EVSTF-06-05e JRC proposal for adoption of "Venting" as a pass/fail criterion in GTR-EVS Incorporating text from: Current GTR EVS draft (EVS-07-04e) - in black “OICA position on venting”, presentation circulated among TF3 experts on December 9, 2015 – in red JRC input – in green Text for I "Statement of technical rationale and justification ", 4.5. "Rationale for REESS requirements" 1. Definitions of terms related to REESS requirements and its applicability: The following terms are used for setting the pass-fail criteria of REESS requirements; - “Electrolyte leakage” (no definition as it depends on the measurement procedure in certain tests) - “Venting“ (3.X) - “Rupture” (3.31.) - “Fire” (3.18.) - “Explosion” (3.15.) These terminologies, in general, correspond to the relevant industry standards and UN Transport of Dangerous Goods, Manual of Tests and Criteria, paragraph 38.3 (UN38.3.) 2. Applicability of these criteria is considered based on the vehicle status intended for each test scenario; e.g. under normal condition, at an accident or other unusual circumstances, etc. For the tests simulating normal condition, all of four five criteria shall be met, while the tests simulating an accident or unusual circumstances, only the severer events such as Fire or Explosion are applied as the criteria. 3. “Venting”, that generally means the release of excessive internal pressure from cell or battery in a manner intended by design to preclude rupture or explosion, is not adopted as the criteria because venting is a safety feature to mitigate the hazard level in the thermal event of the cell. Text for II "Text of Regulation", 3. "Definitions" 3.X "Venting" means the release of excessive internal pressure from cell or battery in a manner intended by design to preclude rupture or explosion. Text for II "Text of Regulation", 5. "Performance requirements" 5.1.X.1 Under normal vehicle operation, the vehicle occupants shall not be exposed to any hazardous environment caused by emitted gases emissions from REESS. (Same as EVS0719e) 5.1.X.1.1 For the open-type traction battery, requirement of 5.1.X.1 shall be verified by the following test procedure. 5.1.x.1.1.1 (same as current EVS-GTR draft 5.1.Y). 5.1.x.1.2 For REESS other than open-type traction battery, the requirement of 5.1.X.1 is deemed to be satisfied, if when no venting gas occurs is observed as verified by visual and/or audible inspection without disassembling any part of the Tested-Device when tested according to 6.X.X.* (based on EVS-0719e). [5.3.2. Vibration The test shall be conducted in accordance with paragraph 6.2.2. During the test, there shall be no evidence of rupture (applicable to high voltage REESS (s) only), electrolyte leakage, venting (for REESS other than open-type), fire or explosion. The evidence of electrolyte leakage shall be verified by visual inspection without disassembling any part of the Tested-Device. The evidence of venting shall be verified by visual and/or audible inspection without disassembling any part of the Tested Device. For a high voltage REESS, the isolation resistance measured after the test in accordance with paragraph 6.1.1. shall not be less than 100 Ω/Volt.] [5.3.3. Thermal shock and cycling The test shall be conducted in accordance with paragraph 6.2.3. During the test, there shall be no evidence of electrolyte leakage, rupture (applicable to high voltage REESS(s) only), venting (for REESS other than open-type), fire or explosion.; The evidence of electrolyte leakage shall be verified by visual inspection without disassembling any part of the Tested-Device. The evidence of venting shall be verified by visual and/or audible inspection without disassembling any part of the Tested Device. For a high voltage REESS, the isolation resistance measured after the test in accordance with paragraph 6.1.1. shall not be less than 100 Ω/Volt.] [5.3.5. External short circuit protection The test shall be conducted in accordance with paragraph 6.2.7. During the test there shall be no evidence of; electrolyte leakage, rupture (applicable to high voltage REESS(s) only), venting (for REESS other than open-type), fire or explosion. The evidence of electrolyte leakage shall be verified by visual inspection without disassembling any part of the Tested-Device. The evidence of venting shall be verified by visual and/or audible inspection without disassembling any part of the Tested Device. For a high voltage REESS, the isolation resistance measured after the test in accordance with paragraph 6.1.1. shall not be less than 100 Ω/Volt.] [5.3.6. Overcharge protection The test shall be conducted in accordance with paragraph 6.2.8. During the test there shall be no evidence of electrolyte leakage, rupture (applicable to high voltage REESS(s) only), venting (for REESS other than open-type), fire or explosion. The evidence of electrolyte leakage shall be verified by visual inspection without disassembling any part of the Tested-Device. The evidence of venting shall be verified by visual and/or audible inspection without disassembling any part of the Tested Device. For a high voltage REESS, the isolation resistance measured after the test in accordance with paragraph 6.1.1. shall not be less than 100 Ω/Volt.] [5.3.7. Over-discharge protection The test shall be conducted in accordance with paragraph 6.2.9. During the test there shall be no evidence of; electrolyte leakage, rupture (applicable to high voltage REESS(s) only), venting (for REESS other than open-type), fire or explosion. The evidence of electrolyte leakage shall be verified by visual inspection without disassembling any part of the Tested-Device. The evidence of venting shall be verified by visual and/or audible inspection without disassembling any part of the Tested Device. For a high voltage REESS, the isolation resistance measured after the test in accordance with paragraph 6.1.1. shall not be less than 100 