University of Manitoba Req # FIRE PROTECTION Section 15500 Page 1 PART 1 - GENERAL 1.1 DESCRIPTION .1 All drawings and all sections of the specifications shall apply to and form an integral part of this section. .2 Refer to 15020 for Approved Manufacturers list. 1.2 WORK PERFORMED BY THIS SECTION .1 Only experienced Fire Protection Sub-contractors, as determined by Consultant, will be considered for this work. Sub-contractors must be able to show evidence of having performed work of similar type and size. .2 Supply all materials, labour, plant, tools, equipment, sealed working drawings, and services necessary and reasonably incidental to provide a complete fire protection system as described herein and shown on the drawings including, but not limited to the following: .1 All piping including external fire department pumper connections, [yard fire hydrants,] [post indicator valves] and equipment. .2 All fire hose and standpipe systems. .3 Wet Pipe Sprinkler System. .4 Dry Pipe Sprinkler System. .5 Pre-action Sprinkler System (required for all Libraries and Voice/Data rooms). .6 Fire Pumps .7 Anti-Freeze Sprinkler System. .8 Standpipe System. .9 Wet Window Sprinkler System. .10 Deluge Sprinkler System. .11 All fire extinguishers, cabinets and brackets. .12 Temporary standpipe during construction as required by Authorities. .13 Preparation of shop drawings, approval by authorities having jurisdiction, inspection, testing and approval as specified herein and as required by authorities having jurisdiction. 1.3 CERTIFICATES .1 Provide written certificate that components are compatible, and where applicable, certified for intended use by nationally recognized testing agency. 1.4 COMMISSIONING .1 Refer to Section 01810 Quality Commissioning for the details of the commissioning process. 1.5 CONTRACTOR QUALIFICATIONS .1 Qualifications: Execute work of this Section only by skilled tradesmen employed by a qualified Fire Protection Contractor licensed in the province of Manitoba regularly engaged in the installation of automatic sprinkler systems and other fire protection equipment and who is a member in good standing of the Canadian Automatic Sprinkler Association. .2 Arrange and pay for all inspections, examinations and tests required by all Authorities specified previously. Provide certificates, where given, to the Consultant. .3 The following Contractors are pre-approved for Section 15500 scope of work: .1 BDR Services .2 SimplexGrinnell .3 Vipond Fire Protection Any other Contractor wishing to bid must be pre-qualified at the time of tender being released. February 27, 2015 University of Manitoba Req # FIRE PROTECTION Section 15500 Page 2 1.6 DELINEATION OF WORK .1 Due to the sprinkler system Subtrade being a specialist installer, delineation of work for this Subtrade, as it interfaces with other Division 15 Subtrades, (in connection with water supplies, mains and valving), is described [on the drawings] [in Section 15400]. ] 1.7 MAINTENANCE DATA .1 Attach tag or label to extinguishers, indicating month and year of installation. Provide space for service dates. .2 Refer to Section 01810 for additional documentation details and requirements. 1.8 MAINTENANCE MATERIALS .1 Provide lockable metal cabinet containing spare sprinklers of each type and melting point temperature to NFPA 13 requirements. Install cabinet where indicated. Include sprinkler wrenches and 2 keys, for emergency repair work. .2 Refer to Section 01810 for additional documentation details and requirements. 1.9 QUALITY ASSURANCE .1 This installation shall conform to the latest edition at the time of bid of each of the following Codes and Standards: .1 Federal, provincial, municipal building and fire regulations as approved by: .1 Provincial Fire Marshal. .2 Factory Mutual System approval guide. .3 FCC 401 Fire Extinguishers, FCC 402 Standpipe and Hose Systems, .4 FCC 403 Sprinkler Systems, FCC 410 Fire Alarm Systems. .5 National NFPA 13, all appendices, Installation of Sprinkler Systems. .6 NFPA Automatic Sprinkler System Handbook. .7 NFPA 14, all appendices, Standpipe and Hose Systems. .8 Underwriters Laboratories Fire Protection Equipment Directory. .9 Factory Mutual Approval Guide. .10 NFPA 20 – Fire Pumps 1.10 SPRINKLER SYSTEM DESIGN CRITERIA .1 Fire Protection Contractor to review existing conditions and all Code requirements prior to submitting tender price. Upgrades to address deficiencies in existing systems and code required upgrades are to be included in tender price. .2 Fire Protection Contractor to review coverage and provide all piping, material, devices, and system as required by Code and Authorities having jurisdiction. .3 Design density to be based on area of sprinkler operation according to latest requirements of NFPA and to FCC requirements. .4 Modify and/or upgrade all existing system components as required to meet latest Code requirements. .5 No extra costs to tender price will be allowed to achieve NFPA requirements of this project. 1.11 SHOP DRAWINGS .1 Submit shop drawings in accordance with authorities having jurisdiction for approval before commencing work. .2 Shop drawings shall clearly indicate: .1 Name of Department of Agency. .2 Location, including street address. .3 Point of compass. .4 Ceiling construction. .5 Full height cross section. .6 Location of fire separations. .7 Occupancy of each area or room. .8 Location and size of blind spaces and closets. .9 Any questionable small enclosures in which no sprinklers are to be installed. February 27, 2015 University of Manitoba Req # FIRE PROTECTION Section 15500 Page 3 .10 .3 .4 .5 .6 Size of city main in street, pressure and whether dead-end or circulating and if dead end, direction and distance to nearest circulating main, with city main test results. .11 Other sources of water supply, with pressure or elevation. .12 Make, type and orifice size of sprinklers. .13 Temperature rating and location of high temperature sprinklers. .14 Number of sprinklers on each riser and on each zone by floors, and total area protected by each zone on each floor. .15 Number of sprinklers on each riser and total per floor. .16 Make, type, model and size of alarm. .17 Kind and location of alarm bells. .18 Cutting lengths of pipe or centre-to-centre dimensions. .19 Crosses, riser nipples and size. .20 Type of hangers, inserts and sleeves. .21 All control valves, checks, drain pipes and test pipes. .22 Small hand hose and hose equipment. .23 Provision for flushing. .24 Name and address of Contractor. Over and above that called for above, show the following for hydraulically designed systems: .1 Hydraulic reference points to be designated by letter or number and to correspond to the comparable reference points shown in the hydraulic calculation sheets. .2 Description of sprinklers used. .3 System design criteria: minimum rate of water application and water application for both inside and outside hose streams. .4 Actual calculated requirements: total quantity of water and pressure required at a common reference point for each system. .5 Elevation data including relative elevation of sprinkler junction points and supply of reference points. Submit calculations of hydraulically designed systems on form sheets, including summary sheet, detailed work sheets and graph sheet. On summary sheet, clearly indicate: .1 Date. .2 Location. .3 Name of Department or Agency. .4 Building number or other identification. .5 Description of hazard. .6 Name address of contractor or designer. .7 Name of approving agency. .8 System design requirements, including design area of water application, minimum rate of water application density and area per sprinkler. .9 Total water requirements as calculated including allowance for inside hose and outside hydrants. .10 Water supply information. On detailed work sheets or computer printout sheets, clearly indicate: .1 Sheet number. .2 Sprinkler description and discharge constant K. .3 Hydraulic reference points. .4 Flow in l/s. .5 Pipe size. .6 Pipe lengths, centre to centre of fittings. .7 Equivalent pipe lengths for fitting and devices. .8 Friction loss in kPa/m of pipe. .9 Total friction loss between reference