V CA QUALITY SERVICE COMMITMENT CIVIL MBE ENGINEERS, INC. ■ ■ STRUCTURAL DBE ■ SBE COUNTY OF LOS ANGELES MIRA LOMA DETENTION CENTER 45100 60th Street West. Lancaster, CA 93536 July 30, 2014 Hydraulics/Hydrology and Site Storm Drainage System Prepared For: DLR GROUP 3130 Wilshire Blvd., 6th floor Santa Monica, CA 90403 Prepared by: VIRGIL C. AOANAN, P.E., S.E., QSD Los Angeles 3951 Medford Street, Los Angeles CA 90063 T e l: 3 2 3 - 7 2 9 - 6 0 9 8 ▪ F a x : 3 2 3 - 7 2 9 - 6 0 4 3 e-mail: vca@vcaeng.com I r v in e 2151 Michelson Dr. # 242, Irvine, CA 92612 T e l: 9 4 9 - 6 7 9 - 0 8 7 0 ▪ Fa x: 9 4 9 - 6 7 9 - 9 3 7 0 www.vcaeng.com V CA QUALITY SERVICE COMMITMENT CIVIL MBE ENGINEERS, INC. ■ ■ STRUCTURAL DBE ■ SBE TABLE OF CONTENTS 1.0 INTRODUCTION ................................................................................................................................. 1 2.0 PROJECT SITE HYDROLOGY ............................................................................................................. 1 2.1 HYDROLOGY DATA, DESIGN CRITERIA ........................................................................................ 2 2.2 PROJECT LOCATION ...................................................................................................................... 3 3.0 EXISTING SITE CONDITION AND STORM DRAINAGE SYSTEM ........................................................ 3 3.1 GEOTECHNICAL REPORT .............................................................................................................. 3 3.2 GROUNDWATER LEVEL ................................................................................................................ 3 3.3 INFILTRATION RATE ..................................................................................................................... 3 4.0 PROPOSED STORM DRAINAGE SYSTEM ........................................................................................... 5 .......................................................... 5 4.1 EXISTING AND PROPOSED PERVIOUS / IMPERVIOUS AREA 4.2 PROPOSED RUNOFF CONVEYANCE AND DISCHARGE SYSTEM . 4.3 CATCH BASIN , BIOSWALE , INFILTRATION STRUCTURE . ............................................................. 7 5.0 5.1 6.0 .................................................. 5 LOW IMPACT DEVELOPMENT ........................................................................................................... 7 STORMWATER QUALITY DESIGN ................................................................................................. 8 PROJECT CONCLUSIONS AND RECOMMENDATIONS ....................................................................... 8 1 Los Angeles 3951 Medford Street, Los Angeles CA 90063 T e l: 3 2 3 - 7 2 9 - 6 0 9 8 ▪ F a x : 3 2 3 - 7 2 9 - 6 0 4 3 e-mail: vca@vcaeng.com I r v in e 2151 Michelson Dr. # 242, Irvine, CA 92612 T e l: 9 4 9 - 6 7 9 - 0 8 7 0 ▪ Fa x: 9 4 9 - 6 7 9 - 9 3 7 0 www.vcaeng.com V CA QUALITY SERVICE COMMITMENT CIVIL MBE 1.0 ENGINEERS, INC. ■ ■ STRUCTURAL DBE ■ SBE INTRODUCTION This Hydrology Report summarizes the storm drain design criteria, Low Impact Development (LID) and Standard Urban Stormwater Mitigation Plan (SUSMP). The report provides general information about the existing condition, site hydrology, Low Impact Development requirements, and site storm drainage system. This report is to provide insights to the design and build contractor the basic need of the site to comply with all applicable code, regulation and AHJ’s the storm water management