Ω/Volt.] [5.3.8. Over-temperature protection The test shall be conducted in accordance with paragraph 6.2.10. During the test there shall be no evidence of; electrolyte leakage, rupture (applicable to high voltage REESS(s) only), venting (for REESS other than open-type), fire or explosion. The evidence of electrolyte leakage shall be verified by visual inspection without disassembling any part of the Tested-Device. The evidence of venting shall be verified by visual and/or audible inspection without disassembling any part of the Tested Device. For a high voltage REESS, the isolation resistance measured after the test in accordance with paragraph 6.1.1. shall not be less than 100 Ω/Volt.] Rationale for adoption of "Venting" as a pass/fail criterion in GTR-EVS Venting, as defined in 3.X, may be part of a normal operation for some battery technologies, such as e.g. for open-type batteries, or may be a signal of unintended processes taking place as e.g. in case of Li-ion battery thermal runaway. Toxic, corrosive and flammable gases can be emitted upon venting of batteries. For aqueous electrolyte batteries vented gases mainly consist of hydrogen and/or oxygen, while for non-aqueous batteries, such as e.g. Li-ion batteries, a complex mixture of chemical substances may be vented. Extensive research has shown that gases generated in and vented from Li-ion batteries typically include carbon dioxide (CO2), carbon monoxide (CO), hydrogen (H2), oxygen (O2), light C1-C5 hydrocarbons, e.g. methane and ethane, and fluorine-containing compounds such as hydrogen fluoride (HF) and fluoro-organics such as e.g. ethyl fluoride[1-6]. For 18650 cells, in average ca. 1.2 L of gas can be vented for each Ah of cell capacity [4]. Hazards associated with toxicity, corrosiveness and flammability of gases emitted from batteries are recognised in various standards and regulations. For example: ISO 6469 [7] requires that "No potentially dangerous concentration of hazardous gases and other hazardous substances shall be allowed anywhere in the driver, passenger and load compartments" and refers to the latest version of applicable National/International Standards or regulations for the maximum allowed accumulated quantity of hazardous gases and other substances. SAE J2464 [8] requires that in hazardous substances monitoring tests both electrolyte vapours and vented airborne volatiles and particulates are analysed. The release of hazardous substances shall be measured and referenced to the ERPG-2 levels [9], and to upper and lower flammability levels when mixed with air. SAE J2929 [10] states that consideration should be given to preventing the build-up of these [harmful to humans] gases in sufficient concentration to be harmful inside the passenger compartment. UL 2580 [11] defines the limits for toxic gas release for both operational and non-operational/crash level tests and lists analytical methods suitable for detection and quantification of toxic emissions. UN 38.3 [12] explicitly includes a requirement of no venting for altitude simulation, thermal test, vibration and [mechanical] shock tests. This regulation includes a no-fire requirement which addresses the issue of vented gas flammability. This regulation also requires determination of hydrogen emissions during the charge procedures of the REESS for open-type batteries, thereby addressing one of the worst-case in-use scenarios of hydrogen gas emission for this type of REESS. To avoid human harm that may occur from the electric power train, for REESS other than open-type, venting is adopted as a pass/fail criterion for the following in-use tests: vibration, thermal shock and cycling, external short circuit protection, overcharge and over-discharge protection, over-temperature protection. _______________________________________________ 1. S. Koike, M. Shikano, H. Sakaebe, H. Kobayashi, "Study of generative gas species from lithiumion battery component under abuse conditions", Abstract # 1009, Honolulu 2012, The Electrochemical Society Meeting. 2. M. Onuki, S. Kinoshita, Y. Sakata, M. Yanagidate, Y. Otake, M. Ue, M. Daguchi, J. Electrochem. Soc., 2008, 155, A794. 3. C. Mikolajczak, M.Kahn, K. White, R.T. Long, "Lithium-Ion batteries hazard and use assessment", Springer, 2011 and references therein. 4. E.P. Roth, C.J. Orendorff, "How electrolytes influence battery safety", Interface, Summer 2012, p.45. 5. W.Kong, H.Li, X.Huang, L.Chen, J.Power Sources, 2005, 142, 285. 6. A. Hammami, N. Raymond, M. Armand, Nature, 2003, 424, 635-636. 7. ISO 6469, "Electrically Propelled Road Vehicles – Safety Specifications – Part 1: On-board Rechargeable Energy Storage System (RESS)", SEP2009. 8. SAE J2464, "Electric and Hybrid Electric Vehicle Rechargeable Energy Storage System (RESS) Safety and Abuse Testing", NOV2009. 9. Information on Protective Action Criteria, including a definition of ERPG levels, is available at http://www.atlintl.com/DOE/teels/teel/search.html 10. SAE J2929, "Safety Standard for Electric and Hybrid Vehicle Propulsion Battery Systems Utilising Lithium-based Rechargeable Cells", FEB2013. 11. UL 2580, "Standard for Safety. Batteries for Use in Electric Vehicles", DEC2013. 12. UN 38.3, "Recommendations on the Transport of Dangerous Goods. Manual of Tests and Criteria", 6th edition, 2015. Proposed GTR-EVS preamble wording of underlying risk/rationale for requirements for detection and quantification of venting for tests addressing safety of REESS postcrash. At the moment venting is not adopted as a requirement for tests addressing safety of REESS post-crash. Accordingly, venting is allowed to occur unrestricted. Assessment of potential safety risks of this requires more research to evaluate whether limits for emissions are required, for which species and which technique can be used to measure these. It was not possible to research and analyse this in Phase 1. Therefore, it will be considered in Phase 2 of this Regulation.