chapter2_circuit_breakers_jan_2014

advertisement

2. Circuit Breakers and Recloser

4/15/2020 Dr.Latif Shaikh

Course Outline

• Introduction

• Circuit Breaker

• The Arc

• Isolators

• Air Circuit Breakers

• Air Blast Circuit Breakers

• Vacuum Circuit Breakers

• Oil Circuit Breakers

• Sulfur Hexafluoride Circuit Breakers

• Circuit Breaker Ratings

• Circuit Breaker Controls

• High Voltage Circuit Breakers Comparison

• Reclosures

• Sectionalizers

• Fuses

• Fuse application

4/15/2020 Dr.Latif Shaikh

Circuit Breaker

• A circuit breaker is a piece of equipment which can Make or break a circuit either manually or by remote control under normal conditions.

• Break a circuit automatically under fault condition

• Make a circuit either manually or by remote under fault condition

4/15/2020 Dr.Latif Shaikh

Operating Principle

• Circuit Breaker consists of fixed and moving contacts called electrodes

• Under normal operating condition these contacts remain closed and will not open automatically unless the system becomes faulty .These contacts can be opened manually or by remote control.

• When a fault occurs in a circuit the trip coils of the circuit breaker get energized and the moving contacts are pulled apart by some mechanism

,thus opening the circuit.

4/15/2020 Dr.Latif Shaikh

Simplified Diagram of Circuit Breaker Control

4/15/2020 Dr.Latif Shaikh

Electric Arc

4/15/2020 Dr.Latif Shaikh

Electric Arc

When contacts of circuit breaker starts separating the contact resistance starts increasing. This increases the (I square r) loss which is heat produced .

This heat increases the energy of electrons in the contact areas and the ionized particles tries to maintain the current when contacts are separated.This flow of charged particles form one contact to other is called an arc .

The medium surrounding the arc also contains ions .

Due to this charged particles the arc continues even if the breakers contacts are separated.

The voltage (potential gradient) across the arc is less and so it continues even for low voltages.

4/15/2020 Dr.Latif Shaikh

ARC in AC and DC circuits

• DC arcs are to be interrupted by increasing the resistance interruption method in which resistance of the arc is increased so that the arc voltage can no longer maintain the current and the arc is extinguished.

• Size of DC circuit breaker increases as the voltage level increases.

• AC arcs current reduces to zero in each cycle (2 times)

• If the circuit breaker contacts are opened at time when the current passed through zero and dielectric strength of the medium is build up rapidly so that arc cannot strike again then arc can be extinguished successfully.

• Size of AC circuit breaker can be small compared to same voltage DC circuit breaker.

4/15/2020 Dr.Latif Shaikh

Principles of Arc extinction

• Separate the contacts of circuit breaker such that the arc resistance increases to a very high value. The pd between the contacts is unable to maintain the arc current. For high voltage circuit breakers this method is impracticable since a separation of many meters will be required.(High Resistance Method)

• The ionized particles between the contacts tend to maintain the arc. If the arc path is deionized ,the arc extinction is facilitated .This may be achieved by cooling the arc or by bodily removing the ionized particles from the space between the contacts.(Low Resistance Method)

4/15/2020 Dr.Latif Shaikh

Important terms

 Arc Voltage – It is the voltage that appears across the contacts of the circuit breakers during the arcing period as the contacts are opened.

 Recovery voltage – It is the normal frequency voltage that appears across the contacts of circuit breaker after final arc extinction.

 Rate of rise of restriking voltage – (RRRV) It is the rate of increase of restriking voltage .RRRV depends upon 1) recovery voltage and

2) Natural frequency of oscillation

4/15/2020 Dr.Latif Shaikh

Restriking Voltage

• It is the transient voltage that appears across the contacts at or near current zero during arcing period.

• If dielectric strength rise is greater than the rise of restriking voltage then the arc will not restrike .

4/15/2020 Dr.Latif Shaikh

Current Chopping

• It is the phenomena of current interruption before natural current zero is reached. It occurs in air blast circuit breaker because they retain same extinguishing power irrespective of the magnitude of current to be interrupted.

• When interrupting low inductive current e.g.magnetising current of transformer, a rapid deionizing effect causes current , to fall below its zero value before natural current zero is called current chopping.

4/15/2020 Dr.Latif Shaikh

Current Chopping

4/15/2020 Dr.Latif Shaikh

Resistance Switching

4/15/2020 Dr.Latif Shaikh

Resistance Switching

The switching Resistor (R) is connected in parallel with the CB contacts. Current chopping produces high voltage oscillations which can be prevented by this method.