requirements. Design and build contractor should design the proposed drainage system of the project to adequately meet the drainage needs of the project site including LID and SUSMP requirements. Among the list includes the design of the following: Storm Drain System – hydraulics, pipe and pipe sizing Catch Basins Retention/Detention Structure Infiltration, Filtration and other Low Impact Development application Mechanical Cleaning Device Using Continuous Deflection Separation or Filter Inserts Standards The following Standards have to be used but not limited to in complying with Storm Water Management for this project. 1. 2. 3. 4. 5. LA County Hydrology Manual (2006) County of Los Angeles Low Impact Development (LID) Standards Manual (2009) Standard Urban Stormwater Mitigation Plan (SUSMP) Manual (2002) Development Best Management Practices Handbook (2012) California Green Building Standards Code, California Code of Regulations, Title 24, Part 11 (2010) 2.0 PROJECT SITE HYDROLOGY Site Description The existing site storm drainage conditions do not meet current design requirements and is determined to be under designed per the design guidelines of the County of Los Angeles Hydrology Manual 2006 25-year storm event. A majority of the stormwater runoff is allowed to sheet flow off the site without considering the Best Management Practices of the Standard Urban Stormwater Mitigation Plan. Project Redevelopment Area Project limit of work incorporates approximately 38 acres within AB 900 boundary line. Design and build contractor may choose how the storm water will be collected, treated and discharge based on applicable code, regulation and standard. The information provided under this report is a schematic guide for design of storm drainage system. Based on the schematic sketch, the proposed redevelopment area was divided into three separate tributary areas. Los Angeles 3951 Medford Street, Los Angeles CA 90063 Tel: 323-729-6098 ▪ Fax: 323-729-6043 e-mail: vca@vcaeng.com I r v in e 2151 Michelson Dr. # 242, Irvine, CA 92612 T e l: 9 4 9 - 6 7 9 - 0 8 7 0 ▪ Fa x: 9 4 9 - 6 7 9 - 9 3 7 0 www.vcaeng.com 1 V CA QUALITY SERVICE COMMITMENT CIVIL MBE ENGINEERS, INC. ■ ■ STRUCTURAL DBE ■ SBE Project Location Mira Loma Detention Center is located in the City of Lancaster at the southeast intersection of West Avenue I and West 60th Street. Project site address of the facility is 45100 60th Street West Lancaster, CA 93536 with an approximate coordinate: Longitude of 34o 42’ 2” and Latitude of 118o 13’ 59”. 2.1 HYDROLOGY DATA , DESIGN CRITERIA The following hydrology data and design criteria are used in the calculations of the runoff. Basis of Design For this project the Los Angeles County Department of Public Works – Hydrology Manual, January 2006 for storm drainage system was used, Los Angeles County Low Impact Development Manual and guidelines. The Hydrology Calculation for Storm Flow Rate for the total drainage area were based on the Modified Rational Method. The analysis of the hydraulic characteristic of the storm drain system is performed using the Tc- Calculator Method. Manning's Equation for the calculation of the storm drain pipe sizing. The catch basins design calculations are carried out based on the capacity of the flow rate from the draining subarea to the individual catch basin and are designed for the largest flow from the Tc calculations. Rainfall Depth The rainfall at this specific project site is 3.10 inches for 50-year, 24-hour and 2.72 inches for 25-year, 24-hour. The rainfall