07 48 00 PERFORMANCE GUIDE SPECIFICATION CODE COMPLIANT CONTINUOUSLY INSULATED EXTERIOR WALL ASSEMBLY: THERMAL & AIR BARRIER WALL SYSTEM with A RAIN SCREEN ATTACHMENT SYSTEM (horizontal members only) for EXTERIOR SIDING or CLADDING PANELS KNIGHT WALL SYSTEMS – 1.855.KWS.WALL DOW BUILDING SOLUTIONS – 1.866.583.BLUE Edit Date: 2/8/2016 ThermaStop, PanelRail, PanelTek, SidingRail, CI-Girt, HCI-Girt, CI-System & CI are Trademarks of Knight Wall Systems, Inc. THERMAX, Styrofoam & WEATHERMATE are Trademarks of The Dow Chemical Company (“Dow”) or an affiliated company of Dow [Project Name] [Project Location] [Project No.] [Date] SECTION 07 48 00 CODE COMPLIANT CONTINUOUSLY INSULATED WALL ASSEMBLY: THERMAL & AIR BARRIER WALL SYSTEM with A RAIN SCREEN ATTACHMENT SYSTEM for EXTERIOR SIDING or CLADDING PANELS SPEC NOTE: This guide specification is intended for use of a code compliant, continuously insulated, wall assembly with a thermally broken cold formed horizontal metal support/attachment system over 25 PSI rigid foam insulation to provide a substrate for veneer panel attachment. Horizontal girts may be spaced up to 36 inches on center vertically (depending on cladding weight & design wind pressures) and support claddings that weight under 9 pounds per square foot. The maximum allowable spacing and dead load is determined per project. This is a function of the live load plus the dead load being equal to less-than the allowable load per wall anchor. Spacing and maximum loads are typically determined by the manufacturer. Make any required selections, such as insulation thickness, board sizes, etc. where selection is indicated with an [OR] statement, select the appropriate paragraph and delete the inappropriate statement. Delete all SPEC NOTEs and [OR] statements prior to final publication. DISCLAIMER: The manufacturer has reviewed the product information contained in this guide specification. The information is organized and presented to assist the specification writer working on a construction project to select the appropriate products and to save time in writing the project specification Section. The specification writer is responsible for product selection as well as the use and application of this information, and should contact the manufacturer to ensure that all options are available and that the associated specification information is valid and correct. PART 1 - GENERAL 1.1 SUMMARY A. Provide a complete thermally broken, true continuous exterior-insulated, rain screen wall assembly inclusive of the following: 1. Thermal and air barrier wall system 2. Cold-formed metal rain screen support/attachment system 3. [SIDING/CLADDING PANEL] 1.2 REFERENCES SPEC NOTE: A. Select the applicable reference standards to suit the projects requirements. Delete non-applicable standards. ASTM International (ASTM): 1. A792 / A792M-[05]: Standard Specification for Steel Sheet, 55% Aluminum-Zinc AlloyCoated by the Hot-Dip Process. 2. B117-[03] Standard Practice for Operating Salt Spray (Fog) Apparatus. CONTINUOUSLY INSULATED EXTERIOR WALL ASSEMBLY SECTION 07 48 00 - 2 [Design Firm] Edit Date: 2/8/2016 ThermaStop, PanelRail, PanelTek, SidingRail, CI-Girt, CI-System & CI are Trademarks of Knight Wall Systems, Inc. THERMAX, Styrofoam & WEATHERMATE are Trademarks of The Dow Chemical Company (“Dow”) or an affiliated company of Dow [Project No.] [Date] B. [Project Name] [Project Location] 3. C203-[99]: Test Methods for Breaking Load and Flexural Properties of Block-Type Thermal Insulation. 4. C209-[98]: Test Method for Cellulosic Fiber Insulating Board. 5. C518-[04]: Test Method for Steady-State Heat Flux Measurements and Thermal Transmission Properties by Means of the Heat Flow Meter Apparatus. 6. C1029-[05]: Specification for Spray-Applied Rigid Cellular Polyurethane Thermal Insulation. 7. C1289-[06]: Specification for Faced Rigid Cellular Polyisocyanurate Thermal Insulation Board. 8. C1513-[04]: Standard Specification for Steel Tapping Screws for Cold-Formed Steel Framing Connections. 9. D822-[01]: Standard Practice for Filtered Open-Flame Carbon-Arc Exposures of Paint and Related Coatings. 10. D1621-[04a]: Test Method for Compressive Properties of Rigid Cellular Plastics. 11. D1622-[03]: Test Method for Apparent Density of Rigid Cellular Plastics. 12. D2126-[99]: Test Method for Response of Rigid Cellular Plastics to Thermal and Humid Aging. 13. D3402-[93]: Standard Test Method for Tumbler Test for Coke. 14. D4214-[07]: Method of Evaluating Degree of Chalking of Exterior Paints. 15. E8-[08]: Standard Test Method for Tension Testing of Metallic Materials. 16. E72-[05]: Standard Strength Tests of Panels for Building Construction. 17. E84-[05]: Test Method for Surface Burning Characteristics of Building Materials. 18. E96/E96M-[05]: Test Method for Water Vapor Transmission of Materials. 19. E330-[02]: Standard Test Method for Structural Performance of Exterior Windows, Doors, Skylights and Curtain Walls by Uniform Static Air Pressure Difference. 20. E331-[00(2009)]: Test Method for Water Penetration of Exterior Windows, Curtain Walls and Doors by Uniform Static Air Pressure Difference. 21. E2357-[05]: Test Method for Determining Air Leakage of Air Barrier Assemblies. 22. E283-[04]: Standard Test Method for Determining Rate of Air Leakage Through Exterior Windows, Curtain Walls and Doors under Specific Pressure Differences Across the Specimen. American Architectural Manufacturers Association (AAMA): 1. C. American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE): 1. D. [Design Firm] 4880 [07]: Class I Wall and Ceiling Panels Building Corner Fire Test. Underwriters Laboratories Inc. (UL): 1. F. 90.1-2010 Energy Standard for Buildings except Low-Rise Residential Buildings. Factory Mutual (FM): 1. E. TIR-A8-[04]: Structural Performance of Composite Thermal Barrier Framing Systems – Section 7.2 723: Surface Burning Characteristics of Building Materials. National Fire Protection Association (NFPA): CONTINUOUSLY INSULATED EXTERIOR WALL ASSEMBLY 07 48 00 - 3 Edit Date: 2/8/2016 ThermaStop, PanelRail, PanelTek, SidingRail, CI-Girt, CI-System & CI are Trademarks of Knight Wall Systems, Inc. THERMAX, Styrofoam & WEATHERMATE are Trademarks of The Dow Chemical Company (“Dow”) or an affiliated company of Dow [Project Name] [Project Location] G. [Project No.] [Date] 1. 285-[06]: Standard Method of Test for the Evaluation of Flammability Characteristics of Exterior Non-Load-Bearing Wall Assemblies Containing Combustible Components Using the Intermediate-Scale, Multistory Test Apparatus. 2. 