During arc interruption CB contacts separate first and after arc gets extinguished ‘S’ opens depending upon the time delay provided to it.

When the fault occurs the CB contacts open and arc is struck between them.

Since R is in parallel with Cb contacts ,a part of arc current flows through this resistance so arc current decreases and deionization rate increases. The arc resistance also increases so current through R increases. This continue till the arc current is insufficient to maintain the arc.

4/15/2020 Dr.Latif Shaikh

Circuit Breaker Rating

 Breaking capacity – It is the current (r.m.s.) that a Circuit Breaker is capable of breaking at given recovery voltage and under specified conditions.

 Making Capacity – The peak value of current (including DC component) during the first cycle of current wave after closure of circuit breaker is known as making capacity. Making capacity = 2.55 × symmetrical breaking capacity

 Short time rating – It is the period for which the CB is able to carry fault current while remaining closed.

 Normal current rating – It is the r.m.s. value of current which the CB is capable of carrying continuously at its rated frequency under rated specified conditions.

4/15/2020 Dr.Latif Shaikh

IEEE Standards for Selection of Circuit Breakers

Step 1.Calculate highest value of initial RMS current considering symmetrical fault. The current can be obtained by sub -transient reactance of synchronous generators and transient reactance of synchronous motors and induction motors are neglected.

Following Multiplying factors are applied to take into account dc components and decrement of dc components in current. If short circuit KVA exceeds

5000,000 ,then add 0.1 to the given factors

8 cycles or slow breaker 1.0

5 cycle breaker

3 cycle breaker

2 cycle breaker

1.1

1.2

1.4

4/15/2020 Dr.Latif Shaikh

IEEE Standards for Selection of Circuit Breakers

4/15/2020 Dr.Latif Shaikh

1) CB rated 1500A,1000MVA,33kV,3sec,3phase oil CB.Find a)rated normal current b) breaking capacity c)rated symmetrical current d)Rated making current e) short time rating f)rated service voltage

4/15/2020 Dr.Latif Shaikh

Problem -A generator connected through a 5 cycle circuit breaker to a transformer is rated 8000KVAand 13.8kV with the reactance of

Xd”=10%,Xd’=16%,and Xd=100% .It is operating at no load and rated voltage when 3 phase short circuit occurs between breaker and transformer. Find

1.Sustained short circuit current in the breaker

2.The initial symmetrical rms current in the breaker

3.Maximum possible dc component in the breaker

4.Current to be interrupted by the breaker

5.The interrupting KVA

4/15/2020 Dr.Latif Shaikh

4/15/2020 Dr.Latif Shaikh

Requirements of Circuit Breaker

4/15/2020 Dr.Latif Shaikh

Classification of Circuit Breakers

4/15/2020 Dr.Latif Shaikh

4/15/2020 Dr.Latif Shaikh

Air Circuit Breakers

1.In this Circuit Breaker the arc is elongated using arc runners and arc splitters so as to increase the resistance of the arc.

3.This increases the voltage required to maintain the arc and if the available voltage cannot sustain the arc ,the arc gets extinguished.

2.At current zero ,the recovery voltage across the contacts becomes less than the arc voltage and the arc gets extinguished.

4. The energy in the system inductance at current zero is zero

.Hence arc interruption is easier.

4/15/2020 Dr.Latif Shaikh

4/15/2020 Dr.Latif Shaikh

Air Circuit Breakers

1.Used For low voltage levels and current levels

2.As voltage level increases, the size of breaker becomes large so not convenient for higher voltage and current levels.

3.Air is used as medium to extinguish the arc which have inferior extinguishing properties compared to SF6 or Vacuum circuit breakers

4.Operating control is manual as well as automatic.

5.It is used up to 6.6kV with a breaking capacity of 15MVA.

6.Suitable for repeated operation because medium of arc extinction is air . So commonly used in Industrial Switchgears . Auxiliary switchgear Generating

Stations

4/15/2020 Dr.Latif Shaikh

Air Blast Circuit Breakers

In this breaker, a high pressure air blast is used as an arc quenching medium.

The contacts are opened and a flow of air blast is maintained by opening the blast valve.

The air blast cools the arc and takes away the arcing products to atmosphere .

This rapidly increases the dielectric strength of the medium between the contacts and the arc is extinguished and the flow of current is interrupted.