points. .10 Elevation head in kPa between reference points. .11 Required pressure in kPa at each reference point. .12 Velocity pressure and normal pressure if included in calculations. .13 Notes to indicate starting points, reference to other sheets or to clarify data shown. February 27, 2015 University of Manitoba Req # Section 15500 Page 4 .7 .8 1.12 FIRE PROTECTION Graph paper of semi-logarithmic type to contain water supply curves and systems requirements plus inside and outside hose requirements so to present a graphic summary of complete hydraulic calculation. Include fire hose system cabinets, valves, racks, hose, wrench and all extinguishers including wall brackets. SUBMITTALS .1 Submit shop drawings on pumps, hose cabinets, fire extinguishers, fire department pumper connections, compressors and other major items. .2 Submittals shall be approved by the Consultant and the University of Manitoba prior to fabrication and installation of the system. .3 Before commencing Sprinkler System installation prepare and submit for acceptance, a complete design, hydraulic calculations and working plans to the Authorities and Consultant. All work with other trades, especially work by other Sections of this Division and Division 16 must be co-ordinated. Extra compensation to remedy interference problems with the Work of Division 15 and 16 Subtrades will not be considered. .4 Submit samples of sprinkler heads and guards. .5 Refer to Section 01810 for additional documentation details and requirements. PART 2 - PRODUCTS 2.1 AIR COMPRESSOR / AIR MAINTENANCE DEVICE .1 Provide an air compressor or maintenance device, sized to completely refill the system within 30 minutes. Compressor: Reliable Model A or approved equal. Air maintenance device: Viking Model D-2 or approved equal. .2 Set the dry pipe system air pressure at the maximum recommended by the information sheet for the dry pipe valve or at 20 psi greater than the standard calculated trip pressure. .3 The PS-40-2 switch setting shall be as follows: The high setting will be the high calculated value plus 10 psi; the low setting will be the low calculated value minus 10 psi. For compressors, the start point shall be set at 5 psi below the lowest calculated point. 2.2 ANGLE VALVES .1 [NPS 1½ cast or forged brass valve with hand wheel, brass cap and chain.] .2 Angle Valve: Bronze NRS gate valve, 64mm (2½"), rate for 1380 kPa (200 psi) operating pressure, c/w 64mm x 38mm (2½" x 1½") reducer, brass cap and chain. National Fig. A56 .3 Angle pattern hose valve: Provide valve with open or drip connections or hydrolator valve so installed that leakage past valve seat will not enter hose. .4 Where water pressure exceeds 690 kPa provide restricting disc orifice restriction to prevent water pressures in excess of 620 kPa from entering hose. 2.3 ANTIFREEZE SYSTEMS .1 Provide propylene glycol based antifreeze system where shown on drawings to NFPA 13-2010 standards. .2 Provide glycol fill station where shown on drawings. Approved indicating valve c/w position monitor switch, which shall be wired to fire alarm system by Div. 16. Provide glycol fill cap, two solution test valves, RP backflow and expansion tank, system drain valves, etc. All as shown in NFPA 13 2010 Figure 7.6.3.3. All components shall be rated for 1210 kPa (175 psig) working pressure. .3 Piping and valves in glycol U-loop shall be securely supported on wall. 2.4 BACKFLOW PREVENTION .1 Where standpipe and/or sprinkler systems are connected to a potable water supply, provide the following: February 27, 2015 University of Manitoba Req # FIRE PROTECTION Section 15500 Page 5 .1 .2 A double check valve assembly to CSA B64.5 where no water treatment, antifreeze or other chemicals are used in the standpipe or sprinkler systems. A reduced pressure principle back flow preventer to CSA B64.4-M where chemicals, water treatment, or antifreeze are used in the standpipe or sprinkler systems. 2.5 BALL VALVES .1 Up to and including 50mm (2") - Ductile iron body, stainless steel ball and stem, TPE seats. Manual gear operator with position indicator. Valve rated for 2.1 mPa (300 psi) operating pressure and complete with supervisory switch. 2.6 BOOSTER PUMP TEST CONNECTIONS .1 Provide in quantities and in locations as shown on the drawings National Fire Equipment Model 230 flush mounted chrome plated wall hydrants with escutcheons and stainless steel screws. .2 Other acceptable manufacturers: CFH, Stelpro, Wilson and Cousins. 2.7 BUTTERFLY VALVES .1 Valves NPS 2 and under: bronze to ASTM B61-80 for both horizontal and vertical mounting Iron body lug style valve with chrome plated disc and replaceable EPDM seat. Manual gear operator with valve position indicator. Valve rated for 1,210 kPa (175 psig) operating pressure. ITT, Grinnell L829 ULC listed ball valves. 2.8 CHECK VALVES .1 Valves NPS 2 and under: .1 bronze to ASTM B61-80 for both horizontal and vertical mounting with replaceable composition disc, screwed cap and ends. .2 Valves NPS 2½ and over: .1 Underwriters' Laboratories pattern, iron body, bronze mounted, regrind-renew bronze disc and seat ring, and flanged or grooved ends. Design for either horizontal or vertical mounting. .3 Check valves: .1 Check valves shall be grooved, iron body, bronze seat, stainless steel clapper with a replaceable rubber seal (a rubber seal integral with the seat is not acceptable), and 175 psi non-shock cold water working pressure. Use Viking Model D, or approved equal. .4 Double check valve assembly: .1 Provide a double check valve assembly including the two OS&Y gate valves 2.9 DELUGE SPRINKLER SYSTEM .1 Provide open head deluge sprinkler system including following items: .1 Signage at wet valve if supplying deluge system. .2 Reliable deluge valve complete with all necessary trim for approved installation. .3 Approved OS & Y or butterfly main control valve. .4 Approved check valve. .5 Deluge system release valve, pilot operated diaphragm solenoid valve, power characteristics as required by electrical. .6 Tampered isolation valve above deluge valve for trip testing. .7 Fire Alarm Panel supplied by Div. 16 shall contain primary power supply, release control, pilot lights and auxiliary contacts as required for operation of the deluge sprinkler system. Provide normally open and normally closed contacts for fire alarm system a required by Division 16. .2 Provide complete operating and maintenance instructions for every sprinkler main control valve assembly. Mount in frame c/w Plexiglas and mechanically fasten onto wall adjacent to valve assembly at approximately 1.5 m above floor. February 27, 2015 University of Manitoba FIRE PROTECTION Req # Section 15500 Page 6 2.10 DRAIN VALVES .1 Drain valves to be ULC Listed, screw-in bonnet bronze globe valves, rated to 175 psi non-shock cold water working pressure by Nibco, United or approved equal. Low point drain valves shall have, in addition, a ¾-inch brass nipple with ¾-inch male hose threads and cap. 2.11 DRY PIPE ALARM VALVE .1 Provide a dry pipe alarm valve, trim package, accelerator and air maintenance device, all by the same manufacturer. 2.12 EXCESS PRESSURE (JOCKEY) PUMP .1 Albany Model CEP-67, or acceptable alternative, bronze close-coupled rotary gear type complete with 1/3 HP motor, flexible hose connections, discharge check valve, suction strainer, mounting bracket, PRV set at 1085 kPa (125 psig) and pressure switch rated for pump operation with range 70 to 860 kPa (10 to 125 psi). 2.13 FINISHES .1 Chrome plate valves, nozzles, fittings, hose rack, and spanner 2.14 FIRE DEPARTMENT CONNECTIONS .1 Provide fire department pumper connection to supply sprinkler system, stand pipe system, and/or sprinkler & standpipe system as indicated. .2 Provide flush-type bronze fire department pumper connection with 4” – 2 lug, hard-coated aluminum, storz connection angled at 30º downward. .3 The storz connection shall be complete with a lock on the inlet and shall conform to the National Standard Thread. The hose sealing surface shall be machined and protected against long-term exposure to the environment. .4 A semi-permanent ¼” mesh screen, constructed of corrosion-resistant metal shall be installed in the storz adaptor. The protective screen must be capable of withstanding high water flows without leaks and be resistant to tampering. .5 The assembly shall have a 4” cap with a chain or cable to secure it. .6 A brass identification plate specifying “Auto Sprinkler”, “Standpipe”. Or “Auto Sprinkler & Standpipe” shall be mounted on the wall at the fire department connection. .7 The fire department connection shall be installed between 30” and 48” above grade. .8 The fire department connection shall be ULC listed and approved. .9 Provide straightway check valve and automatic drip piped to the nearest floor drain. 