259-[08]: Standard Test Method for Potential Heat of Buring Materials. American Iron and Steel Institute (AISI) 1. Code of Standard Practice. 2. TS-4-02 Standard Test Method for Determining the Tensile and shear Strength of Screws. 3. TS-5-02 Test Methods for mechanically Fastened Cold-Formed Steel Connections. 4. TS-6-02 Standard Procedures for Panel and Anchor Structural Tests. 1.3 SYSTEM DESCRIPTION A. B. Furnish and install exterior continuous insulated wall assembly WITH NO THERMAL BRIDGES other than fastener to effectively control thermal, air and water performance. System shall include the following: 1. Aluminum-faced, fiberglass-reinforced rigid insulation secured to exterior of cold formed metal wall framing assembly [OR] concrete masonry unit wall [OR] concrete wall. 2. Butyl-based flashing tape to seal insulation board joints, damaged areas, and appropriate penetrations. 3. Cold-formed steel support and attachment framing system installed to exterior of rigid insulation, consisting of horizontal girts, thermal isolators and associated fasteners. 4. Closed-cell, medium-density spray polyurethane foam applied to interior wall cavity [for steel studs]. 5. Panel/siding manufactured for installation over cold-formed steel support and attachment framing. Design Requirements: 1. Constructed exterior wall system and component materials shall be acceptable for use under the building code in force in the jurisdiction of the project. 2. Products may be dimensioned in either English or Metric units. Design calculations, details and shop drawings shall take this into account. 3. Structural Design: Exterior-insulated rain screen wall assemblies capable of withstanding effects of load and stresses from dead loads, wind loads, snow loads and normal thermal movement without evidence of permanent defects of assemblies or components. a. Dead Load: As required by (applicable building code) ________________. b. Live Load: As required by (applicable building code) ________________. c. Wind Load: Uniform pressure (velocity pressure) of (Insert Design Criteria) lb/sq ft. (Insert Design Criteria), acting inward or outward. 4. Thermal Movements: Provide assemblies that allow for thermal movements resulting from the following maximum changes (range) in ambient and surface temperatures by preventing buckling, opening of joints, overstressing of components and other detrimental effects: 5. Temperature Change (range): 120 degrees Fahrenheit (67 degrees C), ambient: 180 degrees Fahrenheit (100 degrees C), material surfaces. 6. Panel/siding joints shall allow movement of panels during expansion and contraction while preventing uncontrolled penetration of moisture 7. Manufacturing, installation, and sealing shall prevent deformation of exposed surfaces. CONTINUOUSLY INSULATED EXTERIOR WALL ASSEMBLY [Design Firm] SECTION 07 48 00 - 4 Edit Date: 2/8/2016 ThermaStop, PanelRail, PanelTek, SidingRail, CI-Girt, CI-System & CI are Trademarks of Knight Wall Systems, Inc. THERMAX, Styrofoam & WEATHERMATE are Trademarks of The Dow Chemical Company (“Dow”) or an affiliated company of Dow [Project No.] [Date] [Project Name] [Project Location] 8. Maximum allowable deflection of span: L/175 9. Accommodate substructure tolerance of +/- 0.375 inch. 10. Support Framing/Attachment System: 11. C. a. No framing component may penetrate the layer of continuous exterior insulation other than thermally isolated fasteners. b. Frequency and spacing of stiffened horizontal girts as indicated by manufacture in project specific engineering package. [INSERT GENERAL PANEL/SIDING DESIGN REQUIREMENTS HERE] Performance Requirements: SPEC NOTE: Insert applicable performance criteria to suit Project requirements, including total wall R-value (U-Factor) required and air barrier and water penetration test PERFORMANCE REQUIREMENTS. 1. Attachment System Performance: Constructed system shall comply with ANSI/ASHRAE 90.1-2010 definition of continuous insulation (c.i.). 2. No thermal bridges other than fasteners and service openings. 3. Thermal Performance: a. Full constructed assembly must have a minimum 95% EFFECTIVE R-value when compared to the exterior insulations rated R-Value. b. Continuous framing profiles penetrating insulation not allowed. c. Effective R-Value calculation or modeling must be done in accordance with ASHRAE guidelines. d. Wall Assembly effective R-Value (U-Factor): [INSERT R-VALUE (U-0.XXX)] 4. Exterior Insulation: ASTM C518, Stabilized R-value of 6.5 at 1 inch of thickness with a maximum 6-month exposure capability to outdoor elements [and 15-year thermal warranty]. 5. Interior Closed-Cell Spray Polyurethane Foam: ASTM C518, 140 degrees F / 90-day Aged R-Value (measured at 75 degrees F mean temperature), for product with a minimum 30 degrees F ambient and substrate application temperature is R6.1/inch, and 140 degrees F / 90-day Aged R-Value (measured at 75 degrees F mean temperature), for product with a minimum 45 degrees F ambient and substrate application temperature is R6.4/inch, and140 degrees F / 90-day Aged R-Value (measured at 75 degrees F mean temperature), for product with a minimum 60 degrees F ambient and substrate application temperature is R6.1/inch. 6. Core density: ASTM D1622, Minimum 2.0 pcf. 7. Acceptable adhesion to substrate based on specific minimum application temperature. 8. Air Barrier Performance: In accordance with ASTM E2357-[05]: 9. a. Air infiltration not to exceed 0.04 cfm per square foot (0.2 L/s*m2) of fixed wall area at a test pressure of not less than 6.24 psf. b. Testing should be conducted at positive and negative sustained wind loading of 12.5 psf (600 Pa) for 1-hour duration in each direction, pressure cycling of the wall at 2000 cycles in both the positive and negative direction, ending with wind gust loading at 25 psf. Water Penetration: In accordance with ASTM E331: a. [Design Firm] No uncontrolled water penetration at a minimum differential pressure of not less than 6.24 psf and not more than 12.0 psf at minimum test duration of 2 hours. CONTINUOUSLY INSULATED EXTERIOR WALL ASSEMBLY 07 48 00 - 5 Edit Date: 2/8/2016 ThermaStop, PanelRail, PanelTek, SidingRail, CI-Girt, CI-System & CI are Trademarks of Knight Wall Systems, Inc. THERMAX, Styrofoam & WEATHERMATE are Trademarks of The Dow Chemical Company (“Dow”) or an affiliated company of Dow [Project Name] [Project Location] [Project No.] [Date] b. D. Mold Resistance: Thermal wall and air barrier system components shall not provide food source for fungal growth. 10. All joints, penetrations and gaps of the thermal and air barrier wall system watertight and air tight. 