nb Lto 2 Lts Lbi Lbo 1 Lbc (4.34) Lbb 0.020 0.01675DS (4.32) (4.35) Tube diameter is not included as an optimization variable because its value is generally fixed ahead of actual design. Again, the tube pitch is not usually a design variable since it can be fixed. Its common values range between 19.75 mm and 31.75 mm depending on the tube size. For the latter, the vector of the strategic variable is expressed by 50 X2 x ' 1 ' x2 ' x3 T N M . P T (4.36) . Where N , P, M are the rotary speed of power machinery, discharge pressure, and the flow quantity of fluid respectively. The operating parameters are fixed for a fixed pressure drops. The constrained condition for optimization structure size of a shell-and-tube heat exchanger: For the inequality constraints gi X 1 0 g1 Lto 2.5 Ds g2 Z oo 1.0 Ds g3 DS 1.0 40 DS Dt g5 38.1 1.0 Dt g6 DS 1 Lbc g8 0.5 1.0 Bc g9 Bc 1 0.10 g12 PT max 1.0 PT g 4 15 g7 (4.37) Lbc 0.20 DS 2 0.78Dotl N g10 N tt g11 tt 1.0 C1 Ltp 7 g13 PS max 1.0 PS g14 Q 1 .0 Qmin g15 Lbb 1.0 0.022 g16 0.075 1 .0 Lbb g17 jc 1.0 0.5 g18 1.3 1.0 jc g19 jb 1.0 0.3 g 20 1.3 1.0 jb g 21 js 1.0 0.5 51 g 22 1.3 1.0 js g 23 jl 1.0 0.7 g 24 0 .8 1 .0 jl For the equality constraints h j X 1 0 h1 N b (4.38) Lto 2 Lts Lbi Lbo Lbc Equations (3.20, 3.21, 3.22, 3.28, 3.29 or 3.30 or 3.31) are used for the calculation of correction factors. Pressure drop in shell side is calculated as per equation (3.37) and pressure drop in tube side is calculated as per equation (3.46). From the above equations, it is vivid that the objective function is a minimum of multivariable design parameters, subjected to nonlinear inequality and equality constraints. Hence, a multivariable search method is used for the minimum area objective function. When the optimizing systems, where components are available in finite steps of sizes, as in shell-and-tube heat exchangers, search methods are often superior to calculus methods, which assumes infinite gradation of sizes. 4.6 Mechanical Design of Shell and Tube Heat Exchanger Designers and fabricators of heat exchanger often treat thermal design and mechanical design as two discrete and separable functions. The interaction between these two is essential in some cases like thermal stresses in multiple passes fixed tube heat exchanger, effect of flexing of tube sheets. Therefore, a designer alert to the mutual influence of these two designs and hence hydro-mechanical design is also done here. 52 4.7 Tube Sheet In this report the thickness of tube sheet is calculated as per the TEMA [15]. Subjected to requirements of the Code, the formulas and design criteria contained below are applicable with limitations noted, when the following normal design conditions are met; size and pressure are within the scope of the TEMA Mechanical Standards. Effective tube sheet thickness is calculated as: For bending T For shear T FG P 2 S 0.31DL P S D t 1 L tp (4.39) (4.40) Where T = effective tube sheet thickness DL = 4A = equivalent diameter of tube center limit perimeter C C = perimeter of tube layout measured stepwise in increments of one tube pitch from center to center of the outer most tubes. A = total area enclosed by perimeter C, P = effective design pressure as per TEMA S = code allowable tensile stress F and G are tube sheet constants 53 4.8 Channel Cover The effective thickness of flat channel covers shall be the thickness measured at the bottom of the pass partition groove minus tube side corrosion allowance in excess of the groove depth. The required value shall be either that determined from the appropriate code formula or from the following section, whichever is greater: 4 h A G T 5.7 P 2 G B dB 100 G 100 1/ 3 (4.41) G = mean gasket diameter dB = nominal bolt diameter hG = radial distance between mean gasket diameter and bolt circle AB = actual total cross sectional area of bolts 4.9 End Flanges and Bolting Flanges and bolting for external joints shall be in accordance with design rules subjected to the following limitations. The minimum permissible bolt diameter shall be 1.27 cm for exchangers with shell diameter of 30.48 cm or less, and 1.58 cm for all other sizes. Maximum recommended bolt spacing for channel is given by: Bmax 2 Dbo 6t cc 0.6 (4.42) 4.10 Baffle Design The segmental baffle and tube support plate are standard parts. Baffle has holes for tubes of sizes depending upon the tube outer diameter and length of the tube as described in Table. 