2.15 FIRE HOSE CABINETS .1 National Fire Equipment Ltd. consisting of a 16 gauge steel factory prime coated tub with trim and door of 12 gauge steel and 5mm (3/16") clear float glass front, complete with 30 m Polyflex single jacket hose, water stop, pin rack, [chrome plated] forged brass couplings attached, 40mm (1½") [A156 pressure restricting] [chrome plated] forged brass valve with hydrolater, 65mm (2½") [A156 pressure restricting] [chrome plated] brass angle hose valve with cap and chain, 40mm (1½") [chrome plated] [ brass plated ] Lexan straight stream fog nozzles and [11.37 1 (3 US gal.) copper [ chrome plated ] pressurized, filled and tested water extinguisher with ULC listing 2A] [multi purpose, ammonium phosphate type tested and charged extinguisher with ULC listing 2A10BC, 2.3 kg (5 lbs) capacity] and one spanner. [Provide 6mm (¼") Lexan fronts on doors, brass valves and couplings and unplated nozzles in parking garage areas.] .2 Cabinets to be surface mounted or recessed as indicated on drawings. .3 Fire hose and extinguisher cabinets; flush, as indicated, constructed of 1.6 mm thick steel with full opening door of 2.5 mm thick steel. Construct and hinge door to prevent sway or sag when opened. .4 Provide back of flush or semi-recessed cabinets with fire resistance equal to fire resistance of wall or partition in which they occur. February 27, 2015 University of Manitoba Req # FIRE PROTECTION Section 15500 Page 7 .5 .6 .7 Equip cabinet door with approved latching device. Provide cabinet door with 5 mm glass viewing panel metal panel 33.3% of door area. Provide angle valve, hose rack, fire hose nozzle and spanner, fire extinguishers in each cabinet. 2.16 FIRE EXTINGUISHERS AND CABINETS .1 Provide multi-purpose dry chemical extinguishers: stored pressure type with hose and shutoff nozzle ULC labelled for A, B, and C fires with wall brackets or for in-cabinet installations. .2 Provide 4.5 Kg (10#) 4A:60B: C Flag or Williams extinguishers as a minimum size in all applications except computer rooms. .3 In computer rooms provide 2.25 Kg (5#) Flag or Amerex CO2 fire extinguishers. .4 Provide wall brackets and cabinets as indicated on drawings. .1 Fully recessed fire extinguisher cabinets to be equal to National Fire Equipment Limited Model 950-3 with 5mm (3/16") clear float glass front. .2 Semi-recessed cabinets to be equal to Model CE-950-3-2 with 5mm (3/16") clear float glass front. .3 Surface-mounted cabinets to be equal to Model CE-950-3-SUR with 6mm (¼") Lexan fronts. 2.17 FIRE HOSE, NOZZLE AND SPANNER .1 Hose: Underwriters' Laboratories labelled 30.5 M long, NPS 1½ nominal diameter, synthetic-rubber lined, mildew and rot resistant. .2 Nozzle: NPS 1½ forced brass or U.L.C. labelled plastic, adjustable combination fog-straight stream with shut-off. 2.18 FIRE HOSE VALVE CABINETS .1 Provide National Fire Equipment Limited Model CV-975 fully recessed valve box with 1/4" thick glazed door, 1/2" adjustable trim turn back. .2 Provide a minimum of 4 additional spanners for hose couplings. 2.19 FIRE HYDRANTS AND VALVES .1 Provide all hydrants and valves to local Municipal requirements. .1 Compression type ULC and FM approved with 2 - 65mm (2½") hose nozzles [and a 100mm (4") Storz connection] with interior main valve 133mm (5") minimum diameter. End connections: 150mm (6") MJ, flanged, or ringtite to suit supply pipe used. Hydrant to have safety flange and stem. Crane - McAvity model M-67. .2 Hydrant isolation valves: Crane "McAvity," to AWWA C509, 2006R flanged or with connections to suit supply piping 150mm (6") IBBM NRS type with 50mm (2") square operating nut with extension stem and McAvity adjustable sliding type valve box. .3 Water main gate valves: Iron body, inside screw, bronze trim, Underwriter's pattern Crane "McAvity" #6168-0 flanged or with connections to suit supply pipe being used and to be complete with McAvity adjustable sliding type valve box. .4 Post indicators, where shown on the Drawings: Crane or McAvity model 6225, ULC and FM approved [with type SS supervisory switch]. [Wall Type; Crane 20060 with 6226 post and wheel operator.] .5 Hydrants and valves as manufactured by Grinnell are also acceptable. 2.20 FITTINGS .1 All steel, galvanized, malleable or cast iron fittings shall be manufactured in Canada or the United States of America. .2 All fittings shall be rated for 1210 kPa (175 psi) working pressure and able to withstand 1400 kPa (200 psi) test pressure. .3 Nipples: No close nipples will be permitted. February 27, 2015 University of Manitoba FIRE PROTECTION Req # Section 15500 Page 8 .4 .5 .6 .7 .8 .9 .10 .11 .12 Grooved fittings and couplings shall be Victaulic or Gruvlok. Grooved couplings and fittings shall be of the same manufacturer. Couplings shall be rigid couplings except where noted otherwise. For couplings on dry pipe systems use a ‘flushseal’ or ‘flush gap gasket. Hole cut outlets, new systems: No hole cut outlets may be used on new sprinkler systems. Hole cut outlets; existing systems: hole cut outlets may be used on existing sprinkler systems only in isolated locations as approved in writing by the U of M Plumbing Shop . Hole cut outlets shall be a full-bodied outlet. U-bolt outlets will not be permitted. Plain end couplings (Roust-A-Bouts, Plainloks, or similar couplings) and Victaulic F.I.T. and Victaulic Style 922 Hooker fittings shall not be used on new or existing sprinkler systems. Plastic piping systems are not permitted without written permission from U of M Plumbing Shop. Pipe flanges: Victaulic or Gruvlok split flanges are permitted on sprinkler systems with grooved fitting and piping. For sprinkler systems with welded piping use Class 150 forged steel flanges. Provide suitable red rubber ring or full-face gasket, machine bolts and hex nuts unless otherwise recommended by manufacturer. Flange bolts: square or hex head bolts with heavy hex nuts. On new sprinkler systems with looped or gridded piping, 1¼“and 1½” grooved couplings may be used in lieu of unions where required for tie-ins where approved by U of M Plumbing Shop. When connecting new piping to existing sprinkler systems, 1¼“ and 1½” grooved couplings may be used in lieu of unions where required for tie-ins where approved by U of M Plumbing Shop. 2.21 FLOOR PLATES .1 Where pipes pass through masonry walls provide steel pipe sleeves full thickness of wall. .2 Risers shall have watertight floor sleeves as recommended in NFPA #13. .3 Provide split or solid round floor plates on all exposed pipes passing through walls, floors, or ceilings. 2.22 FLOW SWITCHES .1 Provide ULC approved paddle-type flow switches with double sets of contacts in the mains where indicated on the drawings and where required elsewhere for zone alarms, etc. Flow switches shall be DPDT type with time delay. .2 Wiring for flow switches to be provided by Division 16. 