11. INSERT PANEL PERFORMANCE REQUIREMENTS HERE (i.e. UV EXPOSURE, WATER ABSORPTION, ETC.) Fire Resistance: 1. System complies with NFPA 285 [06]: Standard Fire Test Method for Evaluation of Fire Propagation Characteristics of Exterior Non-Load-Bearing Wall Assemblies Containing Combustible Components Using the Intermediate Scale, Multistory Test Apparatus. 2. Include fire-stopping measures at floor line in stud cavity, per code, when wall assembly extends beyond edge of floor line. 3. Exterior Insulation: 4. a. Class 1 (<and/or= 25 Flame Spread Index and < 450 Smoke Developed Index) classified at maximum thickness per UL 723 criteria or ASTM E84 criteria. b. Fire Performance Evaluation as a component of an NFPA 285 approved wall assembly per the requirements of the International Building Code. Spray Polyurethane Foam: a. Minimum density 2.0 pcf and closed-cell polyurethane foam. b. Class 1 (<and/or= 25 Flame Spread Index and < 450 Smoke Developed Index) classified at maximum thickness per UL 723 criteria or ASTM E84 criteria. 5. Fire Performance Evaluation as a component of an NFPA 285 approved wall assembly per the requirements of the International Building Code. 6. Must be separated from the interior of the building by an approved thermal barrier complying with IBC section 2603.4 as applicable. 1.4 SUBMITTALS A. Product Data: Submit manufacturer's product data, installation instructions and Material Safety Data Sheets (MSDS) for each component product required for complete wall system. Submit manufacturer’s product literature and descriptions of testing performed on system components to indicate that they will meet or exceed performance specified herein. B. With submission of bid, provide the following: 1. Thermal and Air Barrier Wall System Manufacturer Contractor Accreditation: 2. Acceptable Accreditation Methods: a. DOW THERMAX™ Wall System-CM Accreditation Program b. Or approved equal. C. Shop Drawings: Submit shop drawings from Panel manufacturer, showing interface of coldformed assembly and panels with adjacent construction, signed and sealed by engineer licensed to practice in authority having jurisdiction, detailing system installation and attachment. D. Structural Calculations: 1. Submit Panel manufacturer’s comprehensive analysis of design loads, including dead loads, live loads, wind loads and thermal movement. Submit façade attachment/support framing system manufacturer’s comprehensive analysis of design loads, including dead loads, live loads, wind loads and thermal movement, signed and sealed by a licensed engineer in the applicable State. CONTINUOUSLY INSULATED EXTERIOR WALL ASSEMBLY [Design Firm] SECTION 07 48 00 - 6 2. Edit Date: 2/8/2016 ThermaStop, PanelRail, PanelTek, SidingRail, CI-Girt, CI-System & CI are Trademarks of Knight Wall Systems, Inc. THERMAX, Styrofoam & WEATHERMATE are Trademarks of The Dow Chemical Company (“Dow”) or an affiliated company of Dow [Project No.] [Date] E. F. [Project Name] [Project Location] Samples: Submit following materials samples for verification: 1. Insulation panel: 8-inch square 2. Insulation fasteners/washers, thermal isolating washers and 8-inch sample of joint flashing tape: one each 3. Horizontal Stiffened Girts: Two 12-inch long samples of each 4. INSERT SIDING/PANEL SAMPLES Test Reports: 1. Façade attachment/support framing system must have been tested to the following standards and provide written test reports by a third party: a. 2. AAMA TIR-A8-[04]: Structural Performance of Composite Thermal Barrier Framing Systems – Section 7.2 Comprehensive three-dimensional thermal modeling report indicating framing systems impact on exterior insulation rated R-value. 1.5 QUALITY ASSURANCE A. B. Spray Polyurethane Foam (SPF) 1. Contractor Qualifications: SPF installation contractor shall be accredited by the Thermal and Air Barrier Wall System manufacturer (Accredited Contractor) and submitted certification at time of bid. 2. Installer Qualifications: During award period and for duration of installation, SPF installer shall be an officially recognized Certified Installer certified by Thermal and Air Barrier Wall System Manufacturer (Certified Installer). Certified Installer shall carry liability insurance and bonding. b. Each worker installing SPF must be, or be accompanied by, a Certified Installer. c. Each Certified Installer can supervise a maximum of 5 workers. The Certified Installer shall be thoroughly trained and experienced in the installation of SPF thermal and air barriers of the types being applied. Certified Installers shall perform or directly supervise all SPF installation work on the project. d. Certified Installers shall have their Thermal and Air Barrier Wall System Manufacturer Certificate in their possession on project site, available for inspection upon request. e. Certified Installer shall ensure that all workers have been trained on and are practicing the proper health and safety precautions required when applying SPF. 3. Follow manufacturer’s guidelines for proper temperature settings regarding spray equipment as stated on manufacturer’s product information sheets. 4. Follow manufacturer’s guidelines for proper spray polyurethane foam formulation based on substrate and ambient temperatures to which product will be applied Support Framing / Attachment System: 1. [Design Firm] a. Installer Qualifications: a. In good standing with manufacturer as qualified installer for work of this Section. b. Onsite superintendent or foreman overseeing installation on site during work of this Section. c. Able to document a minimum 5 completed projects of equivalent scope and quality upon request by Architect or General Contractor. CONTINUOUSLY INSULATED EXTERIOR WALL ASSEMBLY 07 48 00 - 7 Edit Date: 2/8/2016 ThermaStop, PanelRail, PanelTek, SidingRail, CI-Girt, CI-System & CI are Trademarks of Knight Wall Systems, Inc. THERMAX, Styrofoam & WEATHERMATE are Trademarks of The Dow Chemical Company (“Dow”) or an affiliated company of Dow [Project Name] [Project Location] 2. C. D. [Project No.] [Date] Manufacturer Qualifications: a. Minimum 5 years’ experience specializing in the manufacturing of façade attachment/support framing similar to those specified. b. Must demonstrate conformance to testing requirements. c. Design provided by a professional engineer experienced in the design of curtain wall systems, anchors, fasteners and licensed in the applicable State. Pre-Installation Meeting: 1. Participants: Authorized representatives of the General Contractor, installation subcontractor, [Construction Manager,] [Owner,] Architect, [Engineer,] SPF applicator, independent inspector, and [Manufacturer’s technical representative]. 