54 Similarly, baffle diameter and thickness are dependent on length and outer tube diameter and internal shell diameter. They are selected using the Tables 4.1, 4.2 and 4.3. Internal shell diameter, m Baffle diameter, m DSi < 0.330 DSi – 0.0508 0.330 < DSi < 0.431 DSi – 0.0508 0.431 < DSi < 0.584 DSi – 0.0508 0.584 < DSi < 0.990 DSi – 0.0508 0.990 < DSi < 1.371 DSi – 0.1143 DSi > 1.371 DSi – 0.1524 Table 4.1 Baffle Diameter [15] Tube length, m Internal shell diameter, m Baffle thickness, m L < 0.305 DSi < 0.356 1.58 0.356 < DSi < 0.711 3.17 0.711 < DSi < 0.965 4.76 DSi < 0.356 3.17 0.356 < DSi < 0.711 4.76 0.711 < DSi < 0.965 6.10 0.965 < DSi < 1.524 6.10 DSi < 0.356 4.76 0.356 < DSi < 0.711 6.10 0.305 < L < 0.606 0.606 < L < 0.914 55 0.914 < L < 1.219 0.711 < DSi < 0.965 7.93 0.965 < DSi < 1.524 9.52 DSi < 0.356 6.10 0.356 < DSi < 0.711 9.52 0.711 < DSi < 0.965 9.52 0.965 < DSi < 1.524 12.70 DSi < 0.356 9.52 0.356 < DSi < 0.711 9.52 0.711 < DSi < 0.965 12.70 0.965 < DSi < 1.524 15.87 DSi < 0.356 9.52 0.356 < DSi < 0.711 12.70 0.711 < DSi < 0.965 15.87 0.965 < DSi < 1.524 15.87 1.219 < L < 1.524 L > 1.524 Table 4.2 Baffle Thickness [15] Tube length, m Outer tube diameter, cm Diameter of hole, mm L < 0.914 Dto > 3.175 Dto + 0.7937 Dto < 3.175 Dto + 0.3968 Dto > 3.175 Dto + 0.3968 Dto < 3.175 Dto + 0.7937 L > 0.914 Table 4.3 Diameters of Holes in Baffle Plate [15] 56 4.11 Costing of Shell and Tube Heat Exchanger Pricing of tube and shell heat exchanger is clearly not a precise matter. It depends, in part on the costs of constructing the unit, but other factors may dominate. Prices will vary depending on the average production backlog and general marketing conditions. However, statistical studies are regularly done and reported in the engineering magazines. In the present project the costs are taken as given by Crane [17]. Typical articles indicate that the price may be estimated using techniques similar to those below. 4.12 Shell Cost The data included in this study-included carbon shells under 30 inches outside diameter. In the absence of data for larger shell, these equations may be extrapolated to larger sizes. For expansion joints it is recommended that the shell be priced as if an additional 5 Ft were added to the length of the shell. For 0 < P < 27.59 bar Cost = 4.76 L DS0.93 (4.43) For 27.59 < P < 41.36 bar Cost = 6.72 L DS0.93 (4.44) 4.13 Tube Costs Tube costs are based on (a) the cost of the tubing itself, usually reported on a cost per square foot of heat exchanger surface, and (b) the cost associated with preparing the tube sheets, installing and rolling the tubes. These two factors may be estimated using the data below: 57 Tube OD, mm Rated pressure, bar Straight Tubes, $ / ft-Tubes U-Tubes, $ / ft-Tubes <= 19.75 10.34 1.15 3.85 <= 19.75 20.68 1.30 4.15 <=19.75 27.59 1.40 4.50 > = 25.4 10.34 1.30 4.14 >= 25.4 20.68 1.45 4.50 >= 25.4 27.59 1.75 4.60 Table 4.4 Preparation Cost [17] Note: This is an unusual procedure required only when fluids must absolute not leak. Normal cost is taken as $4.72 / Tubes. Material Cost, $/inch3 Alum / Brass 1.38 Admiral Brass 1.36 304 SS 2.56 316 SS 7.74 321 SS 3.57 70 / 30 CuNi 2.76 90 / 10 CuNi 2.39 A3003 0.79 330 Brass 1.79 Half – hard Copper 2.34 58 Copper 2.02 Carbon Steel 1.71 Table 4.5 Material Cost [17] 4.14 Installed Nozzle Cost The total cost of preparing the opening, purchasing and welding the nozzles in place may be estimated from the following equations. The data from which these fits were obtained were for nozzles ranging between 3 and 12”. For 0 < P < 10.34 bar Cost = 118 – 4.33D + 2.46D2 (4.45) For 10.34 < P < 20.68 bar Cost = 140 – 10D + 3.33D2 (4.46) For 20.68 < P < 41.36 bar Cost = 119 – 2.5D + 3.75D2 (4.47) 4.15 Front and Rear Head Cost The following equation has been fitted to estimate the costs of the front and rear end heads based on various TEMA categories: Costs = C DS1.037 (4.50) Where C is given from Table 4.6 below as a function of pressure Construction 10.34, bar 20.68, bar 27.59, bar 41.36, bar AEU 201 230 258 276 AEM 306 351 391 421 AEN 337 387 432 463 59 AEL 387 441 494 