eMerge Browser Managed Security Platform Module 2 Hardware install Panel layout Tamper switch Power cable Controller board Ribbon cable Access board Power supply board Input board Input board Empty expansion slot Wire hold-down Power requirements IEI eMerge systems must be AC powered using the grounded plug-in transformer provided. Power should come from a circuit with an isolated ground and must be wired to the power supply mounted inside the eMerge cabinet. Transformer Input: 120 V AC 60 Hz 48W. Transformer Output: 16.5V AC 2400mA. The IEI eMerge includes a DC power supply. The eMerge power supply provides 12V DC at 3.3 amps. The recommended battery which is not included 12V DC, 7 AH, SLA (sealed lead acid). CAUTION!!! MAKE SURE ALL POWER IS OFF BEFORE CONNECTING OR DISCONNECTING MODULES IN THE IEI eMerge. Network Controller board layout The network controller board must be located in the top position Top side of board Processor Ribbon cable connector Network port (reserved for future use) Node Reset Cabinet Tamper Switch input Power supply Input 2-pin Bottom side of board I-button socket Ribbon cable connector Battery Compact flash socket Panel LED Battery Input/ Charger 3-pin 2-port Network switch Network Controller Reset Expansion Node Card The Expansion Node board must be located in the top position Ribbon cable connector Node Reset Cabinet Tamper Switch Input Ribbon cable connector Battery Power supply Input 2-pin Panel LED Battery Input/ Network port Charger 3-pin I-button and tamper switch Tamper switch mounts Processor Cabinet tamper switch connector Mounting holes The tamper switch is installed on the tamper switch mounts and wired to the provided cord which is then plugged into the tamper switch connector on the control board Controler I-button socket MODEL XXX Serial Number Revision The label is here This side goes down into socket xxxxxxxx REV.X Ribbon cable connector Battery The controller I-button comes pre installed Compact flash socket The I-button contains system licensing. Installing board in panel 1. Power down the eMerge. 2. Thread the standoff tube provided down onto the threaded post on the chassis next to the slot where you will insert the additional module. Be sure that you are grounded and insert the additional module into the slot on the chassis with the ribbon cable connector toward the left of the eMerge cabinet. See diagram below. 3. 4. Place the lock washer provided over the top of the standoff and thread the screw provided through the flange and down into the top of the standoff and snugly down onto the lock washer. See diagram below. 5. Connect the ribbon cable from the Controller/Node module in the topmost slot to the newly installed module. The connector is polarized. Make sure that the center bump fits into the opening for it on the connector on the module. Press the connector firmly into place until you hear the click of the extraction levers snapping into vertical position. You may have to press the extraction levers into full vertical position before you will hear the click. lock washer Standoff comes flush to flange Board goes down into slot standoff tube Ribbon cable Slot numbers are determined by the connector on the ribbon cable that is plugged into the module. The ribbon cable (see diagram below) is a bus and a module’s place on the bus determines the slot number. You will see that it is possible to place a module in physical slot 5 and yet attach ribbon cable connector 6 to the module. If this occurs the module will be in slot 6 on the bus. Controller/Node connector Connectors for slots 1 2 3 4 5 6 Note: When connecting the modules to the ribbon cable be sure the connector is fully seated in the board (push on cable do not rely on the tabs on the boards) 7 Access Control module (ACM) #2 Weigand reader connections #1 Ribbon cable connector The access control module can be used for 2 doors with Position both in reader or 1 door for in and out readers. 4 3 2 1 Form C relay outputs 4 3 2 1 2-pin supervised inputs The ACM board can be located in slot positions 2-7 Input Board layout Ribbon cable connector The input board is used for monitoring alarm points, or when multi supervised inputs are needed. Position 8 7 6 5 4 3 2 1 2-pin supervised inputs The Input board can be located in slot positions 2-7 Output Board layout Ribbon cable connector The Output board is Used for elevator control or when additional form C relays are required. Position 8 7 6 5 4 3 2 1 Form C relay outputs The Output board can be located in slot positions 2-7 Wiring battery and power to controller. Power supply input 2-pin The power supply is pre wired to the network controller. pin 1 +12V DC pin 2 ground Battery input 3-pin pin 3 ground pin 1 +12V DC AC GND AC AC IN +V Processor NEG +BATT- Note: Do Not connect Battery to power supply board connect to the controller board Wiring Weigand readers CAUTION!!! Each eMerge Access module can supply a total of 400 milliamps of power for readers. If the reader(s) connected to the Access module draw more than 400 milliamps then external power must be supplied to these readers. Pwr (red) Gnd (black) Bpr Grn LED control D0 (green) D1 (white) Access Control module (ACM) The maximum distance for wiring weigand devices to the access board is 500 Ft. For distances longer then 500 ft. you need to use an additional expansion node with acm or there are 3rd party devises made to extend the distance. Red LED control ACM 2-pin inputs Ribbon cable connector Supervised Inputs wiring The inputs on the eMerge panel are supervised that allows the panel to monitor the status including if the input is in a normal state, alarmed or triggered, and if the wires before the devise is shorted or the same is opened. 4 3 2 1 positions Supervised input board Ribbon cable connector Position 8 7 6 5 4 2-pin inputs Input state Input device Normally Open (NO) 2-pin input connector Normal 1k Ohms ±5% Alarm 0.5k Ohms ±5% Short 0 Ohms Open No current (∞ Ohms) Input State Resistance Value Normal 1k Ohms ±5% Alarm 2k Ohms ±5% Short 0 Ohms Open No current (∞ Ohms) 1K Resistors - Install at or near input device Input device Normally Closed (NC) 2-pin input connector 1K Resistors - Install at or near input device Resistance Value 3 2 1 ACM Wiring Outputs Ribbon cable connector 3-pin outputs 1 2 3 4 Output board 3-pin outputs DC output device Pin 2 common + + DC power supply 3-pin output connector Pin 3 normally open Diode - 1N4933 or equivalent + Pin 1 normally closed + DC power supply positions 8 7 6 5 4 3 - - DC output device Ribbon cable connector 3-pin output connector - Diode - 1N4933 or equivalent Pin 2 common The dry contact relay is wired up as shown we show using a DC power supply for the lock. A diode is used for dc this is so the relay does not fail prematurely from a voltage spike from the lockset. When using AC voltage use a mov SNRD56k2 or equivalent. Diodes and movs are supplyed with the access boards and output boards. 2 1 Connecting to the network When connecting to the controller board use a patch cord. A router or DHCP server needs to be connected so the node will get an IP address issued through DHCP. Panel Led operation Green steady The network communication is functioning and external power is on. Green flashing The network communication is functioning and the eMerge is using battery power. Yellow steady The network communication is not functioning and external power is on. Yellow flashing The network communication is not functioning and the eMerge is using battery power.