2011 Title 24 Supermarket CASE LARGE SUPERMARKET: Simulation Assumptions Document – August 3, 2010 Air-Cooled Condenser Large Supermarket Evap-Cooled Condenser Fluid Cooler Central Distributed Central Central MAC MAD MEC MFC Distributed MFD Assumptions apply to all Large Supermarket configurations listed in the table above, unless otherwise noted. For each ECM, Baselines are defined in the “Baseline” column adjacent to ECM description in “ECM” column. Item Base Case Baseline ECM System Information Refrigerant 404A Same Same System Type MAC, MAD, MEC, MFC, MFD Same Same [Baseline ECM 3.2] Floating head pressure control Indirect systems (optional): SCT-CTRL = FIXED SCT-SETPT = 70 SCT-THROTTLE = 2 BACKFLOOD-CTRL=FIXED BACKFLOOD-SETPT = 69 Ambient-following logic SCT-CTRL = DRYBULB-RESET or WETBULB-RESET SCT-AMBIENT-DT = << optimum TD >> SCT-THROTTLE = 1 Condenser fan variable speed control None CAPACITY-CTRL = VAR-SPEEDFAN [ECM 3.2] Indirect System=ON Suction setpoint automation TEMP-CTRL = LOAD-RESET MIN-TEMP-SETPT = design suction temperature per refrigeration schedule MAX-TEMP-SETPT = design SST + 5°F Mechanical subcooling TEMP-SETPT = 50 DESIGN-SUBCOOL-T = 50 SUBCOOL-DP = 2 LIQUID-CIRCUIT = MT Group SUCTION-CIRCUIT = MT Group LED Lighting in Reach-in Glass Doors See LED Lighting Page 1 Spreadsheet Comparison LED Lighting in Open Cases See LED Lighting Spreadsheet Comparison Compressor Compressor Type MAC, MEC, MFC: Semihermetic compressors Same Same Same Same LT Scroll: ZF40KVE MT Scroll: ZB92KCE (3) Three SST Levels (1) LT Suction Group (2) MT Suction Groups No AC Rack Same Same Pressure Drop between SET and SST 2°F Same Same Compressor RGT Adjustment See representative compressor spreadsheets Same Same Fixed setpoint electronic sequencing control with on/off cycling Same [ECM 2.3] Suction setpoint automation MAD, MFD: Scroll compressors Compressor Selection MAC, MEC, MFC: LT Semi-Hermetic: 06DR316 MT Semi-Hermetic: 06DR725 MAD, MFD: Suction Groups (RGT = Return Gas Temperature) Means of compressor control TEMP-CTRL = LOAD-RESET MIN-TEMP-SETPT = design suction temperature per refrigeration schedule MAX-TEMP-SETPT = design SST + 5°F DESIGN-SST = design suction temperature per refrigeration schedule Subcooling None None [ECM 2.4] Mechanical subcooling TEMP-SETPT = 50 DESIGN-SUBCOOL-T = 50 SUBCOOL-DP = 2 LIQUID-CIRCUIT = MT Group SUCTION-CIRCUIT = MT Group Condenser Page 2 Condenser Type MAC, MAD: Air cooled Same Same Same Same 10°F TD for LT air-cooled condensers 15°F TD for MT aircooled condensers Same Same Between 20°F and 25°F TD, based on WBT: 78°F WBT: 98°F SCT 72°F WBT: 95°F SCT 68°F WBT: 93°F SCT Pick the closest TD for the ambient temperature Condenser approach: 20F Fluid cooler approach: Same method as evap condenser selection above, less 5 F. Same 140 BTU/Watt for evaporative @ 100ºF SCT & 70ºF WBT Same [ECM 1.5] Condenser specific efficiency Same [ECM 1.5] Condenser specific efficiency MEC: Evaporative cooled MFC, MFD: Fluid cooler Ambient Temperature & Condenser Approach TD