depth was found from the Los Angeles County Hydrology Manual 2006. Soil Type The numerical soil classification used for the project is 120 and was found from the Los Angeles County Hydrology Manual 2006. Percentage of Imperviousness The percentage of imperviousness for the propose post-development within the project scope is unknown at this moment but for calculation purposes only it will be assumed at 82% of the total area. Design and build contractor to verify this during design and use the calculated numbers to their pipe sizing and hydrology analysis. Los Angeles 3951 Medford Street, Los Angeles CA 90063 Tel: 323-729-6098 ▪ Fax: 323-729-6043 e-mail: vca@vcaeng.com I r v in e 2151 Michelson Dr. # 242, Irvine, CA 92612 T e l: 9 4 9 - 6 7 9 - 0 8 7 0 ▪ Fa x: 9 4 9 - 6 7 9 - 9 3 7 0 www.vcaeng.com 2 V CA QUALITY SERVICE COMMITMENT 2.2 CIVIL MBE ENGINEERS, INC. ■ ■ STRUCTURAL DBE ■ SBE PROJECT LOCATION Mira Loma Detention Center is located in the City of Lancaster at the southeast intersection of West Avenue I and West 60th Street. Project site address of the facility is 45100 60th Street West Lancaster, CA 93536 with an approximate coordinate: Longitude of 34o 42’ 2” and Latitude of 118o 13’ 59”. 3.0 EXISTING SITE CONDITION AND STORM DRAINAGE SYSTEM The site generally slopes from North West to South East (some to the Eastside) through v –gutter and sheet flow along the existing pavement. The storm water run-off discharges directly to offsite around the site without proper treatment (see Figure 1). Underground storm drainage system information are unknown and the available as-built drawing does not provide show any underground storm drainage pipe. Another verification information Although topographic survey shows few isolated catch basins around the project site yet the underground storm drainage line are unknown. 3.1 GEOTECHNICAL REPORT Information and recommendations from the soils report prepared by Converse Consultants entitled “Geohazard Study Report” Mira Loma Detention Center, dated June 12, 2014, which are relevant to hydrology and hydraulics of the project site is partly included on this report. See attachment in page 35. 3.2 GROUNDWATER LEVEL Perched groundwater was encountered during the subsurface exploration at depths approximately of 27 feet below the ground surface. The historic high groundwater level in this area ranges from approximately 110 to 150 feet or more below the existing ground water surface. 3.3 INFILTRATION RATE From the geotechnical report, the percolation rate of the site has an approximately 1.47 in./hr. From the four boring numbers tested. In accordance with County of Los Angeles requirements, the minimum percolation rate for design of infiltration system for the storm water management is 0.50 inch/hour. See attachment in page 35. Los Angeles 3951 Medford Street, Los Angeles CA 90063 Tel: 323-729-6098 ▪ Fax: 323-729-6043 e-mail: vca@vcaeng.com I r v in e 2151 Michelson Dr. # 242, Irvine, CA 92612 T e l: 9 4 9 - 6 7 9 - 0 8 7 0 ▪ Fa x: 9 4 9 - 6 7 9 - 9 3 7 0 www.vcaeng.com 3 V CA QUALITY SERVICE COMMITMENT CIVIL MBE ENGINEERS, INC. ■ ■ STRUCTURAL DBE ■ SBE FIGURE 1 Los Angeles 3951 Medford Street, Los Angeles CA 90063 Tel: 323-729-6098 ▪ Fax: 323-729-6043 e-mail: vca@vcaeng.com I r v in e 2151 Michelson Dr. # 242, Irvine, CA 92612 T e l: 9 4 9 - 6 7 9 - 0 8 7 0 ▪ Fa x: 9 4 9 - 6 7 9 - 9 3 7 0 www.vcaeng.com 4 V CA QUALITY SERVICE COMMITMENT CIVIL MBE ENGINEERS, INC. ■ ■ STRUCTURAL DBE ■ SBE 4.0 PROPOSED STORM DRAINAGE SYSTEM 4.1 EXISTING AND