MVWG Report to TSS January 2014 Stephanie Lu, MVWG Chair Seattle City Light Recent Meetings / Workshops REMTF Nov 4-5, 2013 Webinar Nov 5, 2013 MVWG Nov 5-6, 2013 LMTF Nov 7, 2013 Generator Modeling Workshop Nov 7-8, 2013 MVWG Items for TSS Approval Updated Phase 2 Wind Type 3 Model Specifications Document Phase 2 Wind Summary Specifications Document Updates to the Approved Dynamics Model List [MSRATF] Distance Relay Model Specifications [MSRATF] Directional Overcurrent Relay Model Specifications (for the addition of the directional and load encroachment elements to overcurrent relays) Phase 2 Wind Approval Items Updated Phase 2 Wind Type 3 Model Specifications Document Phase 2 Wind Summary Specifications Document To formally approve the document with the changes previously discussed and approved To include all four wind types in one document for easier reference Motion: Approve the Phase 2 WT3 Model Specifications Motion: Approve the Phase 2 Wind Model Specifications Summary Approved Dynamics Model List MVWG approved the following changes to the Approved Dynamic Models List Add hydro governor model h6b Add equation-based overcurrent relay TIOCRS PSSE model for PDCI updated from “new” to “pdcnsu” and “pdcsnu” Motion: Approve the Approved Dynamics Model List January 2014 MVWG Activities Overview Load Modeling System Model Validation Generator Modeling, Testing, and Validation Renewable Energy Modeling HVDC Modeling Other items: SVSMO3 Modeling, NERC Updates, WECC Project Updates, RAS/Relay Modeling, Program Updates Next Meetings and Workshops Load Modeling Load Modeling – Composite Load Model Data Tools Load Model Data Tool (LMDT4A) is available in the Composite Load Model Folder on the TSS Base Cases website A stand-alone load model data tool developed by PNNL can output PSLF dyd and PSSE dyr formats Publicly website available on the WECC TSS Base Cases Load Modeling – Composite Load Model Motor Protection IEEE PES T&D Conference accepted the motor protection paper “Voltage Sag and Recovery Influence for Modeling Motor Loads”, to be presented in Chicago April 2014 Confirmed that that assumptions used in the cmpldw for protection parameters are a good starting point Load Modeling – Voltage Dip Criteria WECC-0100 project to develop a guideline for items remaining from RBP and other needs for TPL-001-4, including acceptable voltage response MVWG will continue to support the WECC-0100 project regarding the transient voltage performance criteria Significant amount of system impact studies are required before one can make an informed decision on how to proceed Load Modeling – CMPLDW Phase 2 Work SCE has PQube data recordings for validation with and without FIDVR, more analysis to be performed Motorc dynamic model is to be cross-validated with LD1PAC performance model Studies show that 3-phase faults with normal clearing (Category B) performed worse than 1-phase faults with delayed clearing (Category C) because more air conditioner motors would stall PNNL is working on an improved version of the Load Composition Model tool, more validation work is in progress Additional data would help System Model Validation System Model Validation WECC staff has developed a Sep 8, 2011 case for model validation, available to operating entities on request Draft model validation report on May 30, 2013 PDCI RAS event is available Additional events that have occurred: July 10, 2013 event (1130 MW generation loss in California) July 25, 2013 event MVWG is continuing to improve the process to develop future model validation cases Using WSM data, EMS data, PI data Created a spreadsheet of key info to collect data from utilities Powerflow Modeling Issues Some generators are connected directly to the high-voltage bus Every generating unit in a base case must have a step-up transformer Many of 230/34.5-kV wind power plant step-up transformers in Pacific Northwest had fixed tap ratio set to 1.0 for high and low sides This resulted in abnormally high reactive power flow from the system to wind power plants Most wind power plants have high side voltage tap set to 241.5-kV, or 1.05 fixed tap ratio - making this correction improved reactive power consumption and voltage profile by wind power plants Several phase shifters are modeled as conventional type 1 transformers Phase shifters should be modeled as type 4 transformers, and include their phase angle control limits Individual shunts are not always modeled separately Even if they are at the same bus, model shunts individually. This should help with reconciling with the WSM case, and improve the ability for accurately adjusting shunts during dynamic simulations. Dynamic Modeling Issues Generators connected to the same bus require either Reactive Current Compensation (RCC) or some type of Cross-Current Compensation (CCC) RCC is most commonly used CCC is used when better voltage support is required Currently implemented at The Dalles, John Day and several Willamette Valley plants operated by USACE These generators