Medium and Low Voltage Grounding Methods August 20, 2010 System Grounding Establish a voltage relationship between the system neutral and ground. •Overvoltage protection for system component insulation •Controlled single-phase-toground fault current magnitude Establish a voltage relationship between energized phase conductors and ground. The ASSET Company August 20, 2010 Equipment Grounding Establish a consistent reference plane for all system components. •Personnel safety •Optimum single-line-toground fault current distribution •Safe conduction of lightning discharge currents •a.k.a. bonding The ASSET Company August 20, 2010 The ASSET Company lg Human Physiological Response: 1 ma – threshold of sensation 6-9 ma “let go” currents 9-25 ma – muscular contraction 60-100 ma – ventricular fibrillation Body resistance: 5000 ohms or higher Cable Sheath Perceptable gradient voltage: 50 volts & above Harmful gradients: 375 volts and above Neutral Wire Water Pipes Building Steel Z Controlling factors o Magnitude of Potential Gradientsmagnitude of ground fault current phase-neutral voltage complexity of return path o Duration of Potential Gradientsprotective device settings fuse, relay, & breaker operation August 20, 2010 The ASSET Company Ig Distribution of Ig: Kaufmann’s work showed that 90-95% of the fault current will return through the cable sheath and/or neutral wire Ig = I C + I N + I P + I S Example: Cable Sheath Neutral Wire Water Pipes Building Steel Z IC IN IP IS Ig = 20000 A IS = 0.05 x 20000 = 1000 A For Vs > 100 V, Z > 0.1 Ohms Power cable- ground shield at both ends to help equalize electric potential along cable length, but be mindful of magnitude and duration Communication cable- do not ground communication cable at both ends to avoid circulating current that would act as noise August 20, 2010 The ASSET Company Ig Cable Sheath Neutral Wire Water Pipes Building Steel Z IC IN IP IS Conclusions: Ineffective grounding at any voltage sets the stage for personnel injury or death. Ineffective grounding at higher voltages can set the stage for potential gradient shocks which are severe enough to distract personnel in the workspace The likelihood of these “distracting gradients” is insignificant at low voltages Low voltage systems can be solidly grounded without undue concern for “distracting” potential gradients. August 20, 2010 The ASSET Company s g System Neutral Ground- an Iintentional electrical connection between the neutral of Ineffective grounding at any voltage sets the the power system and ground stage for personnel injury or death. Grounded System- a system in which one conductor, usually the neutral, is intentionally connected to ground. Effective grounding at higher voltages can set Ungrounded System- a system in which none the electrical conductors theof stage for potential gradientisshocks which intentionally connected to ground are severe enough to distract personnel in the IC distributedworkspace Note: There is an inherent Cable Sheath capacitance between each conductorThe likelihood of these “distracting gradients” is s s and ground. Hence, an IN“ungrounded insignificant at low voltages system” really capacitively grounded Neutral isWire Low voltage systems can be solidly grounded without unduebetween concernthe for neutral “distracting” Solidly Grounded Neutral- a direct electrical connection and Water Pipes potential gradients. ground with no added impedance IS an electrical connection in which a resistor is ResistanceBuilding Grounded NeutralSteel inserted between neutral and ground Reactance Grounded Neutral- an electrical connection in which an inductive reactance is inserted between neutral and ground Z Capacitance Grounded Neutral- an electrical connection in which a capacitor is inserted between neutral and ground IP August 20, 2010 The ASSET Company Effective Grounding- grounding such that the steady-state operating voltage on the healthy phases of the power system during a single-line-to-ground fault will not exceed 140% of the open-circuit line-to-neutral RMS voltage. and Both must be met “Since power sources are fewer in number than loads and are less likely to be disconnected, they are preferred as grounding points.” - Industrial Power Systems Handbook General Electric Company © Donald Beeman, editor August 20, 2010 The ASSET Company Forms of Neutral Grounding -G Fault Magnitude Transient Overvoltages Arrester Applications (% of VL-L) System Protection Selectivity Comments Ungrounded 0 Very high 100% None Not Recommended Solidly I3 < 140% 80% Generally Good Common at high voltages and low voltages Low Resistance 100 – 1200 A Not Excessive 100% Generally Good Common at medium voltages High Resistance 2 – 10 A Not Excessive 100% Requires Special Equipment Alarm application for continuity must trip >5kV Reactive < I3 > 0.125 I3 Not Excessive 100% Generally Good Special case – rarely need Resonant 0 Not Excessive 100% Special Treatment Special case – very rarely need Capacitive I3 High 100% Generally Good Special case – very rarely need August 20, 2010 The ASSET Company or Ungrounded or