PROPOSED PERVIOUS /IMPERVIOUS AREA Based on topo survey determination of pervious impervious area of existing site, it is difficult and challenging to clearly recognize paved, dirt, and planter area due to unclear identification of the said features. For estimating purposes, the pervious is approximately 15.50 acres and the impervious area is about 28.50 acres from a total of 44 acres AB 900 Project improvement boundary. At schematic level of the proposed site, defining the landscape, planter area can be challenging as this will change over few more revisions from concept to construction document. Design and Build contractor will have to verify this during the project design stage and identify the design pervious/impervious of the site. For purposes of providing hydrology report and guide, VCA approximated the proposed improvement pervious / imperviousness of the site to have it at between 15 to 20% pervious and between 80 to 85% impervious. Table 1 – Existing and Proposed Impervious/Pervious Areas Site Condition Pervious Area (Acres) Impervious Area (Acres) % Pervious % Impervious Existing 15.43 28.34 35.00 65.00 Proposed 7.80 35.97 18.00 82.00 Note: The above figures are for design guide and reference only. Design and build contractor to calculate, verify existing and the proposed pervious and impervious component. 4.2 PROPOSED RUNOFF CONVEYANCE AND DISCHARGE SYSTEM. Runoff conveyance is a method of safely storing storm water to a LID receiving planter area or infiltration structure promoting infiltration or filtering of the runoff. Discharging describes the different types of ways the storm water runoff are released from the project site. A schematic storm drainage system on figure 2 provides an insights on how the drainage can be handled, treated and discharge. Design and build contractor needs to design the drainage system that addresses the hydraulics and hydrology of the project and in compliance with the applicable requirements. The grading for the new facility should drain towards the catch basin, bioswale, planter box, and/or underground infiltration structure and ultimately treat the run-off water before discharge. The onsite drainage system conveys and discharges runoff from the site to a catch basin with filter inserts as pre-treatment, then through a bioswale area and eventually to the infiltration structures, and bubbler catch basin with an overflow to the street or adjacent land area. Infiltration structures should be sized to handle 100% retention with a drawdown time of less than within 48 hours. Storm drainage pipe sizes will have a 6” diameter as a minimum size and can be as big as between 18” to 30” diameter pipe size on the main line depending on the tributary area, slope of the pipe and number discharge points. Design and Build contractor will have to base their sizing based on their design options. The schematic storm drainage shown on the narrative, sketches, plan are for reference and guide only. Los Angeles 3951 Medford Street, Los Angeles CA 90063 Tel: 323-729-6098 ▪ Fax: 323-729-6043 e-mail: vca@vcaeng.com I r v in e 2151 Michelson Dr. # 242, Irvine, CA 92612 T e l: 9 4 9 - 6 7 9 - 0 8 7 0 ▪ Fa x: 9 4 9 - 6 7 9 - 9 3 7 0 www.vcaeng.com 5 V CA QUALITY SERVICE COMMITMENT CIVIL MBE ENGINEERS, INC. ■ ■ STRUCTURAL DBE ■ SBE FIGURE 2 Los Angeles 3951 Medford Street, Los Angeles CA 90063 Tel: 323-729-6098 ▪ Fax: 323-729-6043 e-mail: vca@vcaeng.com I r v in e 2151 Michelson Dr. # 242, Irvine, CA 92612 T e l: 9 4 9 - 6 7 9 - 0 8 7 0 ▪ Fa x: 9 4 9 - 6 7 9 - 9 3 