Title 24 Joint Appendix JA2 0.1% for design Wet Bulb Temperature 0.1% for design Dry Bulb Temperature TBD Condenser Selection TD Air Cooled Condenser Condenser Selection TD Evaporative Cooled Condenser Condenser and Fluid Cooler Selection TD Water Cooled Condenser Condenser Specific Efficiency Air Cooled and Evaporative Cooled Condensers Water Cooled Condensers and Fluid Cooler Note: Condenser approach not included in high priority ECMs to be modeled for 9/15 Webinar. Same Note: Condenser approach not included in high priority ECMs to be modeled for 9/15 Webinar. Same Same Note: Condenser approach not included in high priority ECMs to be modeled for 9/15 Webinar. 53 BTU/Watt for aircooled @ 10ºF TD 105 BTU/Watt Fluid cooler pump is controlled at a fixed speed. Base case pump power is TBD, but not exceeding that required for the base case GPM at 30 PSID. Page 3 Condenser Fan Motor Power and Efficiency Motor power is inherent in the base case specific efficiency calculation. Same [ECM 1.5] Condenser specific efficiency Means of Condenser Control Fixed setpoint strategy [Baseline ECM 1.2] Ambient-following logic [ECM 1.2] Ambientfollowing logic BACKFLOOD-CTRL=FIXED BACKFLOOD-SETPT = 69 OVERRIDE-MIN-SCT = 70 SCT-CTRL = DRYBULB-RESET or WETBULB-RESET SCT-AMBIENT-DT = << optimum TD >> SCT-THROTTLE = 1 Means of Condenser Fan Control Air cooled: fan cycling (based on pressure) [Baseline ECM 1.3] Condenser fan variable speed control [ECM 1.3] Condenser fan variable speed control SCT-CTRL = FIXED SCT-THROTTLE = 2 CAPACITY-CTRL = CYCLE-FAN CAPACITY-CTRL = VAR-SPEEDFAN CAPACITY-CTRL = TWO-SPEEDFAN BACKFLOOD-CTRL=FIXED BACKFLOOD-SETPT = 69 OVERRIDE-MIN-SCT = 70 SCT-CTRL = DRYBULB-RESET or WETBULB-RESET SCT-AMBIENT-DT = << optimum TD >> SCT-THROTTLE = 1 Condensing Temperature Setpoint 80°F SCT Same Pressure Drop at SDT and SCT 3°F Same Same Heat Recovery (air) None Same Same Heat Recovery (domestic hot water heating) None Evap cooled: two-speed fan control SCT-SETPT = 80 BACKFLOOD-CTRL = FIXED BACKFLOOD-SETPT = 79 [ECM 1.1] Floating head pressure control SCT-CTRL = FIXED SCT-SETPT = 70 SCT-THROTTLE = 2 BACKFLOOD-CTRL=FIXED BACKFLOOD-SETPT = 69 Note: Heat recovery (air) not included in high priority ECMs to be modeled for 9/15 Webinar. Same Same Note: Heat recovery (DHW) not included in high priority ECMs to be modeled for 9/15 Webinar. Walk-ins and unit coolers Unit Cooler Sizing See Walk-in box definitions below See Walk-in box definitions below Same Unit Cooler CFM and wattage See Walk-in Box Definitions below Same [ECM 5.2] Unit cooler specific efficiency Note: Unit cooler approach not included in high priority ECMs to be modeled for 9/15 Webinar. Page 4 Fan Motor Type ECM in walk-in evaporator coils for all fan motors < 460V and < 1 hp. Otherwise, PSC fan motors. Same Same Walk-in insulation level R-25 for cooler walls, ceiling and doors R-32 for freezer walls, ceiling and doors R-28 for freezer floors Same Same Walk-ins served by System A MT Suction Group: (1) Deli Cooler, (8 x 8 x 10) ft3 Evaporator