Solidly Grounded August 20, 2010 The ASSET Company August 20, 2010 The ASSET Company Low Resistance XL Reactance High Low High Resistance Ground R August 20, 2010 The ASSET Company Resonant Neutral Grounding A A B B C C Capacitive Neutral Grounding August 20, 2010 The ASSET Company B A B C 400 A 10 sec R A B 400 A 10 sec C R C B B A A 7970 7970 C VR=0 C Effectively Grounded VR = 7970 Volts If V = IR, and you wish to limit I to 400 Amps, 7970 = 400 R R = 19.9 A Resistor must be insulated at One terminal for 8000 V and to pass 400 Amps for 10 seconds without damage B 7970 VR C August 20, 2010 The ASSET Company For Low Resistance Resistors ANG80-4 13800 8000 400 20 46 60 76 900 Neutral Grounding Resistor IBM Substation August 20, 2010 The ASSET Company Let’s limit ground fault current to 10 amps 7970:240 V Grounding Transformer Impedance Transformer Effectively grounded under normal conditions August 20, 2010 If IG is 10 amps, then the power through the transformer is: The ASSET Company Power in the secondary is the same: Transformer spec : 75 kVA or 100 kVA 7970 : 120 V Resistor spec: 0.723 Rated for 240 VAC operation for 10 seconds IR IG IG August 20, 2010 The ASSET Company - Low voltage or 5 kV process plant distribution - Delta winding transformers - Generators August 20, 2010 The ASSET Company Scott-T Connection 1 3 Zig-Zag H3 2 3 H2, 2 -Small, lightweight -Economical -Off-the-shelf in common ratings -Not practical for unusual applications (i.e. voltage, frequency, current levels) -Limited to Low-R applications X2 Y - Transformer X3 -Standard transformer X1 -Applications are readily H1,1 field-designed H3,3 -Can be used for any grounding mode -Grounding resistor can be inside delta if single phase units are used in Hi-R scheme -Offers option for redundant backup protection X2 H2 -Custom designed X1 -Can fit any application X3 1 2 H1 -Can be designed to provide full reactive limitation with no external impedance -Can be used for effectively grounded system Potential Transformers X2 X2 H2, 2 X3 -Usually required for metering -Economical -Thermal ratings suitable for X1 H1,1 H3,3 -highly restricted schemes only -Application may not provide desired limitation of transient overvoltages because the grounded wye winding is high impedance August 20, 2010 The ASSET Company 13800 V 13800 V This wye-delta transformer connection doesn’t limit fault current, except the winding impedance of the grounding transformer. August 20, 2010 The ASSET Company 13800 V 13800 V Low resistance ground fault limiting – same type calculations as before. August 20, 2010 The ASSET Company Legend AM- Ammeter CPB- Control Power Breaker CR- Main Contactor CT- Current Transformer HR- Horn Relay HRX- Auxiliary Relay MR- Meter Relay PR- Pulsing Relay PT- Potential Transformer R3- Fault Time Delay R4- Pulsing Adjustment TR- Timing Relay UV- Undervoltage August 20, 2010 The ASSET Company Placing a Resistor in the transformer secondary will limit the primary ground fault current. August 20, 2010 The ASSET Company B H2 X4 X2 R= 0.106 A X1 X6 X5 H1 H0 H3 C X3 Transformer ratio is 23900 GRY – 120 V delta. This is 13800 V to ground on the primary, and is the voltage on each winding. The secondary voltage of 120 V is the voltage across each winding. August 20, 2010 V=0 120 13800 The ASSET Company Under non-faulted balanced system conditions, the voltage at the corner delta = 0 August 20, 2010 The ASSET Company 13800 When one phase suffers a bolted fault, a phase for instance, the voltage vectors change: B C The resulting voltage at the delta corner rises to 208 V. For a 0.106 Resistor with 208 V across it, the current through it is 1963 Amps. (The resistor is rated 208 V, 1960 Amps, 10 sec.) Ours is actually a 13800 V L-L system: August 20, 2010 The ASSET Company 69.3 V 7970 B C The resulting voltage across the resistor is 120 V, and the 0.106 resistor has 1,132 Amps through it. August 20, 2010 The ASSET Company 69.3 V 7970 B C This system is a high impedance grounding system that limits current to 10 Amps. The resulting voltage across the resistor is 120 V, and the 0.106 resistor has 1,332 Amps through it. August 20, 2010 The ASSET Company The relay settings for the job were: 300 Amp pickup on the secondary side, which equates to 2.6 Amp primary. 50 V setting on the 59 G relay is equal to Voltage element is much more sensitive than current element A voltage element, looking at voltage across the resistor, and a current element, looking at current through the resistor, are used in conjunction for redundant ground fault detection. August 20, 2010 The ASSET Company High Voltage Bus •Normal central station practice – no generator breaker •GSU neutral not required on generator side •Saves cost of startup transformer •Availability of suitable breakers •GSU neutral grounding required on generator side August 20, 2010 The ASSET Company Low Voltage (< 1000 volts) Medium Voltage (through 15kV) High Voltage (> 15kV) 1. Solid Grounding 2. High Resistance 1. Low resistance grounding 2. High resistance grounding 3. Effective grounding 1. Effective grounding (at the source)