2.23 GATE VALVES .1 Valves: 40mm ( 1½") and smaller: Bronze to ASTM B61-80.1, OS & Y pattern with threaded ends, rated for 1.2 mPa (175 psi) operating pressure. Jenkins Fig. 820. .2 Valves 50m (2") and larger: Underwriters' Laboratories pattern, iron body, bronze mounted, with Outside screw and yoke (OS & Y) pattern, double disc or wedge, with flanged or grooved ends, rated for 1.2 mPa (175 psi) non-shock cold water operating pressure. Jenkins Fig. 825A. 2.24 GLOBE VALVES .1 Valves 50mm (2") and smaller: bronze to ASTM B61-80 screwed ends, composition disc replaceable without removing valve from line. .2 Valves 64mm (2½") and larger: iron body, bronze mounted OS&Y, flanged ends bolted bonnet and yoke, bronze seat, solid bronze disc, seat and disc replaceable without removing valve from line. 2.25 HANGERS AND SUPPORTS .1 Sprinkler system shall be in accordance with NFPA 13. .2 Standpipe system shall be in accordance with NFPA 14. February 27, 2015 University of Manitoba Req # FIRE PROTECTION Section 15500 Page 9 .3 .4 .5 .6 .7 .8 Hangers: Provide hangers to support all piping in perfect alignment without sagging or interference and to permit free expansion and contraction. Pipe rings shall be zinc coated Grinnell figure 69 or approved equal. Hanger rods: Hanger rods shall be electro-galvanized. Riser clamps shall not protrude more than 50mm (2”) beyond the edge of the hole. The riser clamps shall be ULC listed, Grinnell figure 261. Concrete expansion anchors shall be Hilti, Phillips, Impex or ITW. Explosive type fasteners are not permitted. Do not suspend pipe, equipment of devices from formed hollow metal decking. 2.26 HOSE RACK (FOR CABINETS) .1 Rack: Swivel type with pins to permit hose to be hung in folds or stationary type rack with pins designed for 180° movement. Locking pin shall prevent flow of water into hose until last fold is removed from rack. 2.27 ISOLATON VALVES .1 Isolation/control valves: Sprinkler system, standpipe, and other above ground controlling valves shall be gear-operated slow-close butterfly valves with flag type indicator, cast iron lug body, bronze disc, EPDM crowned seat, stainless steel stem with bronze bushings, two internal single-pole, double-throw monitor switches, and locking chain supplied by the valve company. Use Grinnell Series 7700FP or approved equal. 2.28 MATERIALS, EQUIPMENT, VALVES AND DEVICES .1 Materials and equipment: All materials and equipment in the system shall be new and current products of a manufacturer regularly engaged in the production of such materials and equipment. Where two or more pieces of equipment are required to perform interrelated functions, they shall be products of one manufacturer. .2 All materials shall conform to standards listed in the current edition of applicable Building Codes. .3 All materials, equipment, valves, devices equipment, and components shall be listed, labeled and approved for intended use by Underwriters Laboratories of Canada (ULC) or Factory Mutual (FM), as well as the Authorities, Agencies, Codes and Standards named in this Section and meet with the approval of the authority having jurisdiction. 2.29 PIPE .1 .2 .3 .4 .5 .6 .7 .8 .9 .10 All steel, galvanized steel, or other ferrous pipe shall be manufactured in Canada or the United States of America. Sprinkler Systems: Pipe and fittings to current requirements of NFPA 13. Provide galvanized pipe and fittings for dry and preaction sprinkler systems. Buried yard piping: PVC equal to John's Manville Class 150 water pipe with rubber gasketted fittings. Provide thrust blocks at all tees and changes in direction as well as at hydrants in accordance with Manufacturer's instructions. Standpipe Systems: Pipe, fittings, hangers and accessories to NFPA 14 and current Codes. Steel pipe: All pipes shall be ferrous and meet the requirements of NFPA 13 and NFPA 14 in all respects. Pipe 2" and larger shall be joined by roll groove mechanical couplings or by welding. Pipe 1½" and smaller shall be joined by threaded connections or by welding. Pipe shall be Schedule 40 for pipe 40mm (1½"), and smaller and Schedule 10 for 50mm (2") and larger. Schedule 10 thin wall pipe, as defined by NFPA 13, may be used in wet sprinkler for 50mm (2”) and greater in lieu of schedule 40 when joined by accepted roll grooving methods and couplings, and pipe meets requirements of ASTM A53 - welded and seamless steel pipe. Welding fittings shall be 13,790 kPa (2000 psi) socket weld fittings up to 38mm (1½") and butt weld fittings for sizes 50mm (2") and larger. February 27, 2015 University of Manitoba FIRE PROTECTION Req # Section 15500 Page 10 .11 .12 Welded pipe sections shall be shop fabricated as far as possible and/or to minimize field welding required. Welding on site is not permitted except with special approval of the U of M Plumbing Shop. If site welding is approved, follow all safety precautions required by such authorities. Plastic piping systems are not permitted without written permission from U of M Plumbing Shop. 2.30 PRE-ACTION SPRINKLER SYSTEMS .1 Pre-action sprinkler system including following items. .1 Tampered isolation valve above preaction valve for trip testing. .2 Signage at wet valve supplying preaction system. .3 Reliable Model B deluge valve complete with all necessary trim for approved installation. .4 Approved OS & Y or butterfly main control valve. .5 Approved check valve. .6 Low air pressure switch. .7 Water in pipe pressure switch. .8 System release valve, pilot operated diaphragm solenoid valve c/w manual bypass trip valve. Electrical power characteristics as required by Division 16. .9 Reliable Model C Air Maintenance Device UL listed, suitable for reducing available air supply at 690 kPa (100 psi) to 10 kPa (1.5 psi) to maintain required supervisory air supply. Device shall be complete with pressure gauge, switch and isolating valve. .10 Fire Alarm Panel supplied by Div. 16 shall contain primary power supply, release control, pilot lights and auxiliary contacts as required for operation of the preaction sprinkler system. Provide Normally Open and Normally Closed contacts for fire alarm system as required by Div. 16. .11 All smoke/heat detector heads, which activate this system, shall be identified. Co-ordinate with Div. 16 - Electrical. .12 Provide complete instructions for normal/emergency operation of system and for routine testing, draining, and pre-activating system. Mount on wall adjacent to valve station at approximately 1.5m (5 ft.) above floor. Instructions shall be mounted in frame c/w Plexiglas. 2.31 PRESSURE REDUCING VALVES .1 Provide, where required, ULC and FM labelled pressure reducing valves (PRV) with adjustable spring range, sized to suit required flow and pressure differential, capable of maintaining differential pressure at "138 kPa ("20 psi) during both flow and static conditions. .2 Provide all necessary trim: Downstream and upstream pressure gauges, isolation valves, by-pass valves, pressure relief valve on low pressure side to compensate for leakage across the PRV. 2.32 PRESSURE GAUGES .1 ULC FM approved listed for fire protection. 2.33 SIGNS .1 Signs: fabricated from metal with chain suspension; white letters on red background. 2.34 SPARE SPRINKLER CABINET .1 Provide a lockable spare sprinkler cabinet to accommodate the required number of spare sprinklers and escutcheons. Include two wrenches for each type of sprinkler in the cabinet. Paint the cabinet fire red and label the cabinet with a riveted or screwed laminated plastic nameplate indicating "SPARE SPRINKLER CABINET" in white letters on a red background, letters to be 3/8” high. February 27, 2015 University of Manitoba Req # FIRE PROTECTION Section 15500 Page 11 .2 Provide spare sprinklers and escutcheons shall for each type and style of sprinkler used in accordance with NFPA 13 and proportioned based upon the number of each type and style of sprinkler used on the job. 2.35 SPLASH PAD .1 Provide a splash pad at the point of discharge for the drains outside of the building, if the ground will be disturbed by the flow of water. 