2. Meeting Timing: Minimum [3] [4] weeks prior to beginning work of this Section and related work that may affect work of this Section. 3. Review metal wall framing assemblies for potential interference and conflicts and coordinate layout and support provisions for interfacing work. 4. Review and document methods, procedures and manufacturer’s installation guidelines and safety procedures for insulated sheathing, flashings, spray polyurethane foam, support framing / attachment system, finish panels, and penetration and gap sealant. 5. Review construction schedule and confirm availability of products, applicator/installer personnel, equipment and facilities. 6. Review governing regulatory requirements and requirements for insurance and certificates. 7. Review field quality control procedures. Mock-Ups: 1. Mock-up complete system at location as directed by Architect. 2. Mock-up shall demonstrate prepared substrate, support/attachment framing, insulation, façade finish, outside corner, inside corner, penetrations, exterior finishes and aesthetic appearance. 3. Verify mock-up as conforming to manufacturer’s instructions and provisions of Contract Documents. 4. Do not begin work of this Section until façade mock-up has been inspected and approved by manufacturer’s representative on site and Architect’s acceptance of mock-up is given in writing. 5. Protect and maintain accepted mock-up as standard of quality for work of this Section. 6. Accepted mock-ups may be incorporated into the work of this Section as direct by Architect. 1.6 QUALITY CONTROL A. Single source responsibility: 1. Furnish all thermal and air barrier system components from a single manufacturer to avoid compatibility and performance issues. 2. Furnish all engineered façade attachment/support framing system components under direct responsibility of single manufacturer to avoid performance issues. 3. Manufacturer of thermal and air barrier system may differ from façade attachment/support framing system manufacturer. CONTINUOUSLY INSULATED EXTERIOR WALL ASSEMBLY SECTION 07 48 00 - 8 [Design Firm] Edit Date: 2/8/2016 ThermaStop, PanelRail, PanelTek, SidingRail, CI-Girt, CI-System & CI are Trademarks of Knight Wall Systems, Inc. THERMAX, Styrofoam & WEATHERMATE are Trademarks of The Dow Chemical Company (“Dow”) or an affiliated company of Dow [Project No.] [Date] [Project Name] [Project Location] B. Field Measurements: Contractor is responsible for all field measurements, verifying actual supporting and adjoining construction before fabrication; record field measurements on project record shop drawings. C. Established Dimensions: Where field measurements cannot be made without delaying work, guarantee dimensions and proceed with fabrication of wall assemblies, including finishes, corresponding to established dimensions. 1.7 DELIVERY, STORAGE AND HANDLING A. Ordering: Comply with manufacturers’ ordering instructions and lead time requirements to avoid construction delays. B. Delivery: Deliver materials and components in manufacturers’ original, unopened and undamaged containers or bundles, fully identified. Exercise care to avoid damage during unloading, storing and installation. C. Store, protect and handle materials and components in accordance with manufacturer recommendations to prevent damage, contamination and deterioration. Keep materials clean, dry, and free of dirt and other foreign matter, and protect from damage due to weather or construction activities. 1.8 PROJECT CONDITIONS A. Environmental Requirements: Undertake installation work only when weather conditions are in compliance with manufacturers’ specific environmental requirements and when conditions will permit work to be performed in accordance with manufacturer recommendations and warranty requirements. 1. [Design Firm] Spray Polyurethane Foam (SPF): a. Do not proceed with installation of SPF until sheathing substrate construction is complete and openings and penetrating items have been installed and sealed. b. Do not proceed with installation of SPF until substrate surface temperatures are above the manufacturer’s recommended minimum surface temperatures for application. c. Verify that substrate surfaces to receive SPF are free of frost, oil, grease, oxidation, dirt, loose paint, loose scale, or other deleterious material that would impair bond. d. Do not apply SPF past 6-month expiry date printed on label of each container. e. Ventilate area to receive SPF by introducing fresh air and exhausting air continuously during and for 24 hours after application to maintain non-toxic, unpolluted, safe working conditions. f. Provide temporary enclosures and ensure all air ducts and openings to other areas of the building are covered to prevent spray and noxious vapors from contaminating air beyond application area. g. Protect workers as recommended by SPF manufacturer. Restrict access to spray area, to spray applicator(s) and their helper(s) while spraying. Anyone in spray area must be wearing full and proper personal protection equipment (PPE). Follow SPF manufacturer’s re-entry guidelines. h. Protect adjacent surfaces and equipment from damage by overspray, fall-out, and dusting of insulation materials. i. Dispose of waste foam daily in location designated by [Architect] [Engineer] and empty drums in accordance with SPF manufacturer's instructions. CONTINUOUSLY INSULATED EXTERIOR WALL ASSEMBLY 07 48 00 - 9 Edit Date: 2/8/2016 ThermaStop, PanelRail, PanelTek, SidingRail, CI-Girt, CI-System & CI are Trademarks of Knight Wall Systems, Inc. THERMAX, Styrofoam & WEATHERMATE are Trademarks of The Dow Chemical Company (“Dow”) or an affiliated company of Dow [Project Name] [Project Location] [Project No.] [Date] 1.9 SEQUENCING A. Coordinate construction to ensure that assemblies fit properly to supporting and adjoining construction; coordinate schedule with construction in progress to avoid delaying work. 1.10 WARRANTY A. Manufacturer Warranties: 1. Exterior Insulation: 6-month exposure [and 15-year thermal warranty] 2. Flashing Tape: Limited warranty 3. Spray Polyurethane Foam: Limited warranty 4. Attachment/Support Framing System: Limited warranty 5. a. Length: Written ten (10) years. b. Covers components of the attachment system, including structural failure of components when all the materials and component are supplied and installed per manufactures requirements. c. Includes labor and material for removal and replacement of defective material. d. Includes labor to remove and reinstall façade finish panels, finish closures and façade finish accessories necessary to access defective material. INSERT ALL SIDING/CLADDING PANEL WARRANTY REQUIREMENTS HERE B. Contractor’s Warranties: 2-year labor warranty, starting from [date of Owner acceptance of completed work][Substantial Completion], to cover repair of materials found to be defective as a result of installation errors. C. Limitation of Warranties: Exclude repairs, replacement, and corrective work to the substrate, primary structure, finish panels, and/or property – unless otherwise noted above. Warranties exclude mechanical damage due to abuse, neglect, primary structure failure, or forces of nature greater than normal weather conditions. 