Characteristics
Configuration
LAN Manager
LON Maker
Schneider Electric - BU Quality Emergency Lighting – Mauro Grilli
2
Characteristics
Schneider Electric - BU Quality Emergency Lighting – Mauro Grilli
3
Dardo LON Module
DLM
Characteristics
● Characteristics
● Connection with Dardo Plus central unit and supervision of the
System through LON Communication (Local Operating Network).
● Compatibility with Schneider Vista software.
● Integration with LON Schneider complete system.
● Mains 24 V DC +/- 10% 100 mA.
● Protection against power polarity inversion.
● Connection with PC using crossing cable for DLM configuration
(cable not included in the packaging).
● Direct connected with Dardo Plus through RS485 serial line.
● LAN Manager software configuration included in the packaging.
Schneider Electric - BU Quality Emergency Lighting – Mauro Grilli
4
Configuration
Schneider Electric - BU Quality Emergency Lighting – Mauro Grilli
5
Configuration
Dardo LON Module
DLM
● Configuration - Connection with Dardo Plus self contained luminaires
and ACL connected with Mastersin Duo
● Up to 20 central units connected with 1 DLM
(20 ACL or 20 DP or 20 ACL+DP).
LK
RS485
TX
RX
100
RX
TX
Dardo Lon Module
LON
RS485
Max. 20
MAX
20
Dardo
Plus
DARDO PLUS
RS485
RS485
DLM Connector
5 Pin RS 485
DLM Connector 5 Pin RS485
1
2
3
4
5
Schneider Electric - BU Quality Emergency Lighting – Mauro Grilli
DardoPlus
plus connection
Plug Plug
Dardo
connection
1
6
5
4
3
2
1
6
LAN Manager
Schneider Electric - BU Quality Emergency Lighting – Mauro Grilli
7
LAN Manager
Dardo LON Module
DLM
● LAN Manager
● Disconnect all the devices from the DLM.
● Connect DLM Device to the PC using Ethernet crossing cable.
● PC configuration
● disable DSN
● set-up address IP 192.168.0.xxx (except 6)
● mask 255.255.255.0.
DLM
Dardo LON Module
Dardo PC Lite
Schneider Electric - BU Quality Emergency Lighting – Mauro Grilli
8
Dardo LON Module
DLM
LAN Manager
● LAN Manager - Computer configuration
● ES with Windows XP.
● Start – configuration panel – Network connection – Local LAN network
connection.
● Mouse right click - property.
Schneider Electric - BU Quality Emergency Lighting – Mauro Grilli
9
Dardo LON Module
DLM
LAN Manager
● LAN Manager - computer configuration
Click “Internet Protocol” (TCP/IP).
Click “Properties”.
Schneider Electric - BU Quality Emergency Lighting – Mauro Grilli
10
Dardo LON Module
DLM
LAN Manager
● LAN Manager - computer configuration
Click “use this IP Address:”.
Address IP: 192.168.0.xxx (except 6).
Subnet Mask: 255.255.255.0.
Click OK.
Schneider Electric - BU Quality Emergency Lighting – Mauro Grilli
11
Dardo LON Module
DLM
LAN Manager
● LAN Manager
● Start with LAN Manager Software.
● File - Open TCP/IP Conn.
● Should be start DLM communication.
Schneider Electric - BU Quality Emergency Lighting – Mauro Grilli
12
Dardo LON Module
DLM
LAN Manager
● LAN Manager
● Click “Downloads”.
Be careful because clicking on this menu DLM device starts with
configuration procedure immediately (3 Led on the panel start blinking) and is
necessary repeat the configuration procedure.
Schneider Electric - BU Quality Emergency Lighting – Mauro Grilli
13
Dardo LON Module
DLM
LAN Manager
● LAN Manager
● Click Load.
● Set up the file .hex corresponding to the right configuration
that is beeing created
1. Dardo2.hex - connection with Dardo 2.
2. DardoPlus.hex - connection with ACL - Dardo Plus - Powersin.
Schneider Electric - BU Quality Emergency Lighting – Mauro Grilli
14
Dardo LON Module
DLM
LAN Manager
● LAN Manager
After the set up of the file .hex click “Program”.
Wait the set up and the information “Program O.K.”.
Click “Verify”.
Click “Start”.
Schneider Electric - BU Quality Emergency Lighting – Mauro Grilli
15
Dardo LON Module
DLM
LAN Manager
● LAN Manager
● Set up the central units connected
to the DLM.