2.36 [SPRINKLER BOOSTER PUMP:] [COMBINED SPRINKLER/STANDPIPE BOOSTER PUMP] .1 Provide, in location and as detailed on the drawings, a complete packaged factory assembled and tested [duplex] booster pumping system consisting of horizontal split case pumps, electric motor drives, coupling guards, controllers, accessories, listed and labelled by ULC; [100% stand-by capacity;] meeting requirements of NFPA 20. .2 Selection: To satisfy hydraulic load calculation for sprinkler [and standpipe] systems to provide a residual pressure of 450 kPa (65 psi) at the most remote hose station while providing the required flow for both sprinkler and standpipe systems. .3 Performance: Capable of delivering not less than 150% of rated capacity at a pressure of not less than 65% of rated head; Shut-off pressure not to exceed 120% of rated head at rated capacity; maximum permissible motor size; [kW] [HP]. .4 Accessories: Discharge tee, air release valve and fittings, discharge and suction pressure gauges, by-pass relief valve or pressure relief as required by system design. .5 Controller[s]: Combined manual and automatic reduced voltage starting (star delta closed transition) with externally openable quick-break disconnect switch, time delay type circuit breaker with trips in all phases set at 300% of full load current and interrupting capacity of 50,000 asymmetrical amperes; factory installed and wired pressure switch and automatic stop. .6 Control Functions: Drop in system pressure starts [lead] pump, which runs for a minimum of 10 minutes for electric and 30 minutes for diesel. [On further pressure drop or lead pump failure, second pump to start automatically. Second pump cannot be energized unless first pump is de-energized.] .7 Monitoring: Pilot lamp to indicate power available. Provide three (3) sets of normally open dry contacts for remote monitoring to indicate: .1 Pump running; .2 Loss of power; .3 Phase reversal. 2.37 SPRINKLER HEADS .1 Install sprinklers as required to provide Code coverage. .2 Provide minimum NPS 12mm (½”) diameter discharge orifice, except when approved by FCC. .3 Sprinklers shall be listed with and bear certification marking of a nationally recognized testing agency. .4 Finished ceilings: Provide pendant type sprinklers of current manufacturer, chrome plated with chrome-plated escutcheons unless noted otherwise. Provide sidewall type where noted. .5 Unfinished areas or areas where sprinkler piping cannot be concealed: upright with finish noted on drawings. .6 Flush mounted: concealed sprinkler c/w white cover in locations noted on drawings. .7 Provide chrome-plated recessed sprinkler c/w white ceiling cup in locations noted on drawing. .8 Provide dry pendant sprinkler in locations noted on drawings. .9 Elevator sprinkler heads shall be selected at approximately 20% higher temperature rating than the fire alarm sensor device. .10 Provide bronze finish for sprinklers in crawlspace areas or as noted on drawings. Provide chrome plated finish for sprinklers in all other areas. .11 Sprinklers shall be listed with and bear certification marking of nationally recognized testing agency. February 27, 2015 University of Manitoba FIRE PROTECTION Req # Page 12 .12 2.38 Section 15500 Provide ULC Listed wire guards for all heads in gymnasium, generator room, mechanical rooms, crawlspaces, storage rooms, shop areas, as well as all sprinkler heads subject to mechanical damage and for any sprinkler lower than 7' 0" above the floor. STANDPIPE .1 Connection for standpipe system to be off sprinkler main. .2 Provide fire standpipe system c/w hose valves, cabinets, piping, etc. .3 System shall meet approval of Authorities having jurisdiction. .4 As construction progresses, install and maintain all fire standpipes and hoses as required by Authorities during building construction. .5 Main shut-off valve for system shall have metal sign, attached to valve with chain, marked “COMBINED SPRINKLER/FIRE STANDPIPE - DO NOT CLOSE.” .6 .7 .8 .9 .10 Provide 89mm (3½”) dial pressure gauge with three-way test valve at top of each standpipe. Install test valve with sufficient clearance at spare port to permit connection of 100mm test pressure gauge. Valve test port shall be plugged. Provide 25mm (1”) valves with nipple and cap at all low points to permit draining system or any section of system. Provide pressure gauges at highest point of each standpipe riser. Provide NPS ¼ gauge connection, fitted with 3-way valve. Provide each hose station with fire hose and extinguisher cabinets. Provide where indicated exposed brass wall hydrants with escutcheon, NPS 4 inlet, 2 NPS 2½ outlets with threads as required, NPS ¾ ball drip, control valve with complete operator assembly with brass outlet caps and chains. Control valve to be NPS 4 non-rising stem. 2.39 SUPERVISED VALVES .1 Provide UL listed valve position monitor switches securely mounted on every shutoff valve controlling water supply to sprinkler and/or standpipe systems, to provide supervisory signal if valve is moved away from fully open positions. Wiring to alarm by Div. 16. .2 Sprinkler and standpipe system branch supervised valves to be butterfly-type ULC / FM Dual approved, complete with micro-switch for wiring into the fire alarm annunciation system. Micro-switch to be in the closed position when the valve is full open and switch to open when the valve stem moves away from full open position. Wiring to annunciator panel by Division 16. .3 Switches shall be finger-type switch. Electrical configuration normally closed contacts and shall be confirmed with Div. 16 before ordering switches. Plug type switches not acceptable. 2.40 VALVES .1 Valves: .1 Of one manufacturer for fire protection .2 ULC listed; bearing manufacturer's name trademark and FM identification figure number and pressure rating. .3 Unless otherwise specified or indicated design for 1.2 mPa (175 psi) working water pressure. .4 All valves shall be indicating valves. .2 Valves with rising stems shall be repackable under pressure. Provide malleable iron hand wheels. .3 Valves on fire lines and standpipe: .1 Equip with contacts and devices necessary for operation of supervisory system specified under "Fire Detection and Alarm System" Section 16601. .4 Acceptable Manufacturer: Victaulic .5 Style 727 2" - 3". Style 705 4" - 8". February 27, 2015 University of Manitoba Req # FIRE PROTECTION Section 15500 Page 13 .6 .7 .8 100 mm (4") and larger above ground: iron body, bronze trim O S & Y, flanged or grooved 200 psi, U.L.C./FM approved. McAvity 10269, Nibco F6070TS ULC. 100 mm (4”) and larger buried: non-rising stem, iron body bronze trim, SS bolts, integral bonnet, ULC/FM approved, McAvity series 616 or Nibco F609/M609 ULC to suit pipe connections. Hydrants: Cast iron construction ULC/FM approved for 9'-0" bury with 1-100 mm (4”) pump and 2½ (65mm) hose connections, compression valve, SS bolting for 150 mm (6") line connection, constructed to AWWA C502 standard: McAvity M-67. 2.41 WET PIPE SYSTEM .1 Note: alarm valves / excess pressure pumps not required if DCVA and time delayed flow switch used. .2 Provide complete with following: .1 Indicating control valves. .2 Inside electric gongs and circuit closer. .3 Outside electric gongs and circuit closer. .4 Excess pressure pump. .5 Indicated water gauges. .6 Piping and fittings. .7 Valves. .8 Hangers. .9 Floor and ceiling escutcheon plates. .10 Backflow preventer. .3 Provide 100 mm electric gong operated by alarm device. .4 Provide standard water flow, valve alarm devices and main control valve. Provide trouble transmitter low air circuit closer for complete central station electrical supervision of system, including battery and rectifier and locate adjacent to alarm valve. .5 Provide valved filling arrangement and anti-freeze solution for areas subject to freezing. .6 Provide complete supervision of water flow, alarm, and control valves for each floor and stand pipe riser to building fire alarm system and central station. 