1.11 MAINTENANCE A. Extra Materials: For use by Owner in building maintenance and repair, provide [a recommended percentage of] [3 percent] additional material in new, unopened cartons, packaged with protective covering for storage and identified with appropriate labels. 1. Façade panels 2. Custom attachment system components PART 2 - PRODUCTS 2.1 PERFORMANCE SPECIFICATION - RIGID INSULATION BOARD A. Glass-fiber-reinforced enhanced polyisocyanurate foam core sheathing faced with nominal 4-mil embossed acrylic-coated aluminum on one side and 1.25-mil embossed aluminum on the other side, complying with ASTM C1289 and meeting the following physical properties: 1. ASTM C1289 Type 1, Class 2 2. Compressive Strength (ASTM D1621): 25 psi, minimum 3. Aged Thermal Resistance (ASTM C518, measured at mean temperature of 75 degrees F): [R-6.5 up to 2 inches], R-6.0 above 2 inches] [RSI 1.14 up to 50 mm, RSI 1.07 above 50 mm] of thickness. CONTINUOUSLY INSULATED EXTERIOR WALL ASSEMBLY SECTION 07 48 00 - 10 [Design Firm] Edit Date: 2/8/2016 ThermaStop, PanelRail, PanelTek, SidingRail, CI-Girt, CI-System & CI are Trademarks of Knight Wall Systems, Inc. THERMAX, Styrofoam & WEATHERMATE are Trademarks of The Dow Chemical Company (“Dow”) or an affiliated company of Dow [Project No.] [Date] [Project Name] [Project Location] 4. Flexural Strength (ASTM C203): Minimum 55 psi 5. Water Absorption (ASTM C209): Maximum 0.1 percent by volume 6. Water Vapor Permeance (ASTM E96): <0.03 perms 7. Maximum Use Temperature: 250 degrees F 8. Board size and configuration: SPEC NOTE: Select applicable panel size, thickness and R-value(s) to suit Project requirements a. Panel Size: 4 feet by 8 feet [12 feet] long b. Shiplap profile on two edges on thicknesses of 1.55 inches and greater. c. Thickness and Stabilized R-Value: [Nominal 0.625-inch thickness, R-4.1] [1-inch thickness, R-6.5] [1.55-inch thickness, R-10.1] [2-inch thickness, R-13] For thicknesses greater than 2” call 1.866.583.BLUE (2583). B. Basis of Design: The Dow Chemical Company “THERMAX™ ci” Exterior Insulation. C. Or approved equal. 2.2 ACCESSORIES: A. Temporary Fasteners: Provide insulated sheathing manufacturer’s recommended fasteners for temporary anchoring of sheathing to metal wall framing. Fastener size and length based on wall sheathing thickness and sufficient to provide solid attachment through rigid insulation to substructure. B. Acceptable Products: Rodenhouse, Inc. 1 3/4 inch diameter “Plasti-Grip CBW” plastic washers which can be installed using either bulk Grip-Deck self-drilling screws or collated Grip-Deck screws. Use the Grip-Lok auto-feed fastening system for high speed application (recommended for wall assemblies up to 2 inches in thickness. Contact Rodenhouse Inc. for more information at 616-454-3100. C. Acceptable Products: Rodenhouse, Inc. 1 3/4 inch diameter “Plasti-Grip III” with pre-spotting stem plastic washers. Recommended for wall assemblies greater than 2 inches in thickness as prespotting stem aids in guiding longer length screws (Use Grip-Deck screws. See below). Contact Rodenhouse Inc. for more information at 616-454-3100. D. Acceptable Products: Rodenhouse, Inc. “Plasti-Grip PMF” fasteners. Recommended for block, concrete, or masonry substrates. Contact Rodenhouse, Inc. for more information at 616-454-3100. E. Acceptable Products: Rodenhouse, Inc. “Grip-Deck” screws available either in bulk or collated and manufactured to high standards. Available in either zinc or ceramic coated (ceramic coated recommended for ACQ/fire treated wood). Contact Rodenhouse Inc. for information at 616-4543100. F. Insulation Flashing Tape: Provide board insulation manufacturer’s compatible joint tape for sealing joints, seams and façade tie penetrations through the insulation layer and sealing window and door wall openings at head, sill and jambs. [Design Firm] 1. Adhesive: Butyl rubber (non-asphalt) 2. Facer: High density polyethylene 3. Self-sealing 4. Thickness (ASTM D3767, method A): 20 mils 5. Water Vapor Transmission (ASTM E96): <1 perm 6. Sizes: 4 inch, 6 inch or 9 inch as required. CONTINUOUSLY INSULATED EXTERIOR WALL ASSEMBLY 07 48 00 - 11 Edit Date: 2/8/2016 ThermaStop, PanelRail, PanelTek, SidingRail, CI-Girt, CI-System & CI are Trademarks of Knight Wall Systems, Inc. THERMAX, Styrofoam & WEATHERMATE are Trademarks of The Dow Chemical Company (“Dow”) or an affiliated company of Dow [Project Name] [Project Location] [Project No.] [Date] a. 7. When greater widths are required for through-wall flashings, butyl rubber adhesive is recommended. Basis of Design: The Dow Chemical Company “WEATHERMATE™” Straight Flashing” a. Or approved equal. 2.3 PERFORMANCE SPECIFICATION - ATTACHMENT/SUPPORT FRAMING SYSTEM: SPEC NOTE: This attachment/support framing system is versatile and suitable for claddings such as (but not limited to) vertically oriented siding/cladding (i.e. corrugated metal, etc.) and Metal Composite Panel systems. Cladding type must meet IBC requirements. 