COMPLIANCE IN OPERATION Charles Workman, CHFM, CHSP, CHEP Director, Regulatory Programs Hospital Corporation of America 1 Introduction • Expected Outcomes from this presentation: – The attendees should be able to understand these processes at the conclusion of the presentation. – Activities that have combined maintenance requirements and compliance activities. – Techniques and resources to align vendors with compliance activities. – Methods to validate compliance on a continual basis. • Please ask questions at any time during the presentation, or • Save them for the end of the session. 2 CMS Memo 12-21: Intent and Content Intent: to allow the 2012 NFPA 101, 18/19.2.3.4 to be adopted as long as the criteria is met. • Smoke compartments are required to be fully sprinkled and automatic fire alarm system installed. Content: • Projections into the corridor shall be permitted for wheeled equipment: 3 − 6 feet corridors must maintain 60 inches clearance − 8 feet corridors must maintain 6 feet clearance • Fire plan addresses the relocation of the wheeled equipment • Limitations of the equipment: In use, Emergency equipment, Lift and Transport • Fixed equipment is allowed in the 8 foot corridors To Implement or Not? The decision must be made with the clinical staff and engineering so everyone understands the implications. Advantages Disadvantages • Free parking for wheeled equipment. • Items will collect in the corridors! • When implemented, NFPA 101, 7.1.10.1 will not apply, even though it is still in the 2012 edition of the code. • Obstructions to Fire Protection features and medical gas shut off valves must be prevented. 4 CMS Memo 13-58 Implementation • Medical Gas Master Alarms – Allows a Computer System to substitute for one of the Category 1 alarm panels. • Openings in Exit Enclosures – Mechanical room doors into stairwells. • EPSS Testing – Reduces the 2-hour to 1.5 hours. – Existing = 25% (30 Mins), 50% (30 Mins), 75% (1 hour). New = 50% (30 Mins), 75% (1 hour). • Doors – From single delayed door in an egress to multiple • Suites – Sleeping to 10,000 square feet • Extinguishing Systems – Electric Fire Pump to Monthly (Churn Test) – Waterflows to Semi-Annually • Clean Waste and Patient Record Containers – Capacity to 96 gallons from 32 gallons • Adoption of CMS Memo 12-21 5 Suite Adoption Issues – Dead End Corridors Existing Building – no limitations on distance Suite “A” Dead End Corridor Suite “B” Utilizing 2000 LSC for 5000 SF suites If Utilizing CMS Memo 13-58, distance must meet new occupancy requirements 6 Specifics of the Corridor CMS Memo • Fixed furniture: – Must be secured to the floor. – Must be located on one side of the corridor. – Space must be located to allow direct supervision from the nurse station. – Area cannot exceed 50 square feet. • This places the area under criteria for a Hazardous Area. (18/19.3.2.1) 7 Process for Implementation Key Actions If adopted, the language must be included under the “Additional Comments” section of the Basic Building Information (BBI) in the electronic Statement of Conditions (e-SOC). • Mark the clearance in the corridor. – Place colored tape on the ceiling tile framing to mark the threshold. • Develop fire plans for the individual clinical areas. • Assignment of person/s to remove equipment in the event of an emergency should be general and not specific. For example: – CNA’s on 3 South will move wheeled items to Nurse station. – Charge nurse will assign staff to remove equipment and place in vacant patient room. • Submit in the minutes of the EOC/Safety Committee the adoption of the Memo. 8 Fire Plan Example Fire Plan must include: 9 • Exit access, • Area to move wheeled equipment, • Areas of refuge (if meets the criteria of 7.2.12), • Access to a public way, • Elevator with firefighter service, • Two-way communication system, and • Must be protected by a 1-hour separation Fire Alarm Devices and Components EC.02.03.05 Includes EPs: • 1: Supervisory signals • 3: Duct detectors • 4: Audio/visual devices • 5: Off-site notification • 13: Kitchen systems • 14: CO2 systems Other components are covered in Fire Suppression Systems 