will have Line Drop Compensation (LDC) and rely on CCC to provide stability Example of “xcomp” issues: Little Goose “xcomp” set to zero. Changed to –0.05. S.Clara “xcomp” set to zero. Changed to –0.05. Magcorp “xcomp” of +0.05. Changed to -0.05. Looks like conversion from PSS®E to PSLF. RCC is positive in PSS®E and negative in PSLF. Dynamic Modeling Issues (cont.) Errors identified in July 4 2012 report are still present Helms units were operated as pumps and showed growing oscillations. The sign of PSS gain needs to be negative for units to be stable in pumping operations. High Desert units (busses 29000 – 29003) do not have exciter models, and go out-ofstep during certain simulations. A typical excitation model is added. “pss2a” model for 46895 "RI SOUTH" 13.80 "BA" is unstable. "Cflag" in “hyg3” model for [ 44143 "CHJ 0506" 13.80 "05"] is changed to 1 from –1 to correctly represent Woodward PID governors installed at the unit similar to other Chief Joseph units 1 – 16. Water starting times were updated for several hydro-turbine models based on the recent data provided by generator owners." 45448 "KFALLCT1" 18.00 “1” "xcomp" is changed to 0.0 from 0.150, otherwise unstable. Confirmed with the test report. Rock Island units changed the sign for "xcomp", otherwise unstable. 16504 "SUNDTCT " 13.80 "2 " "xcomp" is changed –0.05 from +0.05, otherwise unstable. Sister unit at same bus has “xcomp” of –0.10. 65021 "MAGCORP " 13.80 "1 ", "2" and "3“"xcomp" changed from 0.05 to –0.05, otherwise unstable (could be PSS®E to PSLF conversion issue). Ryan units in Montana "xcomp" are changed to -0.042 from +0.042, otherwise units at same bus are unstable (could be PSS®E to PSLF conversion issue). System Model Validation MVWG is participating in the TSS WBRTF effort MVWG contract with GE to convert WECC dyd data to an “element code” definition with WSM GE provided demo of node-breaker capabilities in PSLF version 19 beta Scan view allows bus-branch, node-breaker, or hybrid view Uses EMS labels for devices (e.g. bus LID) Has provided benefits to reconciling modeling differences, identifying and fixing modeling discrepancies Recommendation: Model shunts individually Final deliverable should be completed in the next few months JSIS Update 522 PMUs have been deployed to date BPA provided comments to FERC NOPR on Frequency Response and Frequency Bias Setting Reliability Standard BAL-003-1, see FERC website Docket Number RM13-11 JSIS developed frequency response application, including adding NERC FRM calculation, adding over 5 years of frequency disturbances into data base WECC, NREL, EPRI, UVIG, Enernex, and Sandia are in a joint effort to use PMU data for wind power plant model validation 2400 MW of renewable generation is covered by PMUs JSIS has further developed the oscillation analysis tool Oscillation detection went live on October 1, 2013 and will alarm dispatchers when there is an event. Currently BPA and WECC RC (Peak Reliability) have this set up in their control centers. WECC RC hosts a Wide Area View that entities should be able to view. JSIS is writing a paper on modes of inter-area oscillations in the West Generator Modeling, Testing, and Model Validation Synchronous Generator, Excitation and Turbine Control Models Power Plant Model Data Task Force Excitation Model Update Governor Modeling Power Plant Model Validation Power Plant Model Data Task Force Reviewed the most recent list of suspected errors Will include suspect data errors related to “xcomp” model If there are additional errors suspected, continue to send them to Kent MVWG will work with SRWG to incorporate additional data checks into the base case review process Excitation Models – OEL / UEL IEEE Standard 421.5 on excitation models are still in process of going to ballot Includes approximately 30 excitation models All include HV and LV gates to incorporate OEL and UEL models More discussion will be needed to determine which model(s) WECC will recommend to be the approved Currently OEL1 is WECC approved UEL1 and UEL2 have been recommended to be implemented in the programs Governor Modeling IEEE PES task force completed a report on turbine-governor modeling: http://www.ieee-pes.org/images/pdf/PES_TR1.pdf H6b model has been implemented in PSLF and tested Discussed an issue raised about powerflow modeling of frequency responsive reserves Power Plant Model Validation Tools Power Plant Model Validation (PPMV) version 1B using PSLF play-in function is available on the WECC MVWG PPMDTF Documents website Tool for validating generator response on a 2 bus system “Generator_Model_Testing.zip” is available on the WECC Library > For Generators website Frequency response tool “Gen_Freq_Response.zip” is available to help analyse generator response to frequency disturbances John Undrill’s data checking tool is posted in the For Generators area in Generator Testing Program Folder Renewable Energy Modeling Wind/Solar Webinar Nov 5, 2013 REMTF Webinar Program Status WECC status on approved