Head of Wall - Firestopping Firestopping and Fireproofing in Head of Wall Assemblies Fireproofing material is sometimes removed to facilitate installation of steel tracks for gypsum walls. The removed fireproofing material results in a thermal short or unprotected area that could result in a fireproofing failure. 0 Head of Wall - Firestopping Firestopping and Fireproofing in Head of Wall Assemblies Third party testing has shown the potential down falls of removing fireproofing materials to facilitate gypsum wall assemblies Thermocouple indicated an unprotected beam would reach the limiting temperature for the structural member. Gypsum boards on one side of beam do not provide adequate fire protection for the beam. 1 Head of Wall - Firestopping Firestopping and Fireproofing in Head of Wall Assemblies A couple potential solutions are to use Z-Clips prior to fireproofing the beam or filling the track with the same thickness of fireproofing that is applied to the beam. 2