2.42 WINDOW SPRINKLER SYSTEM .1 General .1 The window sprinkler assembly system consists of distribution and interconnecting piping, window sprinkler heads, hangers, baffles, alarm flow switches, control valves, check valves, electrical switches and associated equipment. The system is to provide a fire separation for the designated window areas. The window sprinkler assembly system shall be zoned separately from the floor sprinkler system. Only a wet pipe system can be used for this type of installation. .2 It is the responsibility of the Contractor to install the system to meet the design criteria. .3 Provide an operating window sprinkler assembly system, including labour, piping, fittings, hangers, drains, window sprinkler heads, alarm devices and other components as required by the contract documents. .4 Areas to be protected by the window sprinkler assembly system are indicated on drawings. .5 With the exception of the combined window sprinkler/floor sprinkler system riser, the window sprinkler assembly system shall be independent from the floor sprinkler system. Make necessary connections to the riser to provide an operating window sprinkler assembly system. .6 The Contractor shall notify the Consultant as soon as the first window sprinkler head is installed. Early inspection should ensure that the installation and positioning of the heads will be made correctly throughout the entire project. .2 Design Criteria .1 The window sprinkler assembly system shall be hydraulically calculated as per the design areas indicated on drawings. February 27, 2015 University of Manitoba Req # FIRE PROTECTION Section 15500 Page 14 .2 .3 .4 .5 .6 Window sprinkler heads shall be located at top centre of each windowpane. See specification detail drawing. .3 The window sprinkler assembly system shall provide a minimum of 95 liters per minute (25.0 US gpm) of water per discharge head at a minimum starting pressure at the window sprinkler head of 138 kPa (20.00 psi). .4 Hydraulic calculations shall be conducted on the basis that window sprinkler heads installed in the design areas will operate simultaneously. .5 Minimum water discharge time is 2 hours. .6 Window sprinkler deflectors shall be installed between 12 mm (1.2 inch) and 19mm (3/4 inch) from an overhang and between 12mm (1/2 inch) and 19mm (3/4 inch) from the glass surface. Refer to specification detail drawing. .7 Water demand for the fire protection systems shall be based on the water demand for the window sprinkler heads in the design area and water demand for the floor sprinkler system, plus the water demand for standpipe hose requirements. .8 Components of the window sprinkler assembly system (with exception of the window sprinkler heads) and the installation method shall comply in every way with Underwriters’ Laboratories of Canada listing or Factory Mutual (FM) approval for their intended use. If deviations to listings or approvals are proposed, these deviations shall be indicated and explained in writing by the Contractor in the tender submission and is subject to approval by the Consultant. .9 NFPA 13-1990 requirements shall apply where no requirement is listed herein. .10 Major components of the system shall have an integral nameplate with the manufacturer’s name, model number, serial number, capacity, date and electrical characteristics where appropriate. Nameplates, including ULC or FM marker plates, shall be placed in conspicuous locations. .11 Refer to specification details illustrating location of window sprinkler heads and system installation. Shop Drawings .1 The Contractor shall provide necessary mechanical drawings of the system to be installed. No installation shall commence until shop drawings and hydraulic calculations have been approved by the consultant (Morrison Hersfield Limited) and the Authority having Jurisdiction. Drawings shall include the following: 1. Location and method of installation of the window sprinkler assembly system. 2. Size and locations of pipes, including equivalent lengths of pipe fittings. 3. Details and locations of hangers. 4. Details and locations of baffles. 5. Piping elevations. 6. Window sprinkler head layouts. 7. Valve locations and arrangements including auxiliary drains. 8. Technical data for equipment. 9. Window sprinkler head coefficients. 10. Hydraulic calculations including supply/demand graph. 11. Identification of the window mullions on the drawings. Window Sprinkler Heads .1 The sprinkler heads for the window sprinkler assembly system shall have an activation temperature of 73°C (165°F). .2 Window sprinkler heads shall have a chrome plated finish and a chrome plated escutcheon plate mounted at the ceiling, except when the piping is fully concealed. Baffles .1 Baffles are required wherever window sprinkler and/or floor sprinkler, are less than 1.8m (6 ft.) apart. Vertical mullions exceeding 50mm (2”) in depth (from glazing to top of mullion) are acceptable. .2 Baffles are to be arranged to shield the actuating elements. .3 Baffles will be supplied and installed by architectural sections. Identification February 27, 2015 University of Manitoba FIRE PROTECTION Req # Section 15500 Page 15 .1 .2 .3 Identify piping and equipment throughout with labels. Apply labels at 12m (40 ft.) in the equipment rooms as required. Letters shall be black minimum 1.9cm (¾”) high of yellow backgrounds. Labels shall read “Window Sprinkler System”. Provide each control valve, shut-off valve, drain valve and test valve with a sign. The size of the sign shall be a minimum of 40mm (1½”) in diameter and shall indicate the position of the valve. Secure the sign to the valve wheel with a key chain. A neat, typewritten directory giving valve number, valve service and location of valves is to be provided in the maintenance manual by the contractor and at main control valve. Provide signs on control valves associated with the window sprinkler assembly system. Signs shall read: “WARNING” SPECIAL SPRINKLER HEADS ON THIS SYSTEM ARE AN INTEGRAL PART OF WINDOW FIRE SEPARATION. THIS WATER SUPPLY MAY ONLY BE SHUT OFF AFTER ALL THE PROPER AUTHORITIES HAVE RECEIVED NOTICE IN WRITING. .4 Signs shall be noncombustible, legibly printed in not less that 12.7mm (½”) block letters with contracting white background and red letter, shall be permanently mounted and maintained beside the main water supply source to this window sprinkler assembly system and any control valves associated with the window sprinkler assembly system. PART 3 – EXECUTION 3.1 ADJUSTMENT .1 Adjust equipment to satisfaction of FCC and authorities having jurisdiction. 3.2 ANCHORING .1 Provide joint anchors, thrust protection, etc. at all critical points in the piping systems throughout the building designed to withstand hydraulic shock and stresses produced by the pumping system. Submit anchor and thrust block design for review by the Consultant. 3.3 BOOSTER AND EXCESS PRESSURE PUMPS .1 Install pumps in locations where they are readily accessible for maintenance and servicing. Refer to manufacturer's instructions and applicable codes for proper arrangement and connections. Mount the booster pump control panel as close as possible to the pump, but in a location providing at least 1m (3 ft.) clear space in front of the panel. .2 Provide the services of the pump manufacturer for field testing of the pumps, motors, and controllers. .3 Provide a full flow test and plot the actual pump performance curve. Comply with all other testing procedures as required by Authorities. .4 Perform all testing in the presence of the Authorities and the Consultant. Submit all test results to the Consultant. 3.4 COOPERATION WITH TRADES .1 Co-operate with all other sub-contractors and/or sub-trades installing equipment which may affect proper installation and operation of work and arrange sprinkler heads, etc. in proper relation to other apparatus, such as lighting fixtures, unit heaters, air inlets, air outlets etc., both new and existing. .2 Provide wiring diagrams, dimensions of concrete bases, dimensions of masonry openings, etc. as required by other sub-contractors and/or sub-trades. February 27, 2015 University of Manitoba Req # FIRE PROTECTION Section 15500 Page 16 3.5 DRAINS .1 System drains and test connections: run to the nearest open drain in the building or to outdoors through wall away from paved areas. Seal and caulk around piping through wall and provide escutcheon and prime paint all metal surfaces exposed to outdoors. [run to the nearest janitors sink. Secure exposed piping with ring stays. Use copper piping only where exposed in the vicinity of the janitors sink.] .2 Route PRV drain line on pressure reducing station into the inspector’s test and drain line. .3 [Run] the base of the inspectors test and drain line and fire pump by-pass line [into storm drain]. .4 Provide drum drips on dry sprinkler system piping at low points and at any point where piping is trapped. 3.6 DRUM DRIPS .1 Provide drum drips on dry sprinkler system piping at low points and at any point where piping is trapped. 