0.75 inch total framing depth from back of cladding to face of insulation (plus the depth of clips, if applicable). Please contact manufacture for further information or questions. A. Constructed system complies with ANSI/ASHRAE 90.1-2007 definition of continuous insulation (c.i.). B. Coating Material: ASTM A792, Al-Zn 55, minimum AZ55 or ASTM A1046, Zinc-AluminumMagnesium, minimum thickness ZM40 C. Steel Classification: Structural Steel (SS), Grade 50, 50 ksi Yield. D. Spacing to comply with applicable live and dead loads and any other requirements of the façade/panel and in accordance with approved engineering calculations E. All framing components must be tested to AAMA TIR- A8-[04] – section 7.2 to determine structural performance and effective moment of inertia for each perforated component. F. Framing system to be comprised of the following: 1. G. Stiffened Horizontal Girt: Minimum 0.0475-inch thick (18 gauge) cold-formed steel. a. Depth: 0.75 inches b. Attachment: Regularly spaced, pre-punched holes to receive centering wall fasteners with thermally isolated washer assembly for attachment to substructure. c. Drainage: Regularly spaced, pre-punched holes integral through the bend of the girt to allow water to easily weep. d. Basis of Design: HCI-Girt™ by Knight Wall Systems e. Or approved equal. Accessories: 1. Fasteners: Stainless steel as instructed by manufacturer. a. Thermoset Polyester coating that exhibits 1,000 hours of salt spray resistance. b. Steel Studs: Self-drill hex-head screw fasteners of sufficient length to provide solid attachment through rigid insulation to substructure as indicated in engineering calculations. c. Concrete and Masonry Wall Anchors: Mechanical and adhesive anchors, bolts, nuts and washers suited to use. 1) 1/4 inch Tapcon by Buildex 2) 1/4 inch UltraCon by Elco Industries 3) Or approved equal. CONTINUOUSLY INSULATED EXTERIOR WALL ASSEMBLY SECTION 07 48 00 - 12 [Design Firm] Edit Date: 2/8/2016 ThermaStop, PanelRail, PanelTek, SidingRail, CI-Girt, CI-System & CI are Trademarks of Knight Wall Systems, Inc. THERMAX, Styrofoam & WEATHERMATE are Trademarks of The Dow Chemical Company (“Dow”) or an affiliated company of Dow [Project No.] [Date] [Project Name] [Project Location] 2. H. Thermal Isolating Washers: Minimum 0.125 inch thick Polyoxymethylene copolymer (POM) washers with integral centering lip to act as a thermal break between wall anchor fastener and box girt. a. Basis of Design: ThermaStop™ Isolator by Knight Wall Systems b. Or approved equal. Galvanic Protection: Utilize tapes and other methods as necessary to separate and prevent contact between dissimilar metals 2.4 PERFORMANCE SPECIFICATION - SPRAY POLYURETHANE FOAM AIR BARRIER A. Spray Polyurethane Foam: Two-component spray polyurethane cellular plastic foam, complying with the following methods and meeting the following physical properties: 1. Core Density (ASTM D1622): [Minimum 2 pcf] 2. Thermal Resistance (ASTM C518): 140 degrees F / 90-day Aged R-Value, measured at 75 degrees F mean temperature: Minimum R-6.1 per inch 3. Flame Spread (ASTM E84, Class A): 25 or less 4. Smoke Developed (ASTM E84, Class A): 450 or less 5. Compressive Strength Minimum (ASTM D1621, 10 percent parallel to rise): [20 psi] [182 kPa] 6. Closed Cell Content (ASTM D2856): minimum 90 percent 7. Water Absorption by Volume Maximum (ASTM D2842): 5 percent 8. Water Vapor Permeability Maximum (ASTM E96): [3.0 perm-inches] [4.4 ng/(Pa.s.m)] B. Basis of Design: The Dow Chemical company “STYROFOAM™ Spray Polyurethane Foam Insulation [CM2030] [CM 2045] [CM2060]” Formulation required will depend upon surface temperature of substrate. Refer to manufacturers recommendations. C. Or approved equal. 1. 2. 3. STYROFOAM™ Spray Polyurethane Foam Insulation CM2030: a. Thermal Resistance (ASTM C518): 140 degrees F / 90-day Aged R-Value, measured at 75 degrees F mean temperature: Minimum R-6.1 per inch. b. Maximum/Nominal 1.5-inch Thickness: Thermal Resistance (ASTM C518): 140 degrees F / 90 day Aged R-Value, measured at 75 degrees F mean temperature: R-9.2. STYROFOAM™ Spray Polyurethane Foam Insulation CM2045: a. Thermal Resistance (ASTM C518): 140 degrees F / 90-day Aged R-Value, measured at 75 degrees F mean temperature: Minimum R-6.4 per inch. b. Maximum/Nominal 1.5 inch Thickness: Thermal Resistance (ASTM C518): 140 degrees F / 90 day Aged R-Value, measured at 75 degrees F mean temperature: R-9.6. STYROFOAM™ Spray Polyurethane Foam Insulation CM2060: a. Thermal Resistance (ASTM C518): 140 degrees F / 90-day Aged R-Value, measured at 75 degrees F mean temperature: Minimum R-6.1 per inch. b. Maximum/Nominal 1.5 inch thickness: Thermal Resistance (ASTM C518): 140 degree F / 90 day Aged R-Value, measured at 75 degrees F mean temperature: R-9.2. 2.5 PERFORMANCE SPECIFICATION – SIDING/CLADDING PANEL: [Design Firm] CONTINUOUSLY INSULATED EXTERIOR WALL ASSEMBLY 07 48 00 - 13 Edit Date: 2/8/2016 ThermaStop, PanelRail, PanelTek, SidingRail, CI-Girt, CI-System & CI are Trademarks of Knight Wall Systems, Inc. THERMAX, Styrofoam & WEATHERMATE are Trademarks of The Dow Chemical Company (“Dow”) or an affiliated company of Dow [Project Name] [Project Location] A. [Project No.] [Date] INSERT SIDING/CLADDING PANEL SPECIFIC PERFORMANCE REQUIREMENTS HERE SPEC NOTE: This section is reserved for all specifications related specifically to the siding/cladding panel(s) including performance requirements (i.e. wind pressure testing, water penetration testing, coating performance, etc.), sizes/modules/thickness, colors and fabrication requirements if applicable. PART 3 - EXECUTION 3.1 EXAMINATION A. Examine substrates and conditions for compliance with requirements for installation conditions affecting performance of the work. 1. Verify that metal wall studs, opening framing, bridging, bracing and other framing support members and anchorage have been installed within thermal wall system alignment tolerances and requirements. 2. Verify that substrate surfaces to receive spray polyurethane foam are free of frost, oil, grease, oxidation, dirt, loose paint, loose scale, or other deleterious material that would impair bond 3. Verify that items required to penetrate thermal wall system are placed and penetration gaps and cracks are properly sealed before installing spray polyurethane foam. 4. Do not proceed with installation until unsatisfactory conditions have been corrected. 5. Ensure weather-resistant barrier (WRB) is installed in conformance with WRB manufacturer’s instructions and discontinuities in WRB are properly flashed and sealed prior to installing support framing and attachment system. B. Field verify architectural details and mechanical and electrical requirements prior to commencing installation. C. Commencement of installation constitutes acceptance of existing conditions and acceptance of responsibility for satisfactory performance. 3.2 INSULATION BOARD INSTALLATION A. Do not install more insulation than can be permanently fastened with vertical cold-formed steel box girts in the same day. Do not leave insulation overnight or for extended periods that is not permanently fastened to building substructure with vertical girts. B. Install insulation in accordance with manufacturer's recommendations. C. Temporary Fastening: Temporarily fasten rigid insulation panels to exterior face of exterior metal stud wall framing. Abut panels tightly together and around openings and penetrations. 