Temp: +26°F Discharge Temp: +36°F Coil Capacity @ 10°F TD: 9,440 Btuh Coil Air Flow: 1,400 cfm Fan Power: 59 W/motor Defrost Type: Off Cycle Walk-in Box Load: 5,900 Btuh (1) Wine Cooler, (11 x 11 x 10) ft3 Evaporator Temp: +26°F Discharge Temp: +36°F Coil Capacity @ 10°F TD: 14,880 Btuh Coil Air Flow: 2,100 cfm Fan Power: 59 W/motor Defrost Type: Off Cycle Walk-in Box Load: 9,260 Btuh (1) Produce Cooler, (20 x 20 x 10) ft3 Evaporator Temp: +26°F Discharge Temp: +36°F Coil Capacity @ 10°F TD: 18,720 Btuh Coil Air Flow: 2,800 cfm Fan Power: 59 W/motor Defrost Type: Off Cycle Walk-in Box Load: 21,800 Btuh MT Suction Group: (1) Bakery Retarder, (10 x 7 x 10) ft3 Evaporator Temp: +26°F Discharge Temp: +36°F Coil Capacity @ 10°F TD: 10,080 Btuh Coil Air Flow: 1,400 cfm Same Same Same Same (Walk-in Box Loads per Supermarket Tables, as noted) Walk-ins served by System B Page 5 Walk-ins served by System C Fan Power: 59 W/motor Defrost Type: Off Cycle Walk-in Box Load: 6,250 Btuh (1) Dairy Cooler, (41 x 16 x 10) ft3 Evaporator Temp: +26°F Discharge Temp: +36°F Coil Capacity @ 10°F TD: 28,440 Btuh Coil Air Flow: 3,900 cfm Fan Power: 59 W/motor Defrost Type: Off Cycle Walk-in Box Load: 35,550 Btuh (1) Meat Cooler, (15 x 36 x 10) ft3 Evaporator Temp: +26°F Discharge Temp: +36°F Coil Capacity @ 10°F TD: 24,120 Btuh Coil Air Flow: 3,250 cfm Fan Power: 59 W/motor Defrost Type: Off Cycle Walk-in Box Load: 30,150 Btuh (1) Meat Holding, (13 x 7 x 10) ft3 Evaporator Temp: +26°F Discharge Temp: +36°F Coil Capacity @ 10°F TD: 12,000 Btuh Coil Air Flow: 1,300 cfm Fan Power: 59 W/motor Defrost Type: Off Cycle Walk-in Box Load: 7,550 Btuh LT Suction Group: (1) Bakery Freezer, (18 x 18 x 10) ft3 Evaporator Temp: -15°F Discharge Temp: -5°F Coil Capacity @ 10°F TD: 16,240 Btuh Coil Air Flow: 2,600 cfm Fan Power: 59 W/motor Defrost Type: Hot Gas Walk-in Box Load: 20,300 Btuh (1) Deli Freezer, (12 x 8 x 10) ft3 Evaporator Temp: -15°F Same Same Page 6 Discharge Temp: -5°F Coil Capacity @ 10°F TD: 10,320 Btuh Coil Air Flow: 1,950 cfm Fan Power: 59 W/motor Defrost Type: Hot Gas Walk-in Box Load: 8,600 Btuh (1) Grocery Freezer, (36 x 15 x 10) ft3 Evaporator Temp: -15°F Discharge Temp: -5°F Coil Capacity @ 10°F TD: 24,200 Btuh Coil Air Flow: 3,900 cfm Fan Power: 59 W/motor Defrost Type: Hot Gas Walk-in Box Load: 30,250 Btuh Walk-ins served by System D None Same Same Fan Motor Power Fan motor input wattage. See walk-in box definitions above. Continuous operation with no VFD Same Same Same [ECM 5.3] Variable speed fan control Fan Control MIN-FLOW-SCH = 0.7 for 22 hrs & 1.0 for 2 hrs FAN-CONTROL = FAN-EIR-FPLR FAN-EIR-FPLR = New-EIR-fPLR New-EIR-fPLR = CURVE-FIT TYPE= RATIO-FRATIO ORDER-OF-FIT= CUBIC INPUT-TYPE= COEFFICIENTS MIN-INPUT-1 = 0 MAX-INPUT-1 = 1.01 COEFFICIENTS= (0.001,0.0444,0.3634,0.6808) FAN-CONTROL = FAN-EIR-FPLR FAN-EIR-FPLR = no_unload_fplr [Baseline ECM 5.4] Liquid-suction heat exchangers [ECM 5.4] Liquid-suction heat exchangers Superheat Gain in LSHX: XX°F (also XX°F RGT) Subcooling Gain in LSHX: XX°F