3.7 EXAMINATION OF DRAWINGS AND COOPERATION .1 Examine all architectural, structural, mechanical, and electrical drawings before preparing shop drawings. Arrange position of sprinkler heads, pipes, etc. as required to prevent interference with work of other trades, and existing conditions. 3.8 EXISTING CONDITIONS .1 Before commencement of any work, examine work of other trades and make immediate report to Consultants of any defect or interference affecting work or guarantee of this work. .2 In case of buildings or site conditions existing prior to tendering, examination and report must be made at least seven (7) working days prior to closing of tenders, otherwise existing conditions will be considered acceptable to Section 15500, and no later allowance will be made for extras relating to these conditions. 3.9 FIELD QUALITY CONTROL .1 Subject systems and equipment to operational test. .2 Hydrostatically test fire hose and standpipe systems, including water supply connections and fire department connections at 350 kPa in excess of normal working pressure but not less than 1.4 mPa for 2 h without loss under supervision of FCC. .3 Upon complete installation of piping and apparatus for sprinkler systems, test joints for tightness and good condition of piping inspected in presence of FCC. When testing with water, install pressure gauge at highest point of installation. If impossible to test whole installation in single operation, sub-divide into several zones and test each zone in manner described. .4 During tests, stop any leaks and remove and repair any defective part. Perform test over again until satisfactory results are obtained. .5 All tests must be coordinated to ensure U of M Plumbing Shop Manager or Sprinkler Installer witnesses each test. 3.10 FIRE EXTINGUISHERS .1 Refer to drawings for location and types of extinguishers. Install brackets on firm backing to manufacturer's instruction. Install cabinets securely with flanges flush with finished wall surfaces. 3.11 HOLES IN STRUCTURAL MEMBERS .1 If drilling of structural beams or other load bearing members is required by design or by site conditions for passage of piping, obtain Consultants approval for location and proposed drilling procedure before drilling. Drill only in locations previously approved by Consultant. Where drilling is required by design or existing site conditions, be responsible for carrying out same to approved procedure. February 27, 2015 University of Manitoba FIRE PROTECTION Req # Section 15500 Page 17 .2 Do not cut or install piping until final drilling locations are approved by Consultant. Section 15500 will not be reimbursed for extra cost incurred to relocate piping previously installed on basis of unapproved drill locations 3.12 HOSE CABINETS .1 Locate as shown on drawings with reference to Architectural wall elevations. Ensure valves are no greater than 1500mm (60") above finished floor or as required by Authorities. Also confirm with Consultant. 3.13 HYDRAULIC DESIGN .1 Section 15500 shall have option of using hydraulic design in preparing shop drawings for system. In some cases hydraulic design may be required by job conditions or by authority having jurisdiction. In any case, it shall be responsibility of Section 15500 to carry out necessary calculations, and to submit calculations, data, and drawings in accordance with requirements of NFPA Standard #13, and authority having jurisdiction. .2 Sprinkler systems up to and including floor level elevation [ xxx ] design to use available street pressure. On higher levels: Design to incorporate a booster pump system. .3 Limit pressure to fire hose cabinets to 448 kPa (65 psi) and 865 kPa (125 psi) to sprinkler system. Use approved pressure reducing valve stations as specified. .4 Perform a hydrant flow test to determine flow characteristics on the street watermain. .5 Confirm with the Authorities the allowable flow test data to be used in the design calculations. 3.14 INSTALLATION .1 Do not recess, paint or conceal piping accessories or work prior to inspection and approval by Authority having Jurisdiction. .2 Allow for expansion and contraction when installing pipe hangers. .3 Discharge drains to safe location outside building, allowing at least 1.2 m past drain valve in interior of building to visible point of free discharge at sump. .4 Install signs required by FCC or local Fire Protection Department. Secure outdoor signs with stainless steel bolts. .5 Install alarm valves and electric gongs as indicated and as specified. .6 When water service is for building supplies and fire protection system install indicating control valve on branch line for fire protection systems immediately after branch connections. .7 Install horizontal valves with stems upright where space allows. .8 Arrange drains as indicated so that they can be fully opened without flooding. .9 Install fire hose and extinguishers cabinets so angle valve is 1.5 m above floor, and door, when open, does not obstruct any other door opening. .10 Install or mount fully charged extinguishers in cabinets or on brackets provided by extinguishers manufacturer and as indicated. .11 Do not order, fabricate, or install any material prior to receipt of all approvals as stipulated in Part 1 of this section. .12 Standards and requirements: Perform all installation work in accordance with the reference standards without exception, and as required by the Authority having Jurisdiction. .13 Install all piping straight, true and plumb. .14 Install all piping as shown on the approved shop drawings. Carefully note any minor deviations on the record drawings. Before making significant deviations from the approved drawings, obtain written approval from the Consultant and the University of Manitoba. .15 Carefully coordinate work with other trades so that unnecessary offsets and revisions to the approved drawings are avoided. Failure to coordinate does not relieve Contractor from meeting performance standards. 3.15 LABELLING .1 Label all valves. Provide valve chart at main control. February 27, 2015 University of Manitoba Req # FIRE PROTECTION Section 15500 Page 18 .2 .3 .4 .5 Refer to Section 15050 for additional details. Label all sprinkler systems at the flow switch identifying the zone number. Co-ordinate zone numbers with Division 16 to match numbers on the fire alarm annunciator panel. Label all sprinkler and standpipe zone and riser isolation valves. Mount design information near the labelling point or at base of riser in a glazed frame. Label all piping throughout the building, i.e. "Sprinkler", "Inspector test". 3.16 PIPING .1 Co-ordinate work of this section with all affected trades. .2 Co-ordinate with Section 15180 and Division 16 Subtrades on all traced and insulated piping. 3.17 PIPING SYSTEMS .1 Inside of all pipe, fittings, valves, and all other equipment to be left smooth, clean, and free from blisters, loose mill scale, sand and dirt. .2 Install flanges or grooved couplings at all equipment connections, valves, etc. .3 Install dielectric insulating couplings between all pipes or apparatus constructed of dissimilar metals. .4 Pipe bending, other than wrought iron, permitted only if seamless steel pipe is used without distortion, rippling and reduction in wall thickness. Consultant reserves the right to have pipe section replaced with fittings if bending is not satisfactory. .5 Cut all pipe accurately to measurements taken at site, and shall be installed without springing or forcing. .6 Run all piping in accessible pipe spaces in such a way that it does not interfere with free access into pipe space. .7 Install all piping to provide maximum headroom. 3.18 PROTECTION OF COMPLETED WORK .1 Painter to assume responsibility for protecting heads during painting. Replace damaged and painted components. .2 Paint exposed steel pipe fittings, except special finishes, in accordance with Section 09900. .3 Securely mount ULC listed wire guards for sprinkler heads in all mechanical rooms, gymnasiums, shop areas, and crawlspaces. 