10 • Testing and inspection requirements are detailed in NFPA 72, Chapter 7. (These include inspection and testing frequencies and procedures.) • EP 25 was directly translated from NFPA 72, specifically: – An inventory must be complete and accurate for all devices. (NFPA 72: permanent records, 7-5.2.2 (7) – “Designation of the detector(s) tested, for example, Tests performed in accordance with Section_____________.”) • The example provided in NFPA 72, Figure 7-5.2.2 will not be sufficient to satisfy an inventory. Fire Alarm and Devices Functionality The testing of the devices must correspond to the output of the fire alarm system. • It must be recorded that activation devices set off a sequence in the fire alarm system. • Supervisory signals must be tested to show a “global” activation of the system. (Requires action by occupants.) • The following table from NFPA 72 shows how initiating devices correspond to the fire alarm system and activate the notification devices. 11 12 Fire Suppression Inspections Inspection of Devices The components of the fire suppression system are required to be inspected as to their condition. • Sprinklers are required to be inspected from floor level annually. (2-2.1.1*) – Sprinklers with corrosion, foreign materials, paint, physical damage, or having the incorrect orientation must be replaced. • Gauges in wet pipe systems are required to be inspected monthly. (2-2.4.1*) – – Gauges must be in good condition. Normal water supply pressure must be maintained. • Gauges must be inspected Monthly and replaced or tested every 5 years. (2-2.4 and 2-3.2*) – 13 Gauges testing outside 3 percent of the full scale must be recalibrated or replaced. Fire Suppression Inspections (continued) Inspection of Devices • Hydraulic nameplate must be inspected quarterly. (2-2.7*) – Must be legible and securely attached to the sprinkler riser. • Sprinkler spares shall be inspected for quantity. (2-4.1.5) For protected facilities, required quantities are: – – – (a) With less than 300 sprinklers — no fewer than 6 sprinklers (b) With 300 to 1000 sprinklers — no fewer than 12 sprinklers (c) With more than 1000 sprinklers — no fewer than 24 sprinklers • A special sprinkler wrench for installing and removing sprinklers is required. (2-4.1.6*) – 14 One sprinkler wrench for each type of sprinkler installed. General Recommendations for Improvement EC.02.03.05 The vendor must follow EP25 and the language from NFPA 72 (1999 edition): • Test methods must be identified (Table 7-2.2) • Visible frequencies must be identified (Table 7-3.1) • Testing Frequencies must be identified (Table 7-3.2 and CMS memo 13-58) • EP25 is TJC trying to convey the language from NFPA 72, 7-5.2 • 15 items must be reviewed and documented (see NFPA 72 which states “designation of detector(s)”) • Example inspection and testing form (Figure 7-5.2.2) If the vendor is not providing the information as per these references, they are in breach of the contract. 15 Utility Failure Policy and Matrix • Policy reads “Follow the Utility Failure Matrix.” • Matrix is located with the Administrator on Call, PBX Operator, and Engineering UTILITY FAILURE MATRIX Call House Operator 24/7 House Operator makes announcement on Public Address System House Operator calls "on duty" Engineering Mechanic using 2-Way radio Failure Code Red Fire Alarm* What to Expect 1) Switch to Security Call XXXX. Defend in place channel or evacuation. 2) Call Fire Department 3) LiveProcess Msg Many lights & Electrical Power equipment out. Only Failure -Emergency RED electrical Generators Working receptacles work 16 Operator to Contact Code Yellow 1) Engineering 2) Clinical Engineering Admin. On Call Determine evacuation needs and medical priorities. Responsibility of Staff Operator via (Comm tool) Respond with tools to the impacted scene. Radio to Operator and Fire Panel. Switch to Security channel; 1) Click "call code" Security to meet the Fire Department. 