7 0 www.vcaeng.com 6 V CA QUALITY SERVICE COMMITMENT CIVIL MBE ENGINEERS, INC. ■ ■ STRUCTURAL DBE ■ SBE 4.3 CATCH BASIN , BIOSWALE , INFILTRATION STRUCTURE. Catch Basin The catch basin design calculation is carried out based on the capacity of the flow rate from the draining subarea to the individual catch basin and was designed for the largest flow from the LA County Tc calculator Version 2.03. There is one size of catch basin used in this project, 12” x 12”. See Part II: Calculations, Attachment II-4 for calculation spreadsheets. Bio Swale The design frequency used for this project was a 25-year, 24-hour storm event. This design frequency is used under the LA County Hydrology Manual (2006). Infiltration Retention Structure Infiltration retention structure is a combination of Chambermaxx Retention System and Ecorain Tank (or approved equal) underneath the surface area. These infiltration structures will capture the surface stormwater runoff that flows into the catch basins and from the bio-swale area as a pre-treatment then collected to the infiltration structure where eventually the stored volume capacity will percolate down to the ground. Excess water will overflow to and discharge clean to the street or adjacent undeveloped land area. 5.0 LOW IMPACT DEVELOPMENT Low Impact Development (LID) is a new approach to managing rainfall and stormwater runoff. LID practices were designed to protect surface and groundwater quality, maintain the integrity of ecosystems, and preserve the physical integrity of receiving waters by controlling rainfall and stormwater runoff at or close to the source. LID is being applied to this project per LA County. This project will prioritize the selection of Best Management Practices (BMPs) to treat stormwater pollutants and reduce stormwater runoff volume. Per LID requirements, BMPs should be implemented in the following hierarchy: 1. 2. 3. 4. 5. Infiltrate Biofiltration Capture and use Mechanical Device Combination of above The BMPs that will be used are infiltration and mechanical device. Los Angeles 3951 Medford Street, Los Angeles CA 90063 Tel: 323-729-6098 ▪ Fax: 323-729-6043 e-mail: vca@vcaeng.com I r v in e 2151 Michelson Dr. # 242, Irvine, CA 92612 T e l: 9 4 9 - 6 7 9 - 0 8 7 0 ▪ Fa x: 9 4 9 - 6 7 9 - 9 3 7 0 www.vcaeng.com 7 V CA QUALITY SERVICE COMMITMENT CIVIL MBE ENGINEERS, INC. ■ ■ STRUCTURAL DBE ■ SBE 5.1 STORMWATER QUALITY DESIGN The peak volume to be mitigated designed with a 3/4 inch of rainfall is determined based on the Los Angeles County Department of Public Works SUSMP Manual dated September 2002. A 3/4-inch 24-hour storm event was used and the result for the Stormwater Quality Design Volume (SQDV) is approximately 90,000 cu.ft. are were distributed into three (3) different location as shown on schematic storm drainage plan. The drawdown time is an LA County requirement where it would have to meet a minimum of 48 hours for all the water infiltrated through the system. 6.0 PROJECT CONCLUSIONS AND RECOMMENDATIONS After analysis of the site hydrology of the existing and schematic propose improvement of the site, the following are the recommendations of VCA Engineers but this information is not limited to the items provided below. Design and build contractor needs to verify and design required parameters in compliance with all applicable codes, regulation, standard and jurisdictional requirement. 