Generator Interconnection Request Wind Generation Facility Data Generating Facility Name: Maximum Net Export Capability (at POI): MW (Gross Generation – Station Service) Gross Generator Capability (at Generator Terminals): MW Station Service Load (including losses): MW 1. Simplified One-Line Diagram. This should be similar to Figure below. If it is different, please mark the difference on the diagram below. Interconnection Transmission Line Collector System Equivalent Main Transformer(s) WTG Step-up Transformer Wind Turbine Generator Equivalent Point of Interconnection WTG Dynamic Reactive Device Fixed Reactive Device PF Correction Capacitors 2. Interconnection Transmission Line. a) Point of Interconnection (substation/transmission line name): b) Line voltage: kV, line rating at 95F ambient: MVA, line length c) R1 = ohm or pu on 100 MVA and line kV base (positive sequence) d) X1 = ohm or pu on 100 MVA and line kV base (positive sequence) e) B1 = F or f) R0 = ohm or pu on 100 MVA and line kV base (zero sequence) g) X0 = ohm or pu on 100 MVA and line kV base (zero sequence) h) B0 = F or 3. Main Transformer. Miles/Feet pu on 100 MVA and line kV base (positive sequence) pu on 100 MVA and line kV base (zero sequence) Number of main transformers: Two-Winding Main Transformer Data (if applicable): a) Rating (OA/FA/FA): / / MVA b) Nominal Voltage for each winding (Low/High): / kV c) Winding Connections (Low/High): Delta or Wye / Delta or Wye d) Available tap positions: / / e) Positive sequence impedance Z1: f) Zero sequence impedance Z0: / %, %, / kV or % # of taps. X/R on self-cooled (OA) MVA rating above. X/R on self-cooled (OA) MVA rating above. g) For padmount transformer, construction: 3 / 4 / 5 -legged Page 1 of 6 Dated: 2/9/2016 Generator Interconnection Request Wind Generation Facility Data Three-Winding Main Transformer Data (if applicable) h) GSU connection and winding (please attach diagram and mark to reference this form). H Winding Data Full load ratings (i.e. OA/FA/FA) / X Winding Data / / MVA Rated high side voltage base / kV / / MVA kV / kV Delta or Wye connected / / Present Tap Setting (if applicable) Neutral solidly grounded? (or) Neutral Grounding Resistor (if applicable) / MVA Delta or Wye connected Tap positions available Y Winding Data kV / / / Delta or Wye connected / / kV / / / kV kV kV kV Ohms Ohms Ohms kV kV kV BIL rating Three-Winding Main Transformer Impendance Data (if applicable) H-X Winding Data Transformer base for impedances provided H-Y Winding Data MVA X-Y Winding Data MVA MVA Positive sequence impedance Z1 % X/R % X/R % X/R Zero sequence impedance Z0 % X/R % X/R % X/R 4. Collector System Equivalent Model. a) Collector system voltage = kV b) Collector system equivalent model rating at 95F ambient = MVA c) R1 = ohm or pu on 100 MVA and collector kV base (positive sequence) d) X1 = ohm or pu on 100 MVA and collector kV base (positive sequence) e) B1 = F or f) R0 = ohm or pu on 100 MVA and collector kV base (zero sequence) g) X0 = ohm or pu on 100 MVA and collector kV base (zero sequence) h) B0 = F or pu on 100 MVA and collector kV base (positive sequence) pu on 100 MVA and collector kV base (zero sequence) Page 2 of 6 Dated: 2/9/2016 Generator Interconnection Request Wind Generation Facility Data 5. Wind-turbine generator (WTG) Step-up Transformers. a) Number of WTG step-up transformers: Rating: MVA Two-Winding WTG Step-up Transformer Data (if applicable): b) Nominal Voltage for each winding (Low/High): / kV c) Winding Connections (Low/High): Delta or Wye / Delta or Wye d) Available taps: / / / / e) Positive sequence impedance (Z1) kV or %, f) Zero sequence impedance (Z0) %, % # of taps. X/R on MVA rating above. X/R on MVA rating above. Three-Winding WTG Step-up Transformer Data (if applicable) g) GSU connection and winding (please attach diagram and mark to reference this form). H Winding Data Full load ratings (i.e. OA/FA/FA) Rated high side voltage base Tap positions available Present Tap Setting (if applicable) Neutral solidly grounded? (or) Neutral Grounding Resistor (if applicable) BIL rating / X Winding Data / / MVA / / MVA kV / / / MVA kV Delta or Wye connected / Y Winding Data kV Delta or Wye connected / kV / / / Delta or Wye connected / / kV / / / kV kV kV kV Ohms Ohms Ohms