2) Select Code Red One staff member to Fire Computer Room, if available. Ensure that life support systems Have staff check that "life are on emergency power (RED support equipment" is plugged Outlets). Ventilate patients by into Red Outlets. hand. Complete cases in progress ASAP. 1) Click "Communications" 2) Send a Notification 3) Type Message 4) Select group "Code Yellow Internal - Power Failure with Generators Working" General Recommendations for Compliance Interim Life Safety Measures (ILSM) ILSM must be evaluated and documented. • The ILSM evaluated box must be entered on the electronic Statement of Conditions (eSOC) • Not all 11 elements in LS.01.02.01 are applicable to all ILSM conditions We need to develop more realistic measures! 17 Example If penetrations are present in a fire or smoke assembly, the integrity has been compromised. The Life Safety Code was designed to provide a sequence of measures. Measure: maintain the next lower protective level until the penetrations are corrected (e.g., next smoke barrier or smoke partition). Evaluation of ILSM Made Simple Criteria Criteria Job Length Greater than 3 months From 1 to 3 months Less than 1 month Less than 1 week Points 20 15 10 0 0 Criteria 2) Impact on Patient Care Work is in patient area Near ambulatory patients near visitor / staff areas Near staff only 0 4) Hazards of Work Activity Methods Open flame Heat producing / elec welding Low Hazards Only Points 20 15 10 0 Score 15 Points 0 Criteria 2) Impact on Patient Care Work is in patient area Near ambulatory patients near visitor / staff areas Near staff only 0 4) Hazards of Work Activity Methods Open flame Heat producing / elec welding Low Hazards Only 20 15 10 0 0 6) Impact on Exiting (Building Exit) Exit blocked Exit obstructed Exit penetrated None 25 20 15 0 15 0 0 8) Impact on Fire Alarms Multiple zones One zone In zone - no working system None 20 15 5 0 0 10) Storage Areas Multiple storage areas in zone One in zone + adjacent Adjacent areas only None 20 15 10 0 0 1) Job Length Greater than 3 months From 1 to 3 months Less than 1 month Less than 1 week 20 15 10 0 3) Hazards of Work Activity Materials Hazards of Work Activity Materials Unprotected flammable Excessive combustible Low Hazards Only 20 15 0 20 15 10 Unprotected flammable Excessive combustible Low Hazards Only 20 15 0 25 15 10 0 Impact on Exit Access (Corridors) Redirect / reroute exit Redirected exits not visible Exit access width reduced None 25 15 10 0 Temp Work Activity Partitions Multiple partitions in zone One partition No partition necessary Access to Emergency Department & Building Exterior Emergency Dept. blocked Building exit blocked > 50' Building exit blocked < 50' None 20 15 0 ILSM Required? 25 20 15 0 0 8) Impact on Fire Alarms Multiple zones One zone In zone - no working system None 20 15 5 0 10) Storage Areas Multiple storage areas in zone One in zone + adjacent Adjacent areas only None 0 0 Missing Significant Compromise Minor Penetrations None 0 Redirect / reroute exit Redirected exits not visible Exit access width reduced None 25 15 10 0 9) Temp Work Activity Partitions Multiple partitions in zone One partition No partition necessary 20 15 0 0 0 25 20 10 0 NOTE: 1) A score of 100 points or more on this Preliminary Life Safety Assessment form will require a more detailed review and evaluation by the Project Manager, and may result in implementation of ILSM. 2) A score greater than 0 in Criteria Sections 5, 6, 7, or 8 above will require an ILSM Evaluation regardless of total points scored. 0 15 Building Exterior Emergency Dept. blocked Building exit blocked > 50' Building exit blocked < 50' None 25 20 10 0 15 NOTE: 1) A score of 100 points or more on this Preliminary Life Safety Assessment form will require a more detailed review and evaluation by the Project Manager, and may result in implementation of ILSM. 2) A score greater than 0 in Criteria Sections 5, 6, 7, or 8 above will require an ILSM Evaluation regardless of total points scored. 0 Preliminary Life Safety Assessment Score 30 0 0 NO FALSE Sum o f 5, 6, 7, 8 Impact o n egress? ILSM Required? 18 25 15 10 0 7) Impact on Exit Access (Corridors) 20 15 10 0 Score 11) Access to Emergency Department & Preliminary Life Safety Assessment Score Sum o f 5, 6, 7, 8 Impact o n egress? 