1. The existing storm drainage system needs to be redesigned to comply with the stormwater quality and quantity control before it is discharged to street. The proposed storm drainage system must be adequate to convey the peak flow rate due to the 25-year, 24-hour rainfall depth. 2. The retention system, and infiltration structure to be sized accordingly with consideration of the percolation rate provided by geotechnical engineer and should be adequate to capture and treat the stormwater runoff from the project site. Drawdown volume capacity at 48 hours must also be verified and calculated to satisfy this requirement. 3. Total capacity retention volume of stormwater runoff of the infiltration structures should accommodate the stormwater runoff from the project site. Provide and utilized an overflow line that will discharge clean to the adjacent street of undeveloped area (within the project property) approved by jurisdictional agency. 4. Provide pre-treatment method of cleaning for storm water run-off such as filter inserts in a catch basins, continuous deflection system storm interceptor (CDS) or other equal products that will insure the quality of the run-off prior to the infiltration system or discharge area. 5. Provide maintenance program will include the following key components: a. Inspection and removal of sediment, debris, and other pollutants on containment chambers and detention structure per manufacturer recommendation. b. Sediment and debris (litter, leaves, papers, cans, etc.) within the area, especially around the trench drains and catch basins with filter inserts, will be collected and removed. c. The frequency of sweeping will be based on the amount of sediment and debris generated. Los Angeles 3951 Medford Street, Los Angeles CA 90063 Tel: 323-729-6098 ▪ Fax: 323-729-6043 e-mail: vca@vcaeng.com I r v in e 2151 Michelson Dr. # 242, Irvine, CA 92612 T e l: 9 4 9 - 6 7 9 - 0 8 7 0 ▪ Fa x: 9 4 9 - 6 7 9 - 9 3 7 0 www.vcaeng.com 8 V CA QUALITY SERVICE COMMITMENT CIVIL MBE ENGINEERS, INC. ■ ■ STRUCTURAL DBE ■ SBE HYDRAULICS/HYDROLOGY CALCULATIONS AND REFERENCES Tc Results – 25 year, 24 Hour Storm Event………….…….……..… 10 Peak Mitigated Flow / Quality Volume………….…….…………… 11 Hydrology Map………….…….….…….…………….…….………. 12 Hydrology Map Locator………….…….…………….…….…….…. 13 Soil Type………….…….…………….…….…………….…….…... Percolation Test (from Geotechnical Report Info) ………….…..….. 15 Cut Sheets………….…….…………….…….…………….….…..… 16 14 - Chambermaxx………….…….…………….…….……………. 16 - Ecorain Tank………….…….…………….…….………….…. - Filter Inserts………….…….…………….…….…………...…. 18 - Continues Deflection System………….…….……………...… 19 SUSMP Calculation………….…….…………….…….…………… 20 Detention Tank Calculation………….…….…………….…….…… 21 Los Angeles 3951 Medford Street, Los Angeles CA 90063 Tel: 323-729-6098 ▪ Fax: 323-729-6043 e-mail: vca@vcaeng.com I r v in e 2151 Michelson Dr. # 242, Irvine, CA 92612 T e l: 9 4 9 - 6 7 9 - 0 8 7 0 ▪ Fa x: 9 4 9 - 6 7 9 - 9 3 7 0 www.vcaeng.com 17 9 V CA QUALITY SERVICE COMMITMENT CIVIL MBE ENGINEERS, INC. ■ ■ STRUCTURAL DBE ■ SBE TC CALCS FOR 25-YEAR, 24 HOUR STORM EVENT: Los Angeles 3951 Medford Street, Los Angeles CA 90063 Tel: 323-729-6098 ▪ Fax: 323-729-6043 e-mail: vca@vcaeng.com PEAK FLOW I r v in e 2151 Michelson Dr. # 242, Irvine, CA 92612 T e l: 9 4 9 - 6 7 9 - 0 8 7 0 ▪ Fa x: 9 4 9 - 6 7 9 - 9 3 7 0 www.vcaeng.com 10 V CA QUALITY SERVICE COMMITMENT CIVIL MBE ENGINEERS, INC. ■ ■ STRUCTURAL DBE ■ SBE PEAK MITIGATED FLOW/ QUALITY VOLUME: Los Angeles 3951 Medford Street, Los Angeles CA 90063 Tel: 323-729-6098 ▪ Fax: 323-729-6043 e-mail: vca@vcaeng.com I r v in e 2151 Michelson Dr. # 242, Irvine, CA 92612 T e l: 9 4 9 - 6 7 9 - 0 8 7 