532 AEW 423 484 541 582 AEP 460 526 587 632 AES 496 569 634 682 AET 639 733 817 878 BEU 120 140 155 165 BEM 225 261 288 309 BEN 256 297 329 352 BEL 306 351 391 421 BEW 326 368 403 439 BEP 345 385 414 457 BES 365 402 426 475 BET 558 642 698 810 CEU 175 202 226 241 CEM 288 324 360 396 CEN 306 348 387 421 CEN 337 387 432 463 CEW 369 425 473 507 Table 4.6 Shell Cost Factors for Selected Shell Constructions [17] 60 4.16 Miscellaneous Cost Delivery cost may be taken as 3 % of total construction cost. Engineering, purchasing and administrative cost may be taken as 16 % of total construction costs. The equations derived for shell-and-tube heat exchanger for given pressure drops are used for thermal evaluation purposes. All the equations are used in design and optimization algorithm in which heat exchanger geometrical dimensions are obtained from performance specifications. Various cost equations are derived with the assumption that the market price of the components is not changing with time. 61 Chapter 5 DEVELOPMENT OF ALGORITHM AND OPTIMIZATION FOR DESIN OF SHELL AND TUBE HEAT EXCHANGER Based on the design and optimization procedure formulated in chapter 4, design and optimization algorithm is developed for shell-and-tube heat exchanger. A solution of core velocity equation is a heart of such an algorithm. The design process of shell-and-tube heat exchanger proceeds through the following steps: Process conditions (stream compositions, flow rates, temperatures, and pressures) must be specified. Required physical properties over the temperature and pressure ranges of interest must be obtained. The type of heat exchanger to be employed is chosen. A preliminary estimate of the size of the exchanger is made, using a heat transfer coefficient appropriate to the fluids, the process, and the equipment. A first design is chosen; complete in all details necessary to carry out the design calculations. The design chosen is now evaluated or rated, as to its ability to meet the process specifications with respect to both heat duty and pressure drop. To do this, heat transfer rate in shell-and-tube heat exchanger is calculated using equation (3.2 or 3.3). The temperature correction factor is determined using equations (3.6). The calculated temperature correction factor should not be less than 0.75. If it is less than 0.75, the 62 number shell passes and tube passes are increased by 1 and 2 respectively. Effectiveness of shell-and-tube heat exchanger is obtained by using equation (3.13). Once effectiveness is available, overall number of transfer units NTU is calculated from equations (3.15 or 3.16). Equations (3.15 and 3.16) are complex functions of minimum thermal heat capacity and NTU. So, bisection method is used for the computation of NTU. The shell side friction factor, heat transfer j factor and baffle cut are all set at standard initial values. The core velocity equation (4.13) is used to find out the velocity on the shell side. This shell side velocity is then used to compute free flow area. Once free flow area is known, the shell diameter is known. The tube count gets fixed for a determined shell diameter. The free flow area on tube side is also determined from core velocity equation. This can be obtained by also tube count. These two free flow areas are matched. Once this is achieved, the heat exchanger area, heat transfer coefficient on tube and shell side is calculated. From the detailed geometry actual friction factor f and j h - factors are estimated and the initial assumptions are tested and updated if necessary. Once initial assumptions and detailed geometry coincide, the design has been successfully accomplished. Based on this result a new configuration is chosen if necessary and the above step is repeated. If the first design was inadequate to meet the required heat load, it is usually necessary to increase the size of the exchanger, while still remaining within specified pressure drops, tube length, shell diameter, etc. This will sometimes mean going to multiple exchanger configurations. If the first design more than meets heat load requirements or does not use the entire allowable pressure drop, a less expensive exchanger can usually be designed to fulfill process requirements. 