4/15/2020 Dr.Latif Shaikh

4/15/2020 Dr.Latif Shaikh

Air Blast Circuit Breaker(Radial Flow)

4/15/2020 Dr.Latif Shaikh

Advantages and Disadvantages

Advantages

 High speed of operation

 Short arcing time

 High speed reclosing

 Less weigh as compared to oil circuit breakers

 Very less maintenance

 No possibility of explosion

Disadvantages

 Cost is more

 For complete compress air installation is required

 These breakers are more sensitive to RRRV.

 For operation and maintenance ,highly skilled persons are required

4/15/2020 Dr.Latif Shaikh

Air Blast Circuit Breakers (Axial Flow)

4/15/2020 Dr.Latif Shaikh

Axial Blast ABCB

Air is admitted in the arc extinction chamber it pushes the moving contact. This air blast takes away the ionized gases along with it.

Afterwards the arc gets extinguished. High pressure air has higher dielectric strength.

The design is such that the air expands into the low pressure

(atmospheric pressure zone).The air at high speed removes heat from the arc, thus arc is quenched. Diameter of arc is reduced.

Uses

1.Arc Furnaces

2.Traction Syetems

4/15/2020 Dr.Latif Shaikh

Modification of Air Blast Circuit Breakers

4/15/2020 Dr.Latif Shaikh

Advantages of Air Blast Circuit Breaker

4/15/2020 Dr.Latif Shaikh

Disadvantages of Air Blast Circuit Breakers

4/15/2020 Dr.Latif Shaikh

Applications of Air Blast Circuit Breakers

4/15/2020 Dr.Latif Shaikh

Vacuum Circuit Breakers

When two contacts of this circuit breaker are separated in vacuum an arc is struck and hot spots are formed on the surface of the contacts .These hot spots produce metal vapor and plasma .the amount of vapor in plasma depends on how rapidly the vapor is emitted from contact surface which depends on the arc current. The current is of alternating nature, it pass through zero several times, so the rate of vapor emission also becomes zero , and the vapor already emitted gets condensed . During this process the dielectric strength builds up rapidly and the restriking of arc is prevented.

4/15/2020 Dr.Latif Shaikh

Vacuum Circuit Breaker

4/15/2020 Dr.Latif Shaikh

Vacuum Circuit Breakers

It consists of fixed contact, moving contact and arc shield mounted inside a vacuum chamber. The movable member is connected to the control mechanism by stainless steel bellows. This enables the permanent sealing of the vacuum chamber so as to eliminate the possibility of leakage,.

A glass vessel or ceramic vessel is used as outer insulating body. The arc shield prevents the deterioration of the internal dielectric strength by preventing the deterioration of the internal dielectric strength.

Applications

Outdoor application where maintenance required is minimum.In the high voltage system from 22 KV to 66kV power Circuits.

4/15/2020 Dr.Latif Shaikh

Working of Vacuum Circuit Breaker

When two contacts of circuit breaker are separated in vacuum arc is struck and hot spots are formed on the surface of the contacts. These hot spots produce metal vapour and plasma.

At current zero the rate of vapour emission becomes zero.

The vapour already emitted gets condensed .

During this process the dielectric strength builds up and the restriking of arc is prevented.

4/15/2020 Dr.Latif Shaikh

Vacuum Circuit Breakers

Advantages

 Compact in size

 Reliable and long life

 Heavy fault can be interrupted effectively

 No gas is generated after arc extinction operation

 Operation is not noisy

 Arc energy is low

 No risk of fire

4/15/2020 Dr.Latif Shaikh

Disadvantages

 Vacuum has to be maintained at desired level always

Oil Circuit Breakers

4/15/2020 Dr.Latif Shaikh

Oil Circuit Breakers

This breaker makes use of oil for quenching the arc.

The circuit breaker which uses more oil or which is bulky is called bulk oil circuit breaker.

The construction is simple and it consists of fixed and moving contacts enclosed in a strong weather –tight earthed tank containing oil up to a certain level and an air cushion above the oil level.

Application

These breakers are used up to 11 KV with an interrupting capacity of

250MVA.

4/15/2020 Dr.Latif Shaikh

Oil Circuit Breaker (Working)

Under normal working conditions, the fixed and moving contacts are closed. On the occurrence of fault, the moving contacts come down and an arc is struck between the contacts. The oil between the contacts gets decomposed and hydrogen gas bubble is formed around the contacts. The hydrogen gas cools the arc and rthe turbulence effect cause the lengthening of arc. The deionization of medium between contacts takes place and at some critical length of gap between the contacts ,the arc is extinguished.