0 ▪ Fa x: 9 4 9 - 6 7 9 - 9 3 7 0 www.vcaeng.com 11 V CA QUALITY SERVICE COMMITMENT CIVIL MBE ENGINEERS, INC. ■ ■ STRUCTURAL DBE ■ SBE HYDROLOGY MAP: Los Angeles 3951 Medford Street, Los Angeles CA 90063 Tel: 323-729-6098 ▪ Fax: 323-729-6043 e-mail: vca@vcaeng.com I r v in e 2151 Michelson Dr. # 242, Irvine, CA 92612 T e l: 9 4 9 - 6 7 9 - 0 8 7 0 ▪ Fa x: 9 4 9 - 6 7 9 - 9 3 7 0 www.vcaeng.com 12 V CA QUALITY SERVICE COMMITMENT CIVIL MBE ENGINEERS, INC. ■ ■ STRUCTURAL DBE ■ SBE HYDROLOGY MAP LOCATOR: Los Angeles 3951 Medford Street, Los Angeles CA 90063 Tel: 323-729-6098 ▪ Fax: 323-729-6043 e-mail: vca@vcaeng.com I r v in e 2151 Michelson Dr. # 242, Irvine, CA 92612 T e l: 9 4 9 - 6 7 9 - 0 8 7 0 ▪ Fa x: 9 4 9 - 6 7 9 - 9 3 7 0 www.vcaeng.com 13 V CA QUALITY SERVICE COMMITMENT CIVIL MBE ENGINEERS, INC. ■ ■ STRUCTURAL DBE ■ SBE SOIL TYPE: Los Angeles 3951 Medford Street, Los Angeles CA 90063 Tel: 323-729-6098 ▪ Fax: 323-729-6043 e-mail: vca@vcaeng.com I r v in e 2151 Michelson Dr. # 242, Irvine, CA 92612 T e l: 9 4 9 - 6 7 9 - 0 8 7 0 ▪ Fa x: 9 4 9 - 6 7 9 - 9 3 7 0 www.vcaeng.com 14 V CA QUALITY SERVICE COMMITMENT CIVIL MBE ENGINEERS, INC. ■ ■ STRUCTURAL DBE ■ SBE PERCOLATION TEST: Los Angeles 3951 Medford Street, Los Angeles CA 90063 Tel: 323-729-6098 ▪ Fax: 323-729-6043 e-mail: vca@vcaeng.com I r v in e 2151 Michelson Dr. # 242, Irvine, CA 92612 T e l: 9 4 9 - 6 7 9 - 0 8 7 0 ▪ Fa x: 9 4 9 - 6 7 9 - 9 3 7 0 www.vcaeng.com 15 V CA QUALITY SERVICE COMMITMENT CIVIL MBE ENGINEERS, INC. ■ ■ STRUCTURAL DBE ■ SBE CHAMBERMAXX: INFILTRATION/DETENTION STRUCTURE Los Angeles 3951 Medford Street, Los Angeles CA 90063 Tel: 323-729-6098 ▪ Fax: 323-729-6043 e-mail: vca@vcaeng.com I r v in e 2151 Michelson Dr. # 242, Irvine, CA 92612 T e l: 9 4 9 - 6 7 9 - 0 8 7 0 ▪ Fa x: 9 4 9 - 6 7 9 - 9 3 7 0 www.vcaeng.com 16 V CA QUALITY SERVICE COMMITMENT CIVIL MBE ENGINEERS, INC. ■ ■ STRUCTURAL DBE ■ SBE Los Angeles 3951 Medford Street, Los Angeles CA 90063 Tel: 323-729-6098 ▪ Fax: 323-729-6043 e-mail: vca@vcaeng.com I r v in e 2151 Michelson Dr. # 242, Irvine, CA 92612 T e l: 9 4 9 - 6 7 9 - 0 8 7 0 ▪ Fa x: 9 4 9 - 6 7 9 - 9 3 7 0 www.vcaeng.com 17 V CA QUALITY SERVICE COMMITMENT CIVIL MBE ENGINEERS, INC. ■ ■ STRUCTURAL DBE ■ SBE FILTER INSERTS: Los Angeles 3951 Medford Street, Los Angeles CA 90063 Tel: 323-729-6098 ▪ Fax: 323-729-6043 e-mail: vca@vcaeng.com I r v in e 2151 Michelson Dr. # 242, Irvine, CA 92612 T e l: 9 4 9 - 6 7 9 - 0 8 7 0 ▪ Fa x: 9 4 9 - 6 7 9 - 9 3 7 0 www.vcaeng.com 18 V CA QUALITY SERVICE COMMITMENT CIVIL MBE ENGINEERS, INC. ■ ■ STRUCTURAL DBE ■ SBE CONTINUOUS DEFLECTION SEPARATOR: Los Angeles 3951 Medford Street, Los Angeles CA 90063 Tel: 323-729-6098 ▪ Fax: 323-729-6043 e-mail: vca@vcaeng.com I r v in e 2151 Michelson Dr. # 242, Irvine, CA 92612 T e l: 9 4 9 - 6 7 9 - 0 8 7 0 ▪ Fa x: 9 4 9 - 6 7 9 - 9 3 7 0 www.vcaeng.com 19 V CA QUALITY SERVICE COMMITMENT CIVIL MBE ENGINEERS, INC. ■ ■ STRUCTURAL DBE ■ SBE Los Angeles 3951 Medford Street, Los Angeles CA 90063 Tel: 323-729-6098 ▪ Fax: 323-729-6043 e-mail: vca@vcaeng.com I r v in e 2151 Michelson Dr. # 242, Irvine, CA 92612 T e l: 9 4 9 - 6 7 9 - 0 8 7 0 ▪ Fa x: 9 4 9 - 6 7 9 - 9 3 7 0 www.vcaeng.com 20 V CA QUALITY SERVICE COMMITMENT CIVIL MBE ENGINEERS, INC. ■ ■ STRUCTURAL DBE ■ SBE Los Angeles 3951 Medford Street, Los Angeles CA 90063 Tel: 323-729-6098 ▪ Fax: 323-729-6043 e-mail: vca@vcaeng.com I r v in e 2151 Michelson Dr. # 242, Irvine, CA 92612 T e l: 9 4 9 - 6 7 9 - 0 8 7 0 ▪ Fa x: 9 4 9 - 6 7 9 - 9 3 7 0 www.vcaeng.com 21