The objective of the first part of this report, is to analyze the cooling load demands of the Wawa store #8053 located in Philadelphia. The RTSM spreadsheets were used to analyze cooling loads when the store is completely empty of internal loads: no equipment, occupant or lighting loads. The building characteristics of the Wawa drawings were used to complete the spreadsheet for the wall composition. The building was broken into three zones, the refrigeration room, Z1, the food preparation area, Z2, and the retail area, Z3. The ACH decided for each zone were determined by taking occupancy loads, equipment loads, and lighting loads into account. The refrigeration room will only have someone in it when supplies are being loaded into the space, other than that, it will remain unoccupied. Based on this, it was assumed to have an ACH of 2 to provide minimum ventilation air for the space. The retail area is the most populated zone throughout the day. However, the equipment loads are not high for this area, so the space was designed for 6 ACH. The food preparation zone has a few cooks working at a time, however, the equipment give off the most latent and sensible heat in the zone. The model has a design ACH of 15 in order to remove the fumes and latent heat coming off of the equipment. The design ACH for the zone is the highest because of the amount of exhaust air removed from the space. Even though the model is designed for zero internal loads, the air changes were designed in the case that the building was occupied. The building orientation starts off with the entrance of Wawa facing south. The peak cooling loads for each zone and rotation are listed below. The peak cooling loads occur during December and July, during the afternoon around 2pm to 6pm. Z1 - 0° Z2 - 0° Z3 - 0° Z1 - 90° Z2 - 90° Z3 - 90° Z1 - 180° Z2 - 180° Z3 - 180° Peak Cooling Load Month Hour 7 16 12 16 12 14 7 16 12 16 7 18 7 16 12 16 12 14 The cooling loads for each zone are broken down by heat gain component. The largest heat gain was from the refrigeration room by infiltration latent heat. The refrigeration room was designed with a metal room in the RSTM spreadsheet which may be the reason why the results are skewed. The retail zone is the only space that has a solar cooling load because the zone’s exterior wall is mainly the glass façade of the south entrance. Component Cooling Wall/Window Roof Solar Z1 - 0° 635.09 0.00 0.00 Z2 - 0° -98.63 -143.95 0.00 Z3 - 0° -3967.60 -505.21 3655.37 Z1 - 90° 676.67 0.00 0.00 Z2 - 90° -98.63 -143.95 0.00 Z3 - 90° 10956.79 2328.02 17799.29 Z1 - 180° 870.69 0.00 0.00 Z2 - 180° -98.63 -143.95 0.00 Z3 - 180° -3967.60 -505.21 3655.37 Loads Inf. Sens. Inf. Lat. 18676.87 25658.22 -901.33 -31.89 -542.41 -17.10 18676.87 25658.22 -901.33 -31.89 715.60 1063.68 18676.87 25658.22 -901.33 -31.89 -542.41 -17.10 BTU/hr Total Cooling Load 50000 45000 40000 35000 30000 25000 20000 15000 10000 5000 0 Z1 - 0° Z2 - 0° Z3 - 0° Z1 - 90° Z2 - 90° Z3 - 90° Z1 - 180° Z2 - 180° Z3 - 180° Zone - Rotation Since the refrigeration room is a metal box, the roof was modeled as a metal interior surface because the space above is empty. Therefore the infiltration load dominates in this zone. The kitchen is mainly an interior room, so it is separated from the exterior conditions. Therefore, the kitchen does not require as big of a cooling load because it is protected by interior spaces. The infiltration dominates the kitchen zone. The retail area zone is dominated by the solar heat gain because of the fenestration on the south façade. After the first analysis, the building was rotated 90 degrees then 180 degrees, so the glass entrance is now facing north. The main changes in cooling loads were due to the solar heat gains in the retail area. Other than zone 3, the other zones had a consistent total cooling loads for all three rotations. The Wawa store was analyzed with internal loads by changing the equipment, lighting, and occupant schedules. The following chart is the assumed schedule of the building for each internal heat gain component. Hours People 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 The assumed ACHs for each zone are the same from the first analysis and can be found at the beginning of this report. The peak cooling loads for the building when it is occupied occur during the summer in the late afternoon. Z1 - 0° Z2 - 0° Z3 - 0° Z1 - 90° Z2 - 90° Z3 - 90° Z1 - 180° Z2 - 180° Z3 - 180° Peak Cooling Load Month Hour 7 16 7 16 7 18 7 16 7 16 7 18 7 16 7 16 7 16 In the refrigeration room, the infiltration load dominates the overall cooling load because there aren’t people occupying the room and there isn’t a significant amount of equipment in the room. The kitchen zone is dominated by the equipment load. The equipment load adds both sensible and latent heat to the space, so both cooling loads equally dominate the other component heat gains. The occupancy loads dominate in the retail area because there are always customers in the retail area, and the equipment loads are not as high. Overall between the three zones, the occupancy load in the retail area dominates over the other loads. The cooling loads are significantly different for the second analysis because since the building is occupied and there are more internal heat gains, the main cooling loads occur during July no matter the orientation of the building. The building still has similar heat gains due to the envelope, however, the equipment and occupant loads are more significant than the envelope loads, especially in the retail zone, where it is heavily occupied, and the food preparation zone where there are more equipment. At lower outdoor temperatures, the energy usage barely increases in commercial buildings. Since the building is open 24/7, there are always customers, and the kitchen is nearly always in operation besides during the night. The kitchen equipment produces a lot of heat and the occupants give off a lot of latent and sensible heat. The internal components of the building are always producing heat, so the building is nearly always in cooling mode. Z1 - 0° Z2 - 0° Z3 - 0° Z1 - 90° Z2 - 90° Z3 - 90° Z1 - 180° Z2 - 180° Z3 - 180° Wall/Window 635.09 311.87 10987.30 676.67 417.73 10956.79 870.69 528.22 12079.93 Roof 0.00 585.33 2328.02 0.00 585.33 2328.02 0.00 585.33 2530.75 Component Cooling Loads Inf. Sens. Inf. Lat. People Sens. Equip. Sens. 18676.87 25658.22 2992.76 3530.70 1443.69 1983.33 716.59 16974.48 715.60 1063.68 23015.86 4810.91 18676.87 25658.22 2992.76 3530.70 1443.69 1983.33 716.59 16974.48 715.60 1063.68 23015.86 4810.91 18676.87 25658.22 2992.76 3530.70 1443.69 1983.33 716.59 16974.48 774.26 1063.68 22881.30 4807.16 Solar 0.00 0.00 10561.67 0.00 0.00 17799.29 0.00 0.00 6255.92 People Lat. Equip. Lat. 2400.00 0.00 581.00 10423.14 18686.67 0.00 2400.00 0.00 581.00 10423.14 18686.67 0.00 2400.00 0.00 581.00 10423.14 18686.67 0.00 Total Cooling Loads (Internal Loads Included) 90000 80000 70000 BTU/hr 60000 50000 40000 30000 20000 10000 0 Z1 - 0° Z2 - 0° Z3 - 0° Z1 - 90° Z2 - 90° Z3 - 90° Zone - Rotation Z1 - 180° Z2 - 180° Z3 - 180°