● Up to 20 lines for the configuration.
Schneider Electric - BU Quality Emergency Lighting – Mauro Grilli
16
Dardo LON Module
DLM
LAN Manager
● LAN Manager - Dardo Plus connected directly
● Up to 20 lines for the set up of Dardo Plus Central units.
Number of line
Schneider Electric - BU Quality Emergency Lighting – Mauro Grilli
17
Dardo LON Module
DLM
LAN Manager
● LAN Manager - End of configuration
Click “Write” to confirm the configuration.
Click “Cancel” to close the configuration procedure.
Click “Activate” and wait the connection.
After that we will be on the operational mode.
Schneider Electric - BU Quality Emergency Lighting – Mauro Grilli
18
Dardo LON Module
DLM
LAN Manager
● LAN Manager - End configuration
● Click “Cancel”.
Schneider Electric - BU Quality Emergency Lighting – Mauro Grilli
19
Dardo LON Module
DLM
LAN Manager
● LAN Manager - downloads - DLM Data
upload
● If “Download” is used, and if an error
occurs, it is possible to repeat the
configuration or upload the recorded
configuration:
Click “Read”.
Click “Write”.
Click “Cancel”.
Schneider Electric - BU Quality Emergency Lighting – Mauro Grilli
20
Dardo LON Module
DLM
LAN Manager
● LAN Manager
It is possible to verify the LAN
communication using “Test” -> LAN test
Menu.
Click “Start” and the communication
will start.
Click “Stop” to stop the test
communication. There isn’t a test time
limit but it is necessary to click “stop”.
Schneider Electric - BU Quality Emergency Lighting – Mauro Grilli
21
Dardo LON Module
DLM
LAN Manager
● LAN Manager - help
● Click “Help” Menu – to have
the instructions for the IP Address
configuration.
Schneider Electric - BU Quality Emergency Lighting – Mauro Grilli
22
Dardo LON Module
DLM
LAN Manager
● LAN Manager - setup
● Clicking “setup” to modify
the IP address of the communication.
● With this operation it is not possible to
modify the IP Address of DLM that is fixed,
and it is the same for all the DLM.
● It is possible to include new devices with
different addresses.
Schneider Electric - BU Quality Emergency Lighting – Mauro Grilli
23
Dardo LON Module
DLM
LAN Manager
● LAN Manager - close the software
It is necessary to close the IP
communication before closing
the LAN Manager software.
Schneider Electric - BU Quality Emergency Lighting – Mauro Grilli
24
Dardo LON Module
DLM
LAN Manager
● DLM - LED RS485 state
● RS485 connection with Dardo Plus: ON fixed.
● RS485 connection with Dardo 2: ON Blinking.
● RS232 Powersin connection: OFF.
● RS485 configuration but not connected after the configuration:
ON Blinking.
Schneider Electric - BU Quality Emergency Lighting – Mauro Grilli
25
LON Maker
Schneider Electric - BU Quality Emergency Lighting – Mauro Grilli
26
Dardo LON Module
DLM
LON Maker
● Examples - LON Maker - Dardo Plus
Commands
Reading
information
Schneider Electric - BU Quality Emergency Lighting – Mauro Grilli
27
Dardo LON Module
DLM
LON Maker
● LON Maker - Dardo Plus
● Commands
Time and Date TF and TA Year/Month/Day
h:m:s.
Frequency TF and TA 1-99 days - 1-99
Weeks.
Duration TF and TA 1-15 min - 1-180 min.
Date and time of the central units.
The configuration is saved in the central unit
memory.
Schneider Electric - BU Quality Emergency Lighting – Mauro Grilli
28
Dardo Lon Module
DLM
LON Maker
● Examples - LON Maker - Dardo Plus
● Functional Test set-up - First situation Fault and after OK
Functional test set-up at 13:15 16/8/2010.
The central unit received the command.
The central units start the test at the right time - Is in test and fault states.
The Central unit finish the test and reset the fault situation.
Schneider Electric - BU Quality Emergency Lighting – Mauro Grilli
29
LON Maker
Dardo Lon Module
DLM
● Examples - LON Maker - Dardo Plus
● Light status
● Each line 8 luminaires.
● Each luminaire 8 bit.
● Lmp0 = Address 1 – Lmp7 = Address 8…
Luminaire N°1
not present
Luminaire N°2
not present
Schneider Electric - BU Quality Emergency Lighting – Mauro Grilli
Luminaire N°3
present and FT
done