63 Chapter 6 RESULT, DISCUSSION, CONCLUSION AND FUTURE SCOPE OF WORK The pressure drop relationship, (equation 4.13), has been applied to develop a specific relationship for a shell-and-tube heat exchanger based on the effectiveness-NTU approach. The Bell’s Delaware design method is used for estimating various parameters. The actual heat transfer coefficient is estimated and pressure drops are checked according to the HEDH method. The flow rates, temperatures, allowable pressure drops, and physical properties of streams are fixed. It is required to determine the optimum area and optimum cost of shell-and-tube heat exchanger. A full specification of the design problem is given in Table 6.1 and Table 6.2. Physical Properties Shell side Tube side Fluid Oil Water Flow rate (kg/s) 22.4 77.96 Fluid density (kg/m3) 740 1000 Heat capacity (J/kg. K) 2407 4187 Viscosity (cps) 0.494 1.000 Thermal conductivity (W/m. K) 0.105 0.61 Inlet temp. (deg C) 100 7.1 Outlet temp (deg C) 42.5 16.6 Allowable P (kPa) 13.7 11.6 Dirt factor (K m2/W) 0.000 0.000 C32100 SS 316 Material 64 Wall resistance (K m2/W) 0.00003 Heat Duty (kW) 3100 Table 6.1 Shell and Tube Exchanger Design Problem [8] – Physical Properties Geometry Values Tube OD (mm) 16 Tube ID (mm) 13.5 Tube layout (deg) 30 Tube pitch (mm) 20.8 Baffle-to-shell clearance (mm) 5.5 Tube-to-baffle clearance (mm) 0.5 Bundle-to-shell clearance (mm) 10 Table 6.2 Shell and Tube Exchanger Design Problem [8] – Geometry The example used here is an adaptation of the one used by Polley, Panjeh Shahi and Nunez [8] to demonstrate the inverse design methodology. The original example involved water on the tube side of the exchanger with an assumed film heat transfer coefficient of 6000 W/m2 K. The fluid on shell side is viscous oil. The tube side and shell side pressure drops for this situation are 11.66 kPa and 13.7 kPa. These are the allowable P subsequently used in our design. 65 The design process of shell-and-tube heat exchanger proceeds through the following steps: Process conditions (stream compositions, flow rates, temperatures, and pressures) must be specified. Required physical properties over the temperature and pressure ranges of interest must be obtained. The type of heat exchanger to be employed is chosen. A preliminary estimate of the size of the exchanger is made, using a heat transfer coefficient appropriate to the fluids, the process, and the equipment. A first design is chosen; complete in all details necessary to carry out the design calculations. The design chosen is now evaluated or rated, as to its ability to meet the process specifications with respect to both heat duty and pressure drop. To do this, heat transfer rate in shell-and-tube heat exchanger is calculated using equation (3.2 or 3.3). The Temperature correction factor is determined using equations (3.6). The calculated temperature correction factor should not be less than 0.75. If it is less than 0.75, the number shell passes and 1 and 2 increases tube passes respectively. Effectiveness of shell-and-tube heat exchanger is obtained by using equation (3.13). Once effectiveness is available, overall number of transfer units NTU is calculated from equations (3.15 or 3.16). Equations (3.15 and 3.16) are complex functions of minimum thermal heat capacity and NTU. So, bisection method is used for the computation of NTU. The shell side friction factor, heat transfer j factor and baffle cut are all set at standard initial values. The core velocity equation (4.13) is used to find out the velocity on the shell side. 66 This shell side velocity is then used to compute free flow area. Once free flow area is known, the shell diameter is known. The tube count gets fixed for a determined shell diameter. The free flow area on tube side is also determined from core velocity equation. This can be obtained by also tube count. These two free flow areas are matched. Once this is achieved, the heat exchanger area, heat transfer coefficient on tube and shell side is calculated. From the detailed geometry actual friction factor f and j h - factors are estimated and the initial assumptions are tested and updated if necessary. Once initial assumptions and detailed geometry coincide, the design has been successfully accomplished. Based on this result