The hydrogen gas bubble produces a very high pressure in the oil. The tank is therefore made strong to withstand a large pressure. The oil moves upwards when hydrogen bubble is formed. The air is present between the oil level and tank top and acts as cushion and absorbs mechanical shock produced due to upward oil movement.

4/15/2020 Dr.Latif Shaikh

Bulk Oil Circuit Breaker

Advantages

• oil has high dielectric strength

• Oil absorbs arc energy while decomposing

• Good cooling property of the gas formed due to decomposition

• It acts as an insulator between the live parts and earth

Disadvantages

• Long arcing time

• Do not permit high speed of interruption

• Arc interruption control can be obtained only by increasing the length of arc

4/15/2020 Dr.Latif Shaikh

4/15/2020

Low Oil circuit Breakers

Operation

When the contacts are separated in oil arc is formed.

The heat of arc decomposes oil and gases are formed. These gases expand due to heating of the arc. The gas flowing near the contact zone cause cooling and splitting of the arc and the arc gets extinguished.

Dr.Latif Shaikh

Minimum Oil Circuit Breakers

In this breaker, the supporting ,current interruption and top chamber are made of porcelain .Hence, clearance between live parts is small and requires less quantity of oil, hence the breaker is called Minimum Oil Circuit Breaker. The chambers are completely filled with oil. The oil from upper chamber does not come to lower.

The fixed contact is enclosed in the quenching chamber. Moving contact makes sliding contact with the lower fixed contact. The operating rod is operated by operating mechanism, the three poles operate simultaneously.

The voltage ratings are from 3.6kV to 420 KV.

Applications –Minimum oil circuit breakers are available in for all voltages and highest breaking capacity hence they are preferred in almost all protection schemes

4/15/2020 Dr.Latif Shaikh

Maintenance of Oil Circuit Breakers

4/15/2020 Dr.Latif Shaikh

Minimum Oil Circuit Breaker

Advantages

 Requires less quantity of oil

 Requires smaller space

 Maintenance is less

 Cost per breaking capacity in MVA is less

 Suitable for both manual and automatic operation

Disadvantages

 Possibility of fire and explosion.

 Difficult to remove gases from the space between contacts.

 Oil deteriorates rapidly due to carbonization

 Smaller quantity of oil, so carbonization increases.

4/15/2020 Dr.Latif Shaikh

SF6 circuit Breaker (Properties of SF6 gas)

 Electronegative –It has the ability of an atom to attract and hold electrons. Such gas have high dielectric stremngth.SF6 is electronegative .It forms negative ions ,Negative ions are heavy and immobile so they do not flow easily .Hence SF6 gas has high dielectric strength.

 Rate of rise of dielectric strength is very high.

 Can be liquefied and stored in steel tanks

 Dielectric strength increase linearly with pressure.

 Gas is inert. Therefore contacts will not get eroded.

 Gas is non –inflammable , Colorless ,odorless, Non-toxic

 Thermally stable up to 55 degrees

4/15/2020 Dr.Latif Shaikh

Sulfur Hexafluoride Circuit Breaker

4/15/2020 Dr.Latif Shaikh

Operation of SF6 Circuit Breaker

• Under normal operating conditions the contacts are closed .

• On occurance of fault contacts are opened. The movable contact moves away from the fixed contact.

• The arc is struck between the fixed and moving contacts.

• High pressure SF6 gas now flows over the arc and it absorbs the free electrons from the arc.

• This builds up the dielectric strength between the gap very fast and the arc is extinguished

4/15/2020 Dr.Latif Shaikh

Advantages and Disadvantages of SF6 Breaker

Advantages

 Silent operation, compact size

 Vary short arcing time

 No risk of fire

 No reduction in dielectric strength due to operation

 No current chopping problem

 Can interrupt larger currents

 Suitable for explosive environment due to totally enclosed body

Disadvantages

 Costly

 Requires conditioning of SF6 gas from time to time

 SF6 gas is suffocating ,so its leakage can cause suffocation of the persons in surrounding areas.

 Special facilities are required for transporting gas

 Additional equipments are required for reconditioning

4/15/2020 Dr.Latif Shaikh

Isolators

4/15/2020 Dr.Latif Shaikh

Isolators

Isolator(disconnecting switch) operates under no load condition.