TBD Liquid-suction heat exchangers (direct refrigerant) None Leaving Gas Temperature LT: 30°F MT: 20°F Same Same Defrost Assumptions Defrost Load: 70% of design load Same Same BACKFLOOD-CTRL=FIXED BACKFLOOD-SETPT = 69 OVERRIDE-MIN-SCT = 70 SCT-CTRL = DRYBULB-RESET or WETBULB-RESET SCT-AMBIENT-DT = << optimum TD >> SCT-THROTTLE = 1 Page 7 Defrost Effectiveness: 15% Quantity of Defrosts per Day: 4 Defrost Duration: 15 minutes Display Case Case fan motor type See display case definitions below Same Same Case light wattage Fixture efficiency – standard offer published by manufacturer. Same [ECM 4.2] LED Lighting in Reach-in Glass Doors See LED Lighting Spreadsheet Comparison [ECM 4.3] LED Lighting in Open Cases See LED Lighting Spreadsheet Comparison Case lighting configuration assumptions For multi-deck meat and deli cases: 2 row canopy lights + all shelves lighted (if available) Same Same For multi-deck dairy, beverage and produce cases: 2 row canopy lights + no lighted shelves Display Case Reach-in Glass Door antisweat heater type & wattage Low wattage doors Same Same Display Case Reach-in Glass Door antisweat heater control on glass door cases None Same Same Night curtains (applicable only to open cases) None Indirect Cooling for None Note: Reach-in door antisweat heater control not included in high priority ECMs to be modeled for 9/15 Webinar. Same Same Same Same INF-SCH = SCHEDULE TYPE = FRACTION THRU DEC 31 (ALL) (1,24) (0.80,0.80,0.80,0.80,0.80,0.80, 0.80,0.80,0.80,0.80,0.80,0.85, 0.85,0.90,0.90,0.95,0.95,0.95, 0.90,0.90,0.80,0.80,0.80,0.80) Note: Display Case Page 8 Display Cases Defrost Type Defrost Control Indirect Cooling not included in high priority ECMs to be modeled for 9/15 Webinar. Electric, Off Cycle or Hot Gas – See refrigeration schedule Same Time initiated, per manufacturers frequency. Same Same Note: Defrost method not included in high priority ECMs to be modeled for 9/15 Webinar. Same Note: Demand Defrost not included in high priority ECMs to be modeled for 9/15 Webinar. Demand Defrost established as a REACH CODE? Temperature terminated on LT electric defrost only [Baseline ECM 4.8] Liquid-suction heat exchangers [ECM 4.8] Liquid-suction heat exchangers Superheat Gain in LSHX: XX°F (also XX°F RGT) Subcooling Gain in LSHX: XX°F TBD Liquid-suction heat exchangers (direct refrigerant) None Electronic expansion valves/case controllers None Leaving Gas Temperature LT: 30°F MT: 20°F Same Same Display Case served by System A MT Suction Group: (1) Sushi Bar, MD Case Case Length: 3 ft Evaporator Temp: +20°F Discharge Temp: +28°F Fan Power: 10.3 Watts/ft No. Fans: 1 fan/12 ft Canopy Light Watts: 0 Shelf Light Watts: 0 No. Canopy Lights: 0 No. Shelves w/ Lights: 0 Defrost Type: Off Cycle Defrost Freq x Duration: Same [ECM 4.2] LED Lighting in Reach-in Glass Doors BACKFLOOD-CTRL=FIXED BACKFLOOD-SETPT = 69 OVERRIDE-MIN-SCT = 70 SCT-CTRL = DRYBULB-RESET or WETBULB-RESET SCT-AMBIENT-DT = << optimum TD >> SCT-THROTTLE = 1 Same Same Note: Electronic expansion valves/case controllers