a new configuration is chosen if necessary and the above step is repeated. If the first design was inadequate to meet the required heat load, it is usually necessary to increase the size of the exchanger, while still remaining within specified pressure drops, tube length, shell diameter, etc. This will sometimes mean going to multiple exchanger configurations. If the first design more than meets heat load requirements or does not use the entire allowable pressure drop, a less expensive exchanger can usually be designed to fulfill process requirements. The final design should meet process requirements (within the allowable error limits) at lowest cost. The lowest cost should include operation and maintenance costs and credit for ability to meet long-term process changes as well as installed (capital) cost. Exchangers should not be selected entirely on a lowest first cost basis, which frequently results in future penalties. 67 6.1 Area Targeting The optimized heat exchanger design derived using the new algorithm is compared with the original one in Table 6.3 and Table 6.4. Geometry New algorithm Polley, Shahi, and Nunez Shell diameter (mm) 520 563 Tube length (mm) 1728 1815 Baffle cut (%) 26.8 29.3 Baffle spacing (mm) 228 253 No. of baffles 5 6 No. of tubes 548 574 No. of tube passes 2 2 Required area (m2) 49.39 52.3 Installed area (m2) 49.39 52.3 Table 6.3 Comparison of Shell and Tube Heat Exchanger Designs – Geometry Performances New algorithm Polley, Shahi, and Nunez Shell side Re 27926 21398 Shell side P (kPa) 13.493 13.7 Tube side P (kPa) 11.61 11.69 Shell side coeff. (W/m2. K) 1471 1406 Tube side coeff. (W/m2. K) 6750 6641 O.H.T.C. (W/m2. K) 1149 1088 Table 6.4 Comparison of Shell and Tube Heat Exchanger Designs – Performances 68 The new algorithm makes the full utilization of the available pressure drop and achieves an overall heat transfer coefficient of 1149 W/m2 K and the required area 49.39 m2 when 90 % of total NTU is distributed between shell and 10 % of total NTU between tube sides. The original design has an overall heat transfer coefficient of 971 W/m2 K with a required area 58.9 m2. Their design procedure yields an overall heat transfer coefficient of 1088 W/m2 K and a required area of 52.3 m2. Because of the way in which problem is set up, all the design makes full use of pressure drop. 6.2 Optimized Results of Components of Shell and Tube Heat Exchanger Program is run to evaluate the thickness of exchanger parts like tube sheet, baffle, shell and tube. It is also possible to calculate the diameter and number of tie rods. Table 6.3 shows the optimized results for mechanical design of a given shell-and-tube heat exchanger Tube thickness 1.25 mm Shell thickness 7.937 mm Tube sheet thickness 13.54 Baffle thickness 12.7 mm Diameter of tie rods 12.7 mm No. of tie rods 6 Table 6.5 Optimized Results of Mechanical Design 69 6.3 Cost Analysis Area targeting in the previous section ensures exchanger of the smallest size with minimum capital cost. However, the power cost and capital cost with pumping liquids and/or compressing gases through an exchange often constitute a significant factor. However, in this thesis, the problem is set up such that the cost associated with power and capital cost of pumps/compressor is fixed. The only cost we look for here is the cost associated with the surface area. The costs of various parts of exchanger for the outputs of the above problem are given below in Table 6.4. Parts list Cost (in $) Shell 3463 Installed nozzles 1330 Baffles 272 Saddle 50.06 Tubes (preparation) 3106 Tube (material) 7893 Front and rear end heads 3205 Table 6.6 Cost Analysis 70 From cost analysis, the total cost of heat exchanger is $ 19319. This is the minimum initial surface cost of a shell-and-tube heat exchanger. The minimum cost is found for the BEU type construction, U-tube material SS 316. 6.4 Conclusion 1. Based on the effectiveness-NTU, a novel methodology is developed for a shell-and-tube heat exchanger with a given pressure drops and provides targets for minimum area and cost. In contrast to earlier approach, the methodology accounts for full use of given pressure drops on both sides of exchanger to yield the smallest exchanger for a given duty. For this, a quantitative relationship is developed that relates the pressure drop, velocity, friction factor and heat transfer factor and NTU. 2. The methodology as presented in this work is based on Delaware method, which provides good predictions for shell side flow. It has been shown that how the basic algorithm can be applied using Delaware method. 