0 6) Impact on Exiting (Building Exit) Exit blocked Exit obstructed Exit penetrated None 20 15 10 0 0 5) Fire / Smoke Separations Fire / Smoke Separations Missing Significant Compromise Minor Penetrations None Points 15 15 YES TRUE Building Maintenance Program? • Do we need one and how do we implement one that is effective? – Doors are verified during fire drills: • Corridor doors positively latch • Some barrier doors close upon activation of fire alarm • Exits and hazardous areas self close and latch – The inventory is assigned to each floor – Smoke Barriers – Survey once a year – Fire Barriers surveyed once a year – The main focus is being Proactive – Above the ceiling access control 19 Above the Ceiling - Permit or Tagging Pro-Active • Purpose: Control activities that penetrate smoke and fire barriers. • Being proactive is the only solution. • Inspections are to measure the expectations of the barrier integrity. • Process must be discussed with Infection Prevention Professionals to determine level of control to access the ceiling spaces. – Permit Process: Detailed description of activities and location of work – Tagging Process: Identify the area on drawings, number tags, evaluate with ICRA 20 Permit Process • • • • • Detailed description of area. Work being completed All areas requiring inspection Signature of Engineering representative Retain the Permit? • Once work is completed, there are No requirements for record retention. 21 Permit Tagging Process • Tags are two-sided • Tag number is identified on a set of drawings • Tag is effective for 24 hours only • At the end of each day, tags are returned • If area involved Smoke/Fire rated walls or partitions - Inspect • If area did not involve Smoke/Fire rated walls or partitions • Discard the tag 22 ICRA and Tag Process Above the Ceiling ICRA Process Start Obtain an Above the Ceiling Tag and complete the log Inspection Only? Yes Review the ICRA, Complete log for ICRA review. No Determine Group level on ICRA form No Group I or II? Complete ICRA form for Group III or IV. Process with Infection Prevention Fill in Group on back of tag. Close tag and ICRA permit upon completion of work. Verify if Smoke or Fire Rated Assemblies are impacted Fire stopping must be provided by contractor before permits are closed out. 23 If work is Group I or II, fill in group on back of tag Yes Drawings for Tagging Process • Have a set of life safety drawings laminated • Identify the area being accessed with erasable ink • End of day once inspected/not inspected • Erase the drawings at the end of the day • Recommend a reward program for all staff for access to the ceiling – Meal tickets – Something from gift shop 24 After Work is Complete No Inspection 25 3945 3945 Inspection General Recommendations for Improvement Medical Gas Systems Per NFPA 99 (1999 edition): • 4-3.1.2.14 Identification • “Piping shall be identified by stenciling or adhesive markers” • All locations where the piping is to be marked are listed • If the medical gas testing company writes on their report that the systems were inspected and tested in accordance with NFPA 99, they should identify missing labels If the testing company does not list missing labels, they are in breach of the contract. 26 General Recommendations for Improvement (cont’d.) LS.02.01.30 Per NFPA 101, (2000 edition) 18/193.6.2: • The smoke compartment must be identified as being sprinkled or non sprinkled • The ceiling is allowed to terminate above the ceiling, in an existing building, the smoke compartment must be sprinkled • In new buildings, sprinklers are not optional; the building must be fully sprinkled Identifying sprinkled area on drawings will alleviate the finding for corridor walls that Do Not go from deck to deck. 27 General Recommendations for Improvement (cont’d.) EC.02.03.05 • Per NFPA 25 (1998 edition) 2-2.1.1, “Sprinklers shall be inspected from the floor level annually.” • If the fire suppression vendor presents you with a document that they have performed sprinkler testing and inspection or water-based fire protection system testing and inspection in accordance with NFPA 25, they are in breach of their contract! We must hold contractors accountable for the service they are to provide! 