It does not have any current breaking capacity or current making capacity. Isolator is not even used for breaking load currents.

Isolators are used in addition to circuit breakers ,and are provided on each side of every circuit breaker to provide isolation and enable maintenance.

Sequence of operation

While opening –Open circuit breaker first and then isolators

While closing –Close isolators first and then close circuit breakers

4/15/2020 Dr.Latif Shaikh

Circuit Breaker Controls

Different types of controls are required for successful operation of circuit breakers.

1.Relays – These are required to give a trip signal to circuit breaker in case of fault condition. Different types of relays are available like over current, over voltage ,under voltage, loss of excitation, reverse power etc.

2.Sensor equipments are required to check the condition of circuit breakers arc extinguishing medium .

The controls are pressure sensors to sense the pressure of air in case of air blast circuit breakers .

In case of Sulfur hexafluoride circuit breakers also the pressure sensors are required.

In case of vacuum circuit breakers also sensors are required to check the vacuum level in the breaker.

4/15/2020 Dr.Latif Shaikh

Automatic Reclosing

Many faults (80-90%) in the overhead distribution system like flash over of insulators, crow faults, temporary tree contacts , etc are temporary in nature.

Thus, taking a feeder or line permanent outage may lead to unnecessary long loss of service to customers. Hence, many utilities use fast automatic reclosers for an overhead radial feeder without synchronous machines or with minimum induction motor load. Presence of synchronous machines will require additional problem of synchro-check to be addressed. The almost universal practice is to use three and occasionally four attempts to restore service before lock out .

4/15/2020 Dr.Latif Shaikh

 Subsequently, energization is by manual intervention. The initial reclosure can be high speed (0.2 - 0.5sec) or delayed for 3 - 5 seconds. This allows for de-ionization time for fault arc. If the temporary fault is cleared, then the service is restored.

Otherwise, the relay again trips the feeder. Then one or two additional time delayed reclosures are programmed on the reclosing relay. Typical schedule might be instantaneous, followed by 30sec, or 35sec, followed by 15sec. If the circuit still continues to trip, the fault is declared as permanent and the recloser is locked out.

Reclosers use three phase and single phase oil or vacuum circuit breakers for overhead distribution lines.

 With underground network, faults tend to be more often permanent and reclosers are not recommended. In case of large synchronous motors, distributed generators or induction motor loads, it is recommended that sufficient time is allowed for underfrequency relays to trip these sources of back emf out-of-thecircuit.

4/15/2020 Dr.Latif Shaikh

Reclosures

Application of reclosers in distribution systems requires selection of its ratings such as minimum trip current, continuous current, symmetrical interrupting current etc.

For a single phase system, single phase reclosers can be used whereas for a three phase system, one three phase recloser or three single phase reclosers can be used. Reclosers have to be selected by considering the following factors.

Voltage Rating.

Continuous current Rating : This is the maximum load current the recloser has to carry.

Maximum Symmetrical Interrupting Rating: The maximum symmetrical fault current should not exceed this rating.

Minimum Tripping current : This is the minimum fault current that a recloser will clear. It is equal to two times the continuous current rating. Usually tolerance is ± 10%. This decides the sensitivity of the recloser

4/15/2020 Dr.Latif Shaikh

Example on Reclosure Selection

• Consider a three phase distribution system with a single phase tap as shown in fig . Maximum load on this single phase tap is 40A and that on three phase line is 200A. Fault currents at F1,F2, F3 and F4 are also shown in the fig. Table shows the available standard rating of single phase and three phase reclosers. Select the ratings of reclosers at B.

4/15/2020 Dr.Latif Shaikh

IEEE Standard Table for Reclosure Selection

4/15/2020

15.0

15.5

15.5

15.5

15.5

15.5

15.0

15.5

15.5

15.5

27.0

27.0

38.0

Table (Source : IEEE Tutorial Course 80EH0157 - 8 - PWR)

Current Rating (Amperes)

Rated Maximum Voltage kV rms

Continous Current Rating

50

100

280

400

560

560

50

100

280

560

100

280

560

Dr.Latif Shaikh

1250

2000

4000

4000

8000

16000

Symmetrical Interrupting Rating at Maximum Volts

1250

2000

4000

8000

2500

4000

8000

Answer

Recloser at B

Maximum load current on this single phase line = 40A.