3. It must be emphasized heat exchanger had the potential danger of accepting a design that satisfies the dirt factor and pressure drop constraints without thoroughly investigating other options that may prove to be more promising. In contrast, in this work a rapid algorithm is developed which takes care of all constraints. 4. Targeting for area and cost is vital and well-established step in the design of heat exchanger networks by pinch technology. Targets present what is the best performance that can be possibly achieved, before actually attempting to achieve it. The targets proposed in this work allow the designer to determine the minimum area and cost (along with tube length, shell diameter and baffle spacing etc.). 71 6.5 Feature Scope of Work With shell-and-tube heat exchangers, the design and optimization methodology is restricted to applications involving single-phase turbulent flows with compressible fluids. This is because vaporization and condensation processes in this type of heat exchangers are often. However, the design method can also be used for two-phase heat transfer exchangers like compact heat exchangers with some little modifications in core velocity equation. Further research is needed before the approach can be extended to cover non-isothermal phase changes. 72 REFERENCES 1. Mcadams, W.H., Heat Transmission, (McGraw-Hill, New York), pp 430-441, 1954 2. Jenssen, S.K., Heat exchanger optimization, Chemical Eng. Progress, 65(7), pp 59, 1969 3. Sidney, K., and Jones, P.R., Programs for the price optimum design of heat exchangers, British Chemical Engineering, April,pp 195-198, 1970 4. Steinmeyer, D.E., Energy price impacts design, Hydrocarbon Process, November, pp 205, 1976. 5. Steinmeyer, D.E., Take your pick – capital or energy, CHEMTECH, March, 1982 6. Peter, M.S. and Timmerhaus, K.D., Plant design and economics for chemical engineers, pp 678-696 3rd Ed., McGraw-Hill, New York, 1981 7. Kovarik, M., Optimal heat exchanger, Journal of Heat Transfer, Vol. 111, May, pp 287293, 1989 8. Polley, G.T., Panjeh Shahi, M.H. and Nunez, M.P., Rapid design algorithms for shelland-tube and compact heat exchangers, Trans IChemE, Vol. 69(A), November,pp 435444, 1991 9. Jegede, F.O. and Polley, G.T., Optimum heat exchanger design, Trans IChemE, Vol. 70(A), March, pp 133-141, 1992 10. Saffar-Avval, M. and Damangir, E., A general correlation for determining optimum baffle spacing for all types of shell-and-tube heat exchangers, International Journal of Heat and Mass Transfer, Vol. 38 (13), pp 2501-2506, 1995 11. Poddar, T.K. and Polley, G.T., Heat exchanger design through parameter plotting, Trans IChemE, Vol. 74(A), November, pp 849-852, 1996 73 12. Steinmeyer, D.E., Understanding ∆P and ∆T in turbulent flow heat exchangers, Chemical Engineering Progress, June,pp 49-55, 1996 13. Soylemez, M.S., On the optimum heat exchanger sizing for heat recovery, Energy Conversion and Management, 41, pp1419-1427, 2000 14. Murlikrishna, K. and Shenoy, U.V., Heat exchanger design targets for minimum area and cost, Trans IChemE, Vol. 78(A), March, pp 161-167, 2000 15. Bevevino, J.W., ET. al., Standards of tubular exchanger manufacturing association, TEMA, New York, 6th Edition, 1988 16. Mukherjee, R., Effectively design shell-and-tube heat exchangers, Chemical Engineering Progress, February, pp 21-37, 1998 17. Crane, R.A., Thermal Aspects of Heat Exchanger Design, University of South Florida, Department of Mechanical Engineering 18. Gulyani, B.B. and Mohanty, B., Estimating log mean temperature difference, Chemical Engineering, November, pp127-130, 2001 19. Sukhatme, S.P., Heat exchangers, A Text Book on Heat Transfer, University Press India Limited, pp 201-226 1996 20. Taborek, J., Shell-and-tube heat exchangers, Heat Exchanger Data Handbook, Hemisphere, 1983 21. Poddar, T.K. and Polley, G.T., Optimize shell-and-tube heat exchangers design, Chemical Engineering Progress, September,pp 41- 46, 2000