not included in high priority ECMs to be modeled for 9/15 Webinar. See LED Lighting Spreadsheet Comparison [ECM 4.3] LED Lighting in Open Cases See LED Lighting Spreadsheet Comparison Page 9 4 x 60 mins. (1) Sushi, MD Case Case Length: 8 ft Evaporator Temp: +20°F Discharge Temp: +28°F Fan Power: 17.2 Watts/ft No. Fans: 1 fan/12 ft Canopy Light W/ft: 19.6 Shelf Light Watts: 0 No. Canopy Lights: 1 No. Shelves w/ Lights: 0 Defrost Type: Off Cycle Defrost Freq x Duration: 4 x 40 mins. (1) Sandwich Prep, MD Case Case Length: 10 ft Evaporator Temp: +20°F Discharge Temp: +30°F Fan Power: 3.71 Watts/ft No. Fans: 1 fan/12 ft Canopy Light W/ft: 8 Shelf Light Watts: 0 No. Canopy Lights: 1 No. Shelves w/ Lights: 0 Defrost Type: Off Cycle Defrost Freq x Duration: 4 x 60 mins. Case Length: 8 ft Evaporator Temp: +20°F Discharge Temp: +30°F Fan Power: 8.25 Watts/ft No. Fans: 1 fan/12 ft Canopy Light W/ft: 24.8 Shelf Light Watts: 0 No. Canopy Lights: 1 No. Shelves w/ Lights: 0 Defrost Type: Off Cycle Defrost Freq x Duration: 3 x 40 mins. Case Length: 28 ft Evaporator Temperature: +20°F Discharge Temp: +35°F Fan Power: 13.75 W/ft No. Fans: 9 fans/12 ft Canopy Light W/ft: 14.3 Shelf Light W/ft: 7.2 No. Canopy Lights: 2 No. Shelves w/ Lights: 2 Defrost Type: Off Cycle Page 10 Defrost Freq x Duration: 3 x 90 mins. Case Length: 12 ft Evaporator Temp: +20°F Discharge Temp: +30°F Fan Power: 17.25 W/ft No. Fans: 3 fans/12 ft Canopy + Shelf Light W/ft: 33 No. Canopy Lights: 2 No. Shelves w/ Lights: 3 Defrost Type: Off Cycle Defrost Freq x Duration: 4 x 20 mins. Case Length: 26 ft Evaporator Temp: +20°F Discharge Temp: +28°F Fan Power: 1 Watt/ft No. Fans: 3 fans/12 ft Canopy Light Watts: 0 Shelf Light Watts: 0 No. Canopy Lights: 0 No. Shelves w/ Lights: 0 Defrost Type: Off Cycle Defrost Freq x Duration: 4 x 30 mins. Case Length: 12 ft Evaporator Temp: +20°F Discharge Temp: +26°F Fan Power: 15 Watt/ft No. Fans: 10 fans/12 ft Canopy Light Watts: 0 Shelf Light Watts: 7 W/ft No. Canopy Lights: None No. Shelves w/ Lights: 1 Defrost Type: Off Cycle Defrost Freq x Duration: 6 x 20 mins. Case Length: 32 ft Evaporator Temp: +26°F Discharge Temp: +30°F Fan Power: 4.5 Watt/ft No. Fans: 3 fans/12 ft Canopy Light W/ft: 14.2 Shelf Light W/ft: 7.1 No. Canopy Lights: 2 No. Shelves w/ Lights: 6 Defrost Type: Off Cycle Page 11 Defrost Freq x Duration: 3 x 30 mins. Case Length: 56 ft Evaporator Temp: +26°F Discharge Temp: +30°F Fan Power: 4.5 Watt/ft No. Fans: 3 fans/12 ft Canopy Light W/ft: 14.2 Shelf Light Watts: None No. Canopy Lights: 2 No. Shelves w/ Lights: 0 Defrost Type: Off Cycle Defrost Freq x Duration: 3 x 30 mins. Case Length: 16 ft Evaporator Temp: +21°F Discharge Temp: +29°F Fan Power: 4.5 Watt/ft No. Fans: 3 fans/12 ft Canopy Light W/ft: 15.3 Shelf Light Watts: 0 No. Canopy Lights: 2 No. Shelves w/ Lights: 0 Defrost Type: Off Cycle Defrost Freq x Duration: 4 x 40 mins. Display Case served by System B Same Same Case Length: 16 ft Evaporator Temp: +20°F Discharge Temp: +25°F Fan Power: 24.1 Watt/ft No. Fans: 1 fans/12 