Continuous current rating of this recloser must be 1.25 - 1.5 times the maximum load current to account for anticipated load growth. i.e. Continuous current rating of this recloser at B = 40 × 1.5 = 60A.

From the table 1, any recloser with continuous current rating of 100A and above is acceptable.

Maximum fault current at B = 1750A.

Interrupting current rating must be greater than 1750A. From the table 1, we see that recloser with 100A continous current rating has 2000A symmetrical rms short circuit current rating. Hence, we can choose this recloser.

Minimum tripping current = Continuous current rating × 2 ± 10% tolerance

= 100 × 2 ± 10% of 200 = 220A

Since the minimum trip current 220A is less than the minimum fault current 250A at the line end, it can protect the entire line.

Voltage rating of the line is 11kV. So we can select the maximum voltage rating of

15.5kV (from the table).

4/15/2020 Dr.Latif Shaikh

Sectionalizers

4/15/2020 Dr.Latif Shaikh

Sectionalizers

Sectionalizers are used in the bus bars so that fault on any section of bus bar will not cause complete shut down.

Advantages of sectionalizers

1.If fault occurs on any section of bus bars then that section is isolated from other sections without affecting the system.

2.Fault current is much lower than in case of un sectionalized system (as the fault is fed from only one section)

3.Repairing and maintenance on one section can be carried out by de energizing that section only eliminating the possibility of complete shut down.

The breaker in the bus bars is acting as sectionalizing breaker in the shown figure.

4/15/2020 Dr.Latif Shaikh

Fuses

Fuse is a device used in circuit for protecting electrical equipments against overloads and /or short circuits.

Fuse element or fuse wire is that part of the fuse device which melts when an excessive current flows in the circuit and thus isolates the faulty device from the supply circuit.

Desirable qualities of fuse elements

1.Low melting point

2.Low ohmic losses

3.High conductivity

4.Free from deterioration due to oxidation

5.Low cost

4/15/2020 Dr.Latif Shaikh

4/15/2020

Thermal Characteristic of Fuse

• As the magnitude of the current increases, melting time reduces. It should be obvious that larger magnitude currents will lead to higher power dissipation (I 2 R) in the fuse and hence faster rise in temperature of the element. This would imply that melting time of the fuse should be inversely proportional to magnitude of square of current. The relationship between the magnitude of the current that causes melting and the time needed for it to melt is given by the fuse's melting time current characteristics (TCC). To cover a wide range of currents and operating time, TCC is plotted on a log-log paper.

Dr.Latif Shaikh

Current Voltage Time relationship of

Non Current Limiting Fuse (Expulsion

Fuse)

Current Voltage Time relationship of

Current Limiting Fuse

4/15/2020 Dr.Latif Shaikh

Expulsion Fuse

• The expulsion type fuse is used where expulsion gases cause no problem such as in overhead circuits and equipment. These fuses can be termed as current awaiting types; and the function of interrupting medium is similar to that of an ac circuit breaker. The temperature of arc is of the order of

4000-5000K. At this temperature special materials located in close proximity to fuse element rapidly create gases. Preferred gas generating materials are fiber, melamine, boric acid and liquids such as oil or carbon tetrachloride. These gases help to create a high pressure turbulent medium surrounding the arc, thus when the current does reach to zero and the arc channel reduces to a minimum; the ablated gases rapidly mix with remaining ionized gas and thereby deionize them as well as remove them from ‘arc area'. In turn, this leads to rapid build up of dielectric strength that can withstand the transient recovery voltage (TRV) and steady state power system voltage.

4/15/2020 Dr.Latif Shaikh

Vacuum Fuses

• Vacuum fuse is a non expulsive fuse but still a current zero awaiting type.

The design, operation and current-voltage-time relationship of this fuse closely matches with that of an expulsion fuse. The main difference is that it is a completely sealed unit and no expulsion action. Interruption occurs because of rapid dielectric build up that occur in a vacuum after current zero is reached

4/15/2020 Dr.Latif Shaikh

4/15/2020

Current Limiting Fuse

• Basically, the current limiting fuses attempt to constrict the arc and it is cooled by sand.

A typical current limiting fuse is shown in fig . In this case, the fusible element is very long. The element is completely surrounded with filler material, typically silica sand, to contain the arc as well as maintain a very high pressure in the long restricted arc area caused by the practically simultaneous melting of the full length of element.

This then allows the fuse to produce a very high resistance in the circuit in a very short period of time (typically hundreds of µsec).

Dr.Latif Shaikh

Download