28 Physical Environment and Utility Systems Physical Environment Definition Reference CMS 29 Utility Systems Design and Operation Conditions of Participation Design The Joint Commission Standards Operations State Regulations Variables to Consider Conditions of Participation (COP) CMS • Language from the CMS COP: − CMS COP 482.41 (Physical Environment) allows the hospital to decide on which Guideline they choose. − Each operating room should have separate temperature control. Acceptable standards such as from the Association of Operating Room Nurses (AORN) or the Facilities Guidelines Institute (FGI) should be incorporated into hospital policy. • Designation of the Guideline being utilized. • A policy must be implemented reflecting the specific guideline • Other Acceptable standards: 30 • Association for the Advancement of Medical Instrumentation (AAMI) • American Institute of Architects (AIA) Joint Commission Standards Specific Standards • EC.02.05.01 EP 6: – – • • 3 The EP has this designation, indicating it is a Direct Impact for scoring EC.02.06.01 EP 13: – The hospital maintains ventilation, temperature, and humidity levels suitable for the care, treatment, and services provided. – Not a Direct impact! EC.02.06.05 EP 1: – 31 In areas designed to control airborne contaminants (such as biological agents, gases, fumes, dust), the ventilation system provides appropriate pressure relationships, air-exchange rates, and filtration efficiencies. Planning for New, altered or renovated spaces use: State rules and regulations, Facility Guidelines Institute (FGI) or a reputable standard or guideline. State Regulations • Variance from State to State: – Florida utilize a State Operations Manual developed and enforced by Agency for Health Care Administration (AHCA) – Texas utilizes a State Operations Manual developed and enforced by the Department of State Health Services (DSHS). Texas Administrative Code (TAC) – Kentucky utilizes a State Operations Manual developed and enforced by the Office of the Inspector General (OIG). • The Kentucky State design laws state the use of the AIA 2006 edition 32 Utility Systems - Design • Design: The parameters in which the HVAC systems were designed is dependent on the State. • Example standard from ASHRAE 170, Attachment D to 2010 FGI: 33 Utility System - Operation Define the Needs • The needs of the patient are a consideration: – The primary reason for the lower temperatures are for the surgeons! – During Cardiac cases, the physicians like to lower the temperature to stop the heart and reduce the organs need for oxygen. – Before closing, the physician wants the temperature raised to increase blood flow and reduce the possibility of hypothermia. – The colder temperature will keep the bacteria count down. – Some consideration must be given to cardiac catheterization cases where all of the clinical staff are wearing lead shielding to prevent excessive dosing from the “C” arm. 34 Variables in Operations Variables: The system was designed for one range and the demand is much lower or higher from the clinical staff! • If the temperatures and relative humidity fall out of range once the physicians request a lower temperature, the HVAC system is not operating within the design parameters. Next Steps: • Present to the clinical staff the following: • Once a parameter is requested outside of the design range, it is no longer an engineering issue! • The clinical staff must meet and decide if they are comfortable with the operating room being out of parameters. • The decision to continue the case must be with the clinicians. 35 Where are Eye Wash Stations Required? 36 Purpose EC.02.02.01 • Emergency first aid as required by OSHA. • The Material Safety Data Sheets (MSDS) describes the first aid actions. • Evaluate the MSDS and determine if flushing is required for a certain period of time. • If no time period is identified in the MSDS. • Flushing station is adequate until the person is taken to the emergency room. 37 Questions? • I can be reached at: • Charles.workman@hcahealthcare.com • 615.344.1187 Thank You 38