ft Canopy + Shelf Light W/ft: 19.3 Canopy Light Watts: ? Shelf Light Watts: ? No. Canopy Lights: ? No. Shelves w/ Lights: ? Defrost Type: Off Cycle Defrost Freq x Duration: 4 x 60 mins. Case Length: 5 ft Evaporator Temp: +40°F Discharge Temp: +45°F Fan Power: 3.67 Watt/ft No. Fans: 1 fans/12 ft Canopy + Shelf Light W/ft: 19.3 Canopy Light Watts: ? Page 12 Shelf Light Watts: ? No. Canopy Lights: ? No. Shelves w/ Lights: ? Defrost Type: Off Cycle Defrost Freq x Duration: 4 x 60 mins. Case Length: 5 ft Evaporator Temp: +20°F Discharge Temp: +25°F Fan Power: 1.83 Watt/ft No. Fans: 1 fans/12 ft Canopy + Shelf Light W/ft: 2.8 Canopy Light Watts: ? Shelf Light Watts: ? No. Canopy Lights: ? No. Shelves w/ Lights: ? Defrost Type: Off Cycle Defrost Freq x Duration: 4 x 60 mins. Evaporator Temp: +20°F Discharge Temp: +27°F Fan Power: 15 Watt/ft No. Fans: 10 fans/12 ft Canopy Light W/ft: 13.7 Shelf Light W/ft: 16.4 No. Canopy Lights: 1 No. Shelves w/ Lights: 1 Defrost Type: Off Cycle Defrost Freq x Duration: 6 x 20 mins. Evaporator Temp: +28°F Discharge Temp: +32°F Fan Power: 4.5 Watt/ft No. Fans: 3 fans/12 ft Canopy Light W/ft: 14.2 Shelf Light Watts: 0 No. Canopy Lights: 2 No. Shelves w/ Lights: 0 Defrost Type: Off Cycle Defrost Freq x Duration: 3 x 30 mins. Case Length: 70 ft Evaporator Temp: +26°F Discharge Temp: +30°F Fan Power: 4.5 Watt/ft No. Fans: 3 fans/12 ft Canopy Light W/ft: 14.2 Page 13 Shelf Light Watts: None No. Canopy Lights: 2 No. Shelves w/ Lights: 0 Defrost Type: Off Cycle Defrost Freq x Duration: 3 x 30 mins. Case Length: 6 ft Evaporator Temp: +26°F Discharge Temp: +30°F Fan Power: 4.5 Watt/ft No. Fans: 3 fans/12 ft Canopy Light W/ft: 14.2 Shelf Light Watts: 0 No. Canopy Lights: 2 No. Shelves w/ Lights: 0 Defrost Type: Off Cycle Defrost Freq x Duration: 3 x 30 mins. Case Length: 8 ft Evaporator Temp: +18°F Discharge Temp: +25°F Fan Power: 4.5 Watt/ft No. Fans: 3 fans/12 ft Canopy Light W/ft: 14.2 Shelf Light Watts: 0 No. Canopy Lights: 2 No. Shelves w/ Lights: 0 Defrost Type: Off Cycle Defrost Freq x Duration: 4 x 40 mins. Case Length: 12 ft Evaporator Temp: +20°F Discharge Temp: +28°F Fan Power: 5.81 Watt/ft No. Fans: 9 fans/12 ft Canopy Light Watts: 0 Shelf Light Watts: 0 No. Canopy Lights: 0 No. Shelves w/ Lights: 0 Defrost Type: Off Cycle Defrost Freq x Duration: 3 x 46 mins. Case Length: 12 ft Evaporator Temp: +22°F Discharge Temp: +27°F Fan Power: 11.33 W/ft No. Fans: 6 fans/12 ft Canopy Light W/ft: 7.13 Page 14 Display Case served by System C Ledge Light W/ft: 7.2 Rail Light W/ft: 7.2 No. Canopy Lights: 2 No. Ledges w/ Lights: 1 No. Rails w/ Lights: 1 Defrost Type: Off Cycle Defrost Freq x Duration: 1 x 90 mins. LT Suction Group: Same Same Case Length: 58 drs Evaporator Temp: -17°F Discharge Temp: -12°F Fan Power: 7.5 Watt/dr No. Fans: 5 fans/5 drs Std Vertical Light W/dr: 72 Defrost Type: Hot Gas Defrost Freq x Duration: 1 x 20 mins. Case Length: 59 drs Evaporator Temp: -9°F Discharge Temp: -5°F Fan Power: 7.5 Watt/dr No. Fans: 5 fans/5 drs Std Vertical Light W/dr: 72 