base cases: PSLF: wind (except new type1/2 pitch controller) and PV in v18.1_02 (already released). PSSE: wind in v33.4 (already released) and PV in v33.5 (already released). PowerWorld: wind in v18 (beta released, planned release in Spring 2014). PV not yet implemented. Currently on PSLF 18.0, soon to go to 18.1_02 PSSE is on version 33.4 PowerWorld version 17 UVIG Resource: http://variablegen.org/newsroom/ REMTF – Wind/Solar Models Distributed PV: PVD1, CMPLDWg Wind/Solar Implementation Plan Description Date MVWG Approved Model Specifications November 2012 TSS Approved Model Specifications January 2013 Complete WECC-scale model testing with model prototypes (Alpha version) September 2013 Release version of commercial software programs (at least PSLF) made available to WECC as Beta version Nov/Dec 2013 Complete drafting of MVWG to provide Application Guidelines with ‘typical’ data for major manufacturers November 2013 March 2014 2-Hr Webinar: cover policy, model development, expected deployment process November 2013 Update Approved Dynamic Models List (add updated wind models and solar models, and remove obsolete models) March 2014 WECC completes PSLF vetting process and address cross-platform conversion tools; release to WECC users March/April 2014 Issue request for entities to submit data using new models into WECC case, with grace period Summer 2014 User Workshop Summer 2014 REMTF – Next Steps Phase 2 Wind Type 3 model – based on one vendor feedback, will pursue additional discussions to determine if it is necessary to keep the more complex torque controller as a separate module Distributed PV models PVD1 is to be reconsidered More discussion is needed between REMTF, program vendors and LMTF to determine how to incorporate distributed PV in the composite load model (CMPLDWg). A new item is to look at energy storage modeling, such as battery storage HVDC Modeling HVDC Modeling Conventional point-to-point HVDC Powerflow model: already exists, documentation is being improved Dynamic model: being developed EPRI provided a benchmark test case to Siemens and GE Siemens recently provided simulation results for comparison, some issues are being investigated When issues are resolved, will seek input from ABB and others on the model HVDC Modeling VSC point-to-point HVDC Powerflow Implemented in PSSE, beta in PowerWorld, PSLF is implementing Next step is to benchmark across programs Dynamic model: specs have been agreed upon model: two proposals are being discussed 1) DC injection based model vscdc and 2) voltage phasor behind reactance type model vscdc1 Siemens recently provided simulation results, to be circulated and discussed HVDC Modeling Pouyan and the HVDCTF provided a memo as an educational document for the HVDC user-defined models in WECC, including PDCI, TransBay, IPP and Blackwater Included is contact information for the HVDC owners Memo has been shared with TSS Trans Bay DC model still needs to be validated PDCI Modeling Sylmar model still needs to be validated Celilo is expected to be replaced in 2016, the updated model is in progress Other Items Other Items SVSMO3 Modeling NERC Updates WECC Project Updates MSRATF Update - RAS/Relay Modeling Program Updates SVSMO3 Modeling S&C presented their experience with the SVSMO3 model and suggested to adding the following to the model: Reactive power control, droop control Line drop compensation similar to in REPC_A Power factor control mode Master-slave control with power plant control Modeling multiple short-time ratings More discussion to follow NERC Updates Eric Allen (NERC) provided updates NERC MWG efforts: Standardization of dynamic models– initial list targeted for July 2014 Will start from interconnection lists, including WECC’s Approved Dynamics Model List Node-breaker modeling proposal – more documentation is needed MOD-032-1 (modeling data) and MOD-033-1 (validation) are open for comment until Nov 20, 2013 PRC-002-2 on Disturbance Monitoring is open for comment until Dec 16, 2013 WECC Project Updates WECC-0101 SAR Gen Validation Policy WECC-0098 Droop Criterion MVWG recommended to the WECC Standards Committee to draft a regional reliability standard or a variance to reconcile WECC Policy and MOD-026 and 027 Drafting team formed, chaired by Shawn Patterson USBR Drafting team disbanded after document not approved, waiting for direction from NERC WECC-0099 PSS Effectiveness Drafting team formed (consists of Control Work Group), chaired by Martin Bauer USBR Additional studies will be performed to support this effort Next Meetings / Workshops Next Meetings / Workshops March 18-20 in Salt Lake City UT, hosted by WECC REMTF Mar 18-19 LMTF Mar 19 MVWG Mar 19-20 June 16-19 in Portland OR, hosted by BPA (pending WECC approval) Renewable (Wind/Solar) Modeling Workshop Generator Testing and Modeling Workshop November 18-20 in Albuquerque NM, hosted by Sandia National Laboratories (pending WECC approval) HVDCTF and PPMDTF will meet independently from the main M&VWG meeting. Questions ?