Instruction for P Type 1 st Grade Mixed

advertisement
Instruction for P Type 1st Grade Mixed-Type Receiver
1. Normal Times: <A> There will be only the green lamp (A.C and power indicating light) and
accumulation indicating lamp (when accumulation is selected) lit on the receiver.
<B> The power indicating lamp will be normal (24V).
2. On Fire: <A> The fire alarming lamp and fire area indicating lamp will be lit, and the main alarm and local alarm
will be ringing.
<B> Same as in <A>. When the transmitter indicating lamp is lit, it indicates fire state with the
transmitter push button is on.
<C> When more than two sensors with operation indicating lamp on the same circuit are operating
simultaneously, only the operation indicating lamp of the sensor operated first will be lit.
<D> When the fire signal input is entered, the accumulation function blocks the detection signal
(voltage on the detection line) instantly. When the fire signal input is entered sequentially until the
accumulation time, the fire alarming lamp and local fire lamp will be lit.
<E> The momentary action will be restored. On the actual fire, it will be judged as fire to ring the
main alarm and local alarm.
<F> If there is failure at the instant detector or a short circuit on the instant line, these are not the
actual fire. Thus, the local fire alarm will not ring. However, the main alarm will ring to inform it to the fire
manager.
<G> The push signal of the receiver will light the operation indicating lamp on the receiver, and the
instant alarm will light the fire alarming lamp and local indicating lamp and ring the main and local alarms.
<H> The flowing water sensor (A, V) and preparatory operation indicating lamp (P, V) will be lit, and
the local alarm and siren will ring.
3. Alarm Stop: <A> When the S/W fire signal input from the main alarm is entered, the main alarm will ring.
Pressing S/W of the main alarm will stop the main alarm. If another fire signal input is entered, the S/W is
released to ring the main alarm again.
<B> Pressing S/W of the local alarm will stop the local alarm. <Please return S/W to the normal
position after operation>
<C> Pressing the ‘Stop S/W’ of the visual alarm will stop the visual alarm. <Please return S/W to
the normal position after operation>
<D> Pressing the ‘Stop S/W’ of siren will stop the siren. <Please return S/W to the normal
position after operation>
<E> Pressing the ‘Stop S/W’ of buzzer will stop the buzzer <Please return S/W to the normal
position after operation>
<F> Pressing the ‘Stop S/W’ of broadcasting will stop the emergency broadcasting
<Please return S/W to the normal position after operation>.
4. Caution for Valve: When the ‘caution for valve’ lamp is lit and the buzzer rings, it indicates the valve is closed.
Please open the valve in this case.
5. Water Level Monitoring: When the ‘water level monitoring’ lamp is lit and the buzzer rings,
it indicates that the water level of the water tank is low.
6. Pump: When the ‘pressure tank’ indicating lamp and operation indicating lamp is lit and the buzzer rings,
it indicates the corresponding pump is in operation.
7. Interlocking Operation Switch: When the ‘automatic (interlocking)’ is on, the operational output is working
when the circuit is in operation. When the switch is on the ‘stop’ position, the starting-up output is in
operation. When the switch is on the ‘stop position’, the starting-up output will be stopped.
8. Automatic (Interlocking) Function: <A> The switch should be on the ‘automatic (interlocking)’ position in
normal state.
<B> When the sensor of the corresponding circuit begins to work, the
starting-up output is in operation. The spring cooler circuit (preparatory operation type) will be operated with
the starting-up output when the corresponding circuit A and B is in operation. The circuit for fire
extinguishing will be operated on the starting-up circuit after 30 seconds since the corresponding circuit A &
B is in operation.
<C> When the corresponding switch on the receiver is on the ‘stop’ position,
the yellow lamp will be lit and, the starting-up output will be stopped.
9. Manual (Interlocking) Function: <A> When the corresponding devices on the receiver panel is manually
operated, the switch positioned on the manual (interlocking) will light the red lamp on.
<B> When the manual (waiting) switch of the corresponding devices is positioned
on the manual operation, the red lamp will be lit to begin the starting-up output.
Type: AC 220C, DC 24V,Window Type, Electric Relay Type, Accumulation/Non-Accumulation Mixed Type
(Outdoor, Indoor Fire Extinguisher, Spring Cooler) Facility, (CO2, powder, halide, water spray) fire
extinguisher, smoke-control device.
Type No.: Su 07-40
Power: AC220V/DC24V
Number of Smoke Sensor Connection: 10 or below per circuit
10. Operation Check Lamp: When the starting-up output is in operation on the corresponding circuit,
the corresponding devices are in operation and the operation check lamp is lit, the buzzer will ring.
11. Restoration: <A> Pressing S/W of the restoration will put out the fire alarm lamp, local indicating lamp and
corresponding device lamp as well as stop the alarm, visual alarm, siren and buzzer.
<B> Restoration failure may be caused by the pressed ‘Push S/W’ on the receiver, bad circuit line,
manual operation position of the sensor due to fire or the manual operation switch.
<C> When the sensor with automatic indicating lamp is in operation, the restoration will be limited
to fire restoration S/W <the restoration to automatic S/W will not be possible).
12. Circuit Test: <A> Positioning the S/W of accumulation function on non-accumulation, pressing the
‘Test S/W’ and turning the S/W of circuit test will light the fire alarm lamp and local indicating lamp sequentially.
13. Continuity Test: <A> Pressing S/W of continuity test will indicate the circuit-break by the indicator
on the continuity tester. When turning S/W of the circuit tester sequentially and the indicator lamp indicates
normal position, it means that the line is normal. If it indicates circuit-break, it means the line is broken.
14. Preparatory Power Test: If pressing S/W of preparatory power makes the power indicating lamp indicate
high (28V) or normal (24V), the battery is normal. If keep pressing, the battery will be completely discharged.
If the indicating lamp indicates low (20V), the batter is not fully charged or faulty.
15. Preparatory Power: <A> The built-in preparatory power is the nickel-cadmium battery.
<B> When the monitoring lamp for the preparatory power is lit, the battery is not fully
charged or faulty. If the power indicating lamp does not indicate normal (24V),
please contact the manufacturer for check-up.
16. Caution for Switch: <A> When the main operational switch is normal, the ‘caution for switch’ lamp is not lit.
When the yellow and red lamp is blinking, please return the corresponding switch to the normal position.
<B> When the manual operation switch is on normal or automatic (interlocking) position,
it indicates normal.
If the yellow and red lamp is blinking, please return the corresponding switch to the normal position.
17. Accumulation Function: <A> Positioning the accumulation switch on the accumulation will start the
accumulation function. When positioned on the non-accumulation, it will operate the same functions
as the common receivers.
<B> Please do not attach the accumulative type sensor when
the receiver is attached. It won’t receive any fire signal.
<C> The accumulation control time of this receiver is approximately 30 seconds.
18. Guide Lamp Interlocking: Positioning S/W of the guide interlocking on fire (interlocking) will light the
guide lamp on fire. If you the S/W is forcefully positioned on the enforced lighting position, it will be
forcefully lit.
Number of Circuits:________Circuits
Preparatory Power: Nickel-Cadmium Batter 24V (Ah)
Voltage: 220V, A24V, A
Number of Alarm Connections: DC24V, 50mA or below
__________ or below
Number of Visual Alarm Connections: DC24V, 150mA or below ________ or below
Number of Siren Connections: _________
Manufacturing No.:
Date of Manufacturing:
Download