Introducing GAC’s New Line of Intelligent Generator Set Controllers The InteliGen • Stand-By, Prime Mover (single and multiple set), and Parralel to Utility (single and multiple set) Applications • Features: 128 x 64 LCD 9 / 9 Discrete Inputs and Outputs (Configurable) Expandable to 21 / 21 3 Analog Inputs (Fuel Level, Coolant Temp., Oil Press.) Expandable to 7 and 1 Analog Output Speed Measurement (Mag Pick-Up) 3 Phase Generator / Utility Voltage Measurement 3 Phase Generator Current Measurement 1 CT Input for Utility Measurement or Earth Fault Protection RS232 for Direct Communication Meets NFPA110 (w/ Annunciator Module iGL-RA15) Remote Communication (Analog, Internet, and GSM) InteliGen Connections 3 Phase Generator Voltage and Current Connection for IOM / COM Module Mag. Pick-up 3 Analog Inputs (Oil, Temp., Fuel.) Utility Current 2 Relay Outputs (Starter, Fuel Solenoid) 3 Phase Utility Voltage 9 Configurable Discrete Inputs Connection for Power Modules Direct PC or Modem Connection 7 Config. Outputs 12 or 24 V DC InteliGen’s Modules • Power Control Modules: PCM and PCLSM (with Load Sharing) • AVR control (needs 18 V AC power supply) • Communications • Expandable I / O • Modem Support (multiple set applications) Power Control Modules Shielded Analog Load Sharing Line (PCLSM only) Governor Control Output AVRi Output Mounts Directly to Back of InteliGen 4 Discrete Inputs 12 or 24 V DC 4 Discrete Outputs AVRi Module 18 V AC Power Supply Output Level Adjustment (turn pot) Output for AVR Control Input from PCLSM DIN Rail Mounting Communication Module NAC H MOC L MOC L M O C- Gi N OI S N E T X E ELUD O M • Used for Multiple Set Applications • Communications Between Sets • Mount: Back of InteliGen • Up to 32 Sets • Use one Modem (w/iG-MU) • RS232 port for IOM NAC H IOM / PTM Module A N A L O G IN P U T S A N A L O G O U T I G -C U IG- IOM S e lN o ria . RS232 for Direct PC Connection P O WE R 8 7 6 5 4 3 2 1 B IN A R Y O U T P U T S 1 Analog Output A I4 COM B I8 B I7 B I6 B I5 B IN A R Y IN P U T S RS 2 3 2 RS232 Connection to InteliGen B I4 B I3 B I2 B I1 9 Discrete Inputs w/ 4 Analog Inputs* Active LED BO BO BO BO BO BO BO BO 8 -3 6 V D C 9 Discrete Outputs w/ Active LED DIN Rail Mounting 12 or 24 V DC w/ Power LED InteliMains: InteliGen With Special Software • Mains (= Utility) Circuit Breaker Control –Reverse Synchronization –Vector surge protection (locally required) • Power Management - Engine Usage Optimization –Number of running engines: Dependent on required load –Engine starting order: Dependent on running hours • Import/Export Control Parallel To Utility & Other Gen Set’s + iG-COM + iG-PCLSM iG-COM G iG-PCLSM + iG-COM + iG-PCLSM G iG-COM InteliMains iG-PCLSM Controller InteliGen’s User Friendly Operating Setpoints Software • Free •User Friendly • PC Format History Values Value Screen All Metered Values in Real Time. Metering Screen Selection History • Every Action Logged • All Values Associated w/ that Action • Up to 177 events (FIFO) Controller • Same as Keypad • Essential Metering • Alarm List • Change any Setpoint • Current Value • Range Setpoints Value Screen Selection Acceptable Range for Parameter Customizable Software • Parameters Nominal RPM 80 300 • Multilingual Texts Overspeed Überdrehzahl Sobrevelocidad • Units °C F; kPa bar psi • Controller Operating Mode SPM SSB SPtM MINT MEXT • Text Water temp Coolant temp Communications Local connection to the Control System Modem connection to remote monitoring* SMS (Mobile phones) connection* Internet connection* Controller Screens • Analog Meters • Bar Graphs • Numeric Values • Controller Screens Allow for Similar Interface as WinEdit Software MAINS: 230 228 233V 50.0Hz GENERATOR: 1517RPM 221 223 220V 50.6Hz 872 896 932A 0.98L 183 194 208kW 118kVAr Running in Island Water Temp Oil Pressure Fuel level 91°C 5.1bar 75% Battery voltage 25.2V Setpoint Adjustment • Adjustable via iG Keypad • Three Level Password Protection PARAMETERS MF-Start Delay Start Attempts Mains OK-Delay Cooling time 3s 5 10s 30s History Screens • History Events Can be Viewed From iG Screens as well as WinEdit • Viewed on Multiple Screens -15 FINISHED HOUR 07:00:00 16.10. -16 GCB CLOSED-ISLAND 06:23:53 16.10. -17 ENGINE START 06:23:49 16.10. -18 MF-MCB OPENED 06:23:44 16.10. 85kW 1503RPM 0.81L 88C 6.1bar 24.9V 84% 50kW 1495RPM 0.72L 25C 5.3bar 24.7V 87% 0kW 0RPM 22C 0.0bar 25.8V 87% 0kW ORPM 22C 0.0bar 25.8V 87% M 0 0 0V G233 227 229V M 0 0 0V G230 228 223V M 0 0 0V G 0 0 0V M190 195 201V G 0 0 0V 121 125 124A 62kVAr 27 29 29kW 72 73 71A 48kVAr 17 18 16kW 0 0 0A 0 0 0kW 0 0 0A 0 0 0kW 0.0Hz 50.1Hz 0.0Hz 49.8Hz 0.0Hz 0.0Hz 48.7Hz 0.0Hz Protection Handling • Adjustable Delay Settings • Five Protective Actions – Warning – Slow stop – Shut-down – Unloading – History Record • Reset Function (Horn + Flashing Light) Protections • Generator / Utility Over / Under Voltage and Frequency • Voltage and Current Asymmetry • OverCurrent • OverLoad • Excitation Failure • Earth Fault • Oil Pressure (two level: warning, shutdown) • Coolant Temp. (three level: low temp warning, high temp warning, and high temp shutdown) Fuel Level (two level: warning, shutdown) •… Summary The InteliGen Offers the Right Solution for the Application. Never Pay for Unneeded Features. GAC Leaves it up to You to Make the Intelligent Choice!!