1. Install panels horizontally with blue aluminum facing to exterior. Use maximum panel lengths to minimize number of joints. Locate edge joints parallel to and on framing. Center end joints over supports and stagger in each course. Provide additional framing wherever panel joints do not bear against framing, plates or sill members. 2. Fasten rigid insulation panels to each support with temporary fasteners, a single row of one fastener at each stud framing member. Set back corner fasteners by 3/8 inch from edges and ends of panel units. Drive fasteners to bear tight and flush with surface of insulation. Do not overdrive or tear aluminum skin of insulation. [Perimeter fasteners can be detailed to bridge gap of abutting board joints due to 1.75 inch diameter washer used to fasten board to studs. Maximum of 2 board joints may be bridged per fastener.] 3. Install flashing joint tape at end and edge joints using sufficient hand pressure to ensure seal and in accordance with rigid insulation manufacturer's joint sealing recommendations. CONTINUOUSLY INSULATED EXTERIOR WALL ASSEMBLY SECTION 07 48 00 - 14 [Design Firm] Edit Date: 2/8/2016 ThermaStop, PanelRail, PanelTek, SidingRail, CI-Girt, CI-System & CI are Trademarks of Knight Wall Systems, Inc. THERMAX, Styrofoam & WEATHERMATE are Trademarks of The Dow Chemical Company (“Dow”) or an affiliated company of Dow [Project No.] [Date] [Project Name] [Project Location] 4. Install flashing tape on insulation behind wall tie and mechanical fastening assemblies for rain screen claddings. 5. Seal joints and penetrations in accordance with rigid insulation panel manufacturer's joint and penetration sealing recommendations. 6. After base flashing is installed on exterior insulation, which may include a termination bar running horizontally along the top edge of the flashing, install 6-inch or 9-inch flashing with butyl rubber adhesive to the exterior sheathing, lapped over top edge of base flashing. 3.3 COLD-FORMED METAL FRAMING INSTALLATION A. Preparation: 1. B. Verify horizontal girt spacing and framing clearances relative to studs or other points of attachment. Installation 1. Use laser or chalk line to mark starting height of horizontal girt. 2. Mount stiffened horizontal girts, fastened up to 36 inches on center (as determined by the manufactures engineering calculations) overtop of installed rigid insulation, using one selftapping screw for each attachment hole at spacing indicated on engineering calculations. a. Check plumb of horizontal girts both parallel and perpendicular to the structure. b. Tighten screws that attach horizontal girt through insulation to substructure to a snug tight condition and not stripped. If installed using hand tools, verify for each installer at beginning of project using snug-tight criteria. Do not use stripped holes. c. Where obstructions are present and unavoidable (i.e. window openings), use laser or chalk line to restart girt. d. The cavity must be clear and free from air flow and drainage obstructions. e. Use shearing instruments (i.e. snips, nibbler, etc.) for cutting metal framing components. Saws are not recommended, as the sparks produced during cutting will damage the anti-corrosion coating. If sparks are generated during cutting, be sure the portion of the component to be installed on the building is protected from sparks and that any stockpile near the cutting station is also protected. f. The systems components should not be cut while installed on the building, unless using a shearing instrument. 3.4 SPRAY POLYURETHANE FOAM INSTALLATION A. B. [Design Firm] Preparation 1. Follow all safety precautions. 2. Mask and cover adjacent areas to protect from overspray. 3. Apply primers for special conditions as recommended by manufacturer. 4. Cover wide joints with transition sheet membrane as specified in Section 07 25 00. 5. Clean work area prior to applying spray insulation. 6. Verify substrate temperature meets manufacturer’s requirements for specific formulations used. 7. Ensure that all stud cavity fire-stopping is installed prior to applying spray foam. Application: Spray-apply polyurethane foam in accordance with ASTM C1029 and manufacturer’s installation guidelines; comply with preparation methods outlined in 3.3.A. CONTINUOUSLY INSULATED EXTERIOR WALL ASSEMBLY 07 48 00 - 15 Edit Date: 2/8/2016 ThermaStop, PanelRail, PanelTek, SidingRail, CI-Girt, CI-System & CI are Trademarks of Knight Wall Systems, Inc. THERMAX, Styrofoam & WEATHERMATE are Trademarks of The Dow Chemical Company (“Dow”) or an affiliated company of Dow [Project Name] [Project Location] [Project No.] [Date] 1. Apply spray polyurethane foam by picture-framing around interior studs at insulatedsheathing-to-steel-stud interface and spraying single pass across all board joints and penetrations. 2. Finish applying spray polyurethane foam with one pass not exceeding 1.5 inches in thickness. Two passes are acceptable to reach maximum thickness of 1.5 inches. 3. If more than one layer is being applied, allow layer applied first to cool to maximum substrate temperature or lower as recommended by spray polyurethane foam insulation manufacturer. 4. Avoid formation of sub-layer air pockets. 5. Apply spray polyurethane foam in overlapping layers to achieve a smooth, uniform surface, total thickness as indicated. 6. Maintain [3-inch] [75 mm] clearance around chimneys, heating vents, steam pipes, recessed lighting fixtures and other heat sources. 7. Do not apply spray polyurethane foam to inside of exit openings or electrical junction boxes. 8. Maintain a continuous layer of spray foam from floor to floor to roof to complete air barrier. 9. Maximum Variation in Applied Thickness: minus [1/4 inch] [6 mm], plus [5/8 inch] [10 mm]. 3.5 SIDING/CLADDING PANEL INSTALLATION A. Insert siding/cladding panel installation specifications here. 3.6 FIELD QUALITY CONTROL A. Spray Polyurethane Foam: 1. Certified Installer: Completion of a daily work record is recommended to record all information required, including results of testing. Keep daily work record on site and make available for routine inspection. Upon request, forward copies of daily work record to manufacturer, owner or owner’s representative. 2. Costs incurred for daily testing and inspection by Certified Installer and completion of daily work record shall be borne by manufacturer’s Accredited Contractor. 