Defrost Type: Hot Gas Defrost Freq x Duration: 1 x 20 mins. Display Case served by System D None Same Same Point of Sale (POS) Boxes with Reach-in (RI) Glass Doors None Same Same POS Box Reach-in Glass Door antisweat heater type & wattage N/A, since no POS Boxes in Base Case Same Same Same Same Same Same Operation, Occupancy and Schedules Facility size 60,700 ft2 (gross area) 57,200 ft2 (conditioned area) Main Sales Interior Spaces 28 ft Page 15 Height People Heat Gain (Sensible/Late nt) 600 Btu/hr/person Same Same People Occupancy (Main Sales Area) 200 ft2/person Same Same People Occupancy (Employee Areas) 100 ft2/person Same Same Schedules See schedules spreadsheet ? W/sf Same Same Same Same Packaged Rooftop Units with EER per Title 24 standards Number of Packaged Rooftop Units: 8 (1) Main Air Handler Unit for Main Sales area with supply fan motor efficiency per Title 24 Always On Same Same Same Same Same Same Two fixed setpoints No night setpoint adjustment 74°F Same Same Same Same Main Sales HVAC Heating Setpoint 70°F Same Same Ventilation Control Always On Same Same Infiltration Load CFM = ? SBD: Engineering evaluation from exhaust quantity, store size, orientation, etc. Same Same Equipment Plug Load Building HVAC Packaged rooftop units (RTU) Main Air Handling Unit Fan Operation Temperature Control Main Sales HVAC Cooling Setpoint Page 16 Envelope & Lighting Exterior Roof Construction U-factor based on Title 24 – Table 143-A Prescriptive Envelope Criteria for Roofs Same Same Same Same For Sacramento (CZ12), U-factor = 0.039 Exterior Wall Construction U-factor based on Title 24 – Table 143-A Prescriptive Envelope Criteria for Walls For Sacramento (CZ12), U-factor = ? Roof Absorptivity AGED Reflectance = 0.55 (Title 24 – Table 143-A) Same Same Skylights Per Title 24 – Sec 143 (c), approximately 1.65% (3.3% minimum skylight area to skylit ratio * 50% of floor area) of sales area is covered by skylights. Same Same Skylight Characteristics Skylight Type: Glass, curb U-factor: 1.11 SHGC: 0.46 Visible Transmittance: 0.552 Same Same Daylighting Controls Power consumption reduction of lighting by at least 2/3 in response to available daylight. Same Same (three step control: 100%, 67%, 33% & 0%) Light setpoint: 75 fc Lighting Power Density (except for Walk-in Coolers & Freezers) 1.5 Watts/ ft2 (Complete Building Method) Same Same Lighting Power Density (Walkin Coolers & Freezers) 0.7 Watts/ ft2 Same Same Lighting Control (Main 24 hr store: Always ON 100% Same Same Page 17 Sales) Same Same Lighting Control (Stockroom) Manual Lights ON 100% from 8am – 5pm Lights ON 50% from 5pm – 8am Manual Lights ON 100% 24 hours/day Same Same Lighting Control (Display Cases) Manual Lights ON 100% 24 hours/day Same [ECM X.X] Display Case Lighting Control Lighting Control (Walkin Boxes) Manual Lights ON 80% 24 hours/day Same Lights OFF during nonoperating hours Same Occupancy Sensors in Walk-in Coolers & Freezers None Same Same Occupancy Sensors in Individual Rooms ? Same Same Lighting Control (Offices) Page 18