3.19 SHOP DRAWINGS, PERMITS AND FEES .1 Prior to installation, prepare complete set of detailed shop drawings in accordance with requirements of NFPA Standard #13, & #14, and inspecting authority. Information as to architectural, structural, mechanical and electrical systems shall be obtained from respective drawings and/or from site. Carry out any necessary flow tests without extra compensation. .2 Detail design shown on shop drawings shall conform to general piping layout and sprinkler arrangement shown on drawings. Consultant’s approval is required for alternative designs or revisions other than as required for co-ordination with other trades and existing site conditions. .3 At completion of work, provide two (2) sets of "As-Built" drawings with all changes incorporated. .4 Submit shop drawings and calculations to Consultant for review and to inspecting and inspection fees. Inspecting authorities for this project will be: .1 Local building inspection department and/or fire department. .2 Owner’s Insurance Underwriters. .3 Morrison Hersfield Limited. .5 Arrange for inspection and testing of all work, and make any changes required to comply with regulations of inspecting authority. .6 Systems shall be designed in accordance with requirements of: .1 Owner’s Insurance Underwriters. .2 Manitoba Building Code and Manitoba Fire Code .3 Local building regulations February 27, 2015 University of Manitoba FIRE PROTECTION Req # Section 15500 Page 19 .4 Morrison Hersfield Ltd. (Window and Deluge Curtain Systems) Telephone (416) 499-3110 Mr. Demir Delen 3.20 SHUTDOWN OF EXISTING SYSTEMS .1 The Project Coordinator shall approve any shutdowns of existing water distribution systems, fire sprinkler systems, domestic water systems or fire alarm systems. Provide advance written notice at least 14 days prior to the shutdown to the Construction Coordinator. 3.21 SPRINKLER HEADS .1 Install and co-ordinate sprinkler head locations with the reflected ceiling plans and Architectural wall elevations and to ensure adequate coverage. .2 Heads indicated on drawings are schematic, for purposes of indicating type of heads only. .3 [Provide additional heads for defined areas to accommodate future office partitioning. Maximum head coverage: 175 ft2 in the perimeter zone, and 200 ft2 in the interior zone.] .4 Install chrome plated escutcheons for heads flush with wall and ceiling surface. 3.22 TESTING .1 Provide all labour, material, equipment, etc. as required to carry out testing as specified herein and as required by authorities having jurisdiction to prove satisfactory completion, performance and acceptance of all systems. .2 Testing shall include: .1 Flow Test .2 Pressure Test .3 Inspectors Tests .4 Pre-action System Tests .5 Deluge System Tests .6 Window Sprinkler Tests .3 Conduct flow tests on water systems as required by authority having jurisdiction. .4 Pressure Tests .1 Perform pressure tests on all new or modified piping systems to requirements of NFPA 13, 14, authority having jurisdiction, and additional requirements noted in this specification. .2 All systems shall be pressure tested after final completion. If subsequent modifications are necessary; e.g. relocation of sprinkler drops or similar minor revisions, pressure tests shall be repeated as directed by Consultant. .3 Sprinkler mains and branch piping above new ceilings shall be pressure tested and all leakage repaired before installation of ceiling tiles. .4 Final pressure test shall be carried out after installation of sprinklers. .5 In addition to hydrostatic pressure tests noted above, and operational tests noted below, all pre-action and deluge sprinkler systems shall be subjected to a pneumatic pressure test. This test shall be carried out after satisfactory completion of operational tests noted below. On completion of operational tests, drain entire pre-action and deluge system including each sprinkler drop leg (pendant sprinklers). Replace all sprinkler heads and test system under 175 kPa (40 psig) air pressure for 24 hours. Test shall be considered satisfactory when observed pressure drop is less that 10kPa (1.5 psig) over 24-hour period. .5 Inspectors Test .1 Inspectors tests shall be performed at all dry pipe, pre-action, deluge and alarm check valve stations, and at all zone stations, flow switches, etc., and at other locations as required by authority having jurisdiction. .2 Tests shall prove satisfactory operation of all flow switches and other alarm devices and all fire detectors connected to pre-action and deluge systems. .6 Pre-Action, Deluge and Window Sprinkler System Test February 27, 2015 University of Manitoba Req # FIRE PROTECTION Section 15500 Page 20 .1 .7 .8 .9 Each pre-action, deluge and window sprinkler system shall be subject to a complete operational test after successful completion of hydrostatic pressure tests noted above. .2 Notify Consultant before testing and arrange suitable time for Consultant to witness test. .3 When conducting work on the Bannatyne Campus, testing of systems connected to the 10" fire main looped service will cause Health Sciences Complex fire pump to run. Notify Owner’s representative prior to performing any work. .4 For each system, verify that main water valve will trip through every associated fire alarm detector circuit. Co-ordinate testing with fire alarm supplier when fire alarm system is being verified. Verify that flow switch for building sprinkler system annunciates on building fire alarm system each time that main sprinkler valve is tripped by an associated fire alarm detector circuit. .5 System control valve shall be open and all other system conditions shall be in normal "ready" condition. System shall be allowed to flood completely and pressurize on at least one occasion. Pre-action system shall remain flooded with water and under normal pressure for a minimum of 24 hours. .6 Verify correct operation of system and components, and provide test documentation. .7 Correct any deficiencies and re-test to satisfaction of Consultant. .8 Drain entire system after testing, including all sprinkler drop legs. .9 After replacing all sprinkler heads carry out pneumatic pressure test as noted in 4.4 above for all deluge systems. Documentation .1 Section 15500 shall properly document all testing distribute same to all authorities having jurisdiction, Consultant, and Owner. Testing shall be repeated as required until acceptable results obtained as determined by authority having jurisdiction and Consultant. .2 On completion on inspections and testing submit to Consultant and authorities having jurisdiction completed signed copies of appropriate NFPA-13 Contractor’s Material & Test Certificate, Forms 85-A and 85-B. .3 Refer to Section 01810 for additional documentation details and requirements. Advance Notice of Testing .1 Arrange suitable times with authorities having jurisdiction, Consultant and Owner in advance of all testing so that all have opportunity to witness testing. Activation .1 All systems including wet, dry, pre-action, deluge and window sprinkler systems shall be left in normal active duty condition immediately following satisfactory completion of testing. .2 Pre-action systems shall be air charged and set for automatic operation. .3 Activate pre-action systems even if associated fire alarm interlocks are incomplete. 3.23 TESTS .1 Co-operate and co-ordinate with Division 16 for all testing on zoning. .2 Pressure Tests: .1 Sprinkler systems; to NFPA 13 requirements. .2 Standpipe systems; for a period of two (2) hours without pressure loss at 345 kPa (50psi) gauge higher than maximum service pressure, but not less than 1380 kPa (200psi) gauge. 3.24 VALVE STATION (AND COMPRESSOR STATION) .1 Arrange piping and equipment to provide adequate service accessibility and minimum space requirements. .2 Provide all electrically connected and supervised equipment and devices such as supervised valves, pressure switches, flow switches, alarm valves, pumps, and February 27, 2015 University of Manitoba FIRE PROTECTION Req # Page 21 .3 3.25 Section 15500 compressor, in locations as indicated on the drawings. Co-ordinate locations of these devices with Division 16. Co-ordinate and co-operate with Division 16 regarding required interconnections for alarm points. WATER SERVICE INSTALLATION .1 Bury all piping below the normal frost line. Refer to detail drawings. END OF SECTION 15500 February 27, 2015