3. If required by Owner, arrange for site inspections by qualified third-party inspector. Frequency and cost of inspections shall be included in bid at Owner’s request. If site inspection reveals defects, manufacturer’s Accredited Contractor shall immediately rectify all such defects at own cost. a. Certified Installer’s daily work record shall verify conformance with thermal and air barrier wall system manufacturer’s instructions. b. Follow manufacturer’s guidelines for proper temperature settings regarding spray equipment as stated on manufacturer’s product information sheets. c. Follow manufacturer’s guidelines for proper spray polyurethane foam formulation based on substrate and ambient temperatures to which product will be applied. d. After product has properly cured, conduct tests to verify adhesion between spray polyurethane foam and substrate. 3.7 CLEANING Remove overspray from non-prescribed surfaces in accordance with manufacturer’s recommendations, without causing damage to surfaces. Remove protective covers from adjacent surfaces CONTINUOUSLY INSULATED EXTERIOR WALL ASSEMBLY [Design Firm] SECTION 07 48 00 - 16 A. Edit Date: 2/8/2016 ThermaStop, PanelRail, PanelTek, SidingRail, CI-Girt, CI-System & CI are Trademarks of Knight Wall Systems, Inc. THERMAX, Styrofoam & WEATHERMATE are Trademarks of The Dow Chemical Company (“Dow”) or an affiliated company of Dow [Project No.] [Date] B. [Project Name] [Project Location] Leave surfaces clean and free of debris and residue. Where required, clean exposed surfaces in accordance with manufacturer’s instructions. END OF SECTION 07 48 00 [Design Firm] CONTINUOUSLY INSULATED EXTERIOR WALL ASSEMBLY 07 48 00 - 17 Edit Date: 2/8/2016 ThermaStop, PanelRail, PanelTek, SidingRail, CI-Girt, CI-System & CI are Trademarks of Knight Wall Systems, Inc. THERMAX, Styrofoam & WEATHERMATE are Trademarks of The Dow Chemical Company (“Dow”) or an affiliated company of Dow [Project Name] [Project Location] [Project No.] [Date] NOTICE: No freedom from any patent owned by Dow or others is to be inferred. Because use conditions and applicable laws may differ from one location to another and may change with time, Customer is responsible for determining whether products and the information in this document are appropriate for Customer's use and for ensuring that Customer's workplace and disposal practices are in compliance with applicable laws and other government enactments. The product shown in this literature may not be available for sale and/or available in all geographies where Dow is represented. The claims made may not have been approved for use in all countries or regions. Dow assumes no obligation or liability for the information in this document. References to "Dow" or the "Company" mean the Dow legal entity selling the products to Customer unless otherwise expressly noted. NO EXPRESS WARRANTIES ARE GIVEN EXCEPT FOR ANY APPLICABLE WRITTEN WARRANTIES SPECIFICALLY PROVIDED BY DOW. ALL IMPLIED WARRANTIES INCLUDING THOSE OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE EXPRESSLY EXCLUDED. Dow Polyisocyanurate Insulation CAUTION: This product is combustible and shall only be used as specified by the local building code with respect to flame spread classification and to the use of a suitable thermal barrier. For more information, consult MSDS, call Dow at 1-866-583-BLUE (2583) or contact your local building inspector. In an emergency, call 1-989-636-4400. WARNING: Rigid foam insulation does not constitute a working walkable surface or qualify as a fall protection product Dow Polyurethane Foam Insulation and Sealants CAUTION: When cured, these products are combustible and will burn if exposed to open flame or sparks from high-energy sources. Do not expose to temperatures above 240ºF (116ºC). For more information, consult MSDS, call Dow at 1-866-583-BLUE (2583) or contact your local building inspector. In an emergency, call 1-989-636-4400 in the U.S. or 1-519-339-3711 in Canada. GREAT STUFF PRO™ sealant and adhesive products contain isocyanate and a flammable blowing agent. Read the label and Material Safety Data Sheet carefully before use. Eliminate all sources of ignition before use. Wear long sleeves, gloves, and safety glasses or goggles. Provide adequate ventilation or wear proper respiratory protection. Contents under pressure.. FROTH-PAK™ Spray Polyurethane Foam contains isocyanate, hydrofluorocarbon blowing agent and polyol. Read the instructions and Material Safety Data Sheets carefully before use. Wear protective clothing (including long sleeves), gloves, goggles or safety glasses, and proper respiratory protection. Do not breathe vapor or mist. Use only with adequate ventilation. It is recommended that applicators and those working in the spray area wear respiratory protection. Increased ventilation significantly reduces the potential for isocyanate exposure, however, supplied air or an approved air-purifying respirator equipped with an organic vapor sorbent and a particulate filter may still be required to maintain exposure levels below ACGIH, OSHA, WEEL or other applicable limits. For situations where the atmospheric levels may exceed the level for which an air-purifying respirator is effective, use a positive-pressure, air-supplying respirator (air line or self-contained breathing apparatus). Spraying large amounts of foam indoors may require the use of a positive pressure, air-supplying respirator. Contents under pressure. STYROFOAM™ Brand Spray Polyurethane Foam contains isocyanate, hydrofluorocarbon blowing agent and polyol. Read the instructions and Material Safety Data Sheets carefully before use. Wear protective clothing (including long sleeves), gloves, goggles and proper respiratory protection. Supplied air or an approved air-purifying respirator equipped with an organic vapor sorbent and a P100 particulate filter is required to maintain exposure levels below ACGIH, OSHA, WEEL or other applicable limits. Provide adequate ventilation. Contents under pressure. STYROFOAM™ Brand SPF should be installed by a trained SPF applicator. Building and/or construction practices unrelated to building materials could greatly affect moisture and the potential for mo ld formation. No material supplier including Dow can give assurance that mold will not develop in any specific system. CONTINUOUSLY INSULATED EXTERIOR WALL ASSEMBLY SECTION 07 48 00 - 18 [Design Firm] Edit Date: 2/8/2016 ThermaStop, PanelRail, PanelTek, SidingRail, CI-Girt, CI-System & CI are Trademarks of Knight Wall Systems, Inc. THERMAX, Styrofoam & WEATHERMATE are Trademarks of The Dow Chemical Company (“Dow”) or an affiliated company of Dow