kV kV kV Three-Winding WTG Step-up Transformer Impendance Data (if applicable) H-X Winding Data Transformer base for impedances provided H-Y Winding Data MVA X-Y Winding Data MVA MVA Positive sequence impedance Z1 % X/R % X/R % X/R Zero sequence impedance Z0 % X/R % X/R % X/R Page 3 of 6 Dated: 2/9/2016 Generator Interconnection Request Wind Generation Facility Data 6. WTG Module Data. a) Number of WTGs: b) Nameplate Rating (each WTG): MW c) Full load rating (each WTG): MW Type 1 – Squirrel-cage induction generator Type 2 – Wound rotor induction machine with variable rotor resistance Type 3 – Doubly-fed asynchronous generator Type 4 – Full converter interface d) WTG Manufacturer and Model: e) WTG Type: Choose Type, see box to the right For Type 1 or Type 2 WTGs: - Uncompensated power factor at full load: - Power factor correction capacitors at full load: - Complete the Interconnection Request application Induction Generator data section. Mvar For Type 3 or Type 4 WTGs: - Maximum over-excited power factor at full load: Mvar - Maximum under-excited power factor at full load: - Control mode (e.g., voltage, power factor, or reactive power): Mvar f) Provide with this form the dynamic modeling data, including plant volt/var control function model and active power/frequency control function model, in a Siemens/PTI PSS/E standard model. If a user-written model is submitted in place of a standard WTG library model, it must include the model characteristics, including block diagrams, values and names for all model parameters and a list of all state variables. All of the associated files, including source code, for dynamic modeling should be in PSS/E versions 30, 32, and 33, and must be shareable on an interconnection-wide basis to support use in the interconnection-wide cases.1 7. Plant Reactive Power Compensation (beyond the inverters built-in reactive capability). a) Type of reactive compensation device(s): Fixed or Dynamic b) Individual fixed shunt reactive device type: - Size of each: × MVA c) Dynamic reactive control device (e.g., SVC, STATCOM): d) Control range at rated Mwoutput: Mvar (lead and lag) e) Control mode (e.g., voltage, power factor, reactive power): f) Regulation point: 1 As required by NERC Reliability Standard MOD-32-1. Page 4 of 6 Dated: 2/9/2016 Generator Interconnection Request Wind Generation Facility Data g) Describe the overall reactive power control strategy: h) Provide with this form the dynamic modeling data in a Siemens/PTI PSS/E standard model. If a user-written model is submitted in place of a standard model, it must include the model characteristics, including block diagrams, values and names for all model parameters, and a list of all state variables. All of the associated files, including source code, for dynamic modeling should be in PSS/E versions 30, 32, and 33, and must be shareable on an interconnection-wide basis to support use in the interconnection-wide cases.2 8. Short Circuit Response of WTG. a) Provide plots of maximum and minimum short circuit output of wind turbine generator units vs. MV bus voltage for 0-3 cycles and for 3 cycles +(examples on page 6): b) Per-unit MV bus voltage at which crowbar is initiated: c) Equivalent per-unit machine impedance when crowbar is initiated: 9. Short Circuit Contribution of the plant at the Point of Interconnection. a) Maximum Three Phase Fault Current: Amps and Duration: b) Maximum Single Line to Ground Fault* Current: Amps and Duration: * Single Line to Ground Fault at the Point of Interconnection with ties to utility open. 10. Harmonic Distortion of the plant at the Point of Interconnection. a) Total Harmonic Current Distortion: % b) Provide with this data form the individual harmonic currents through 49th harmonic, in % of fundamental current rating. 2 As required by NERC Reliability Standard MOD-32-1. Page 5 of 6 Dated: 2/9/2016 Generator Interconnection Request Wind Generation Facility Data Example of Momentary Short Circuit Output 1) Per-Unit Momentary Short Circuit Capability (0-3 cycles) vs. MV bus voltage (MV bus of wind turbine unit transformer) Example of Short Circuit Output After 3 Cycles • Per-Unit Short Circuit Capability (3 cycles+) vs. MV bus voltage (MV bus of wind turbine unit transformer) Page 6 of 6 Dated: 2/9/2016