Presentation 9 Hydronic heating 2693KB May 22 2013 06:09:15

advertisement
1
HVACR216 - Hydronics
Hydronic Heating
Hydronic Heating Systems
• Hydronic heating systems rely on circulating
water or steam to deliver heat to the remote
locations where warming of a space is desired.
2
Hydronic Heating Systems
3
4
Hydronic Heating Systems
The Heat Source
• Heat energy is transferred from the heat
source (burners) to the water in the boiler.
– There are two different types of boilers on the
market today.
• High mass
• Low mass
5
The Heat Source
• Cast iron (high mass) boilers are most
commonly boiler found in residential
applications.
– Residential cast iron boilers typically hold
between 10 - 15 gallons of water.
6
7
Cast iron (high mass) boiler
8
Cast iron (high mass) boiler
• The boiler manufacturer supplies us with a booklet
that is sent with the boiler.
• It is important that these instructions are followed
when the boiler is installed.
• This booklet also contains information about
proper boiler maintenance or troubleshooting.
9
The Heat Source
• Stainless steel (low mass) boilers are
gaining popularity due to the higher
efficiencies being obtained today by many
different manufacturers.
– Low mass boilers hold between 4 - 7 gallons
of water.
10
Low mass boiler
11
Hydronic controls
• Thermostat
– The heating thermostat, whether it is a modern
digital, snap action or mercury bulb type, is a
close on temperature drop device.
12
Thermostat types
• Digital
Snap action Mercury bulb
Hydronic controls
• Aquastat
– The Aquastat is a temperature-sensing
switch that is responsible for cycling
the boiler on and off to keep the water
in the boiler close to the desired
temperature.
– It may be strapped onto a pipe or
immersed in the water via a well.
13
14
Aquastat types
• Immersion
Strap-on
Triple
Low Water Cutoff
• The Low Water Cutoff is responsible for deenergizing the combustion operation in the event
the water level in the system falls below the
desired level established by the manufacturer.
• The Low Water Cutoff is a safety device that
code officials require to be installed on all
hydronic systems.
• The Low Water Cutoff can be a stand alone
device or a built in part to the Aquastat.
15
Low Water Cutoff
16
17
High limit switch
• Manual reset high limit switches are required
in light commercial applications.
Circulator Pumps
• The circulator pump is used to move water
throughout the hydronic system.
• The circulator pump is also called a
centrifugal pump.
• The centrifugal pump is made up of a motor,
a linkage and an impeller.
18
19
Circulator pump styles and brands
• Taco 007
Taco 110
Grundfoss
20
Circulator location
• Early circulators were large and heavy. The
easiest place to mount them was on the return
piping close to the boiler.
• Modern locations for a circulator is on the supply
piping just beyond the air eliminator and the
expansion tank.
21
Pump control panels
• Circulator pump panels (switching relays)
control the operation of multiple pumps
(zones) at one time.
– A thermostat located in the space to be heated
calls for heat and the zone panel turns on the
correct circulator for that space.
22
Taco zoning controls
23
Zone valves
• Zone valves are sometimes used to allow
or dis-allow water from flowing through a
system.
• Zone valves are either directly controlled
by a thermostat or a zone panel
24
Zone valve brands
•
Taco
Honeywell
B&G
25
Cut-away picture of a zone valve
26
Zone valve panels
• Zone valves can also be controlled by a
panel much like the circulator pumps.
Non-electrical components
• Expansion Tanks
– There are two types of expansion tanks
• Standard expansion tank
– Nothing more than a large tank located
somewhere above the boiler.
• Diaphragm expansion tank
– Divided into two sections separated by a
rubber, semi-permeable membrane.
– One side of the tank contains air and the
other side is open to the water circuit.
27
Modern diaphragm expansion tank with air scoop and vent.
28
29
Automatic water feed
• Automatically maintains the preset water
pressure in the system.
• Usually 12-14 psi
Combination Auto Feed and Backflow Preventer
The backflow preventer allows water flow only
in one direction similar to a check valve.
Its very common to see the backflow preventer
and the water feeder together like this.
30
31
Pressure-reducing Valve
• Another name for the water feeder is the
pressure reducing valve.
• The pressure-reducing valve automatically
lowers the pressure of the supply water to the
pressure at which the boiler is designed to
maintain.
32
Pressure reducing valve
Pressure Relief Valve
• The pressure relief valve is designed to
open if the pressure in the system
reaches the set point on the valve.
– The is the most important safety
device installed on a hydronic
system.
33
Pressure Relief Valve
34
Flow-Control Valve
• The flow-control valve controls flow in a
hydronic system.
• The flow control valve is also called a
check valve or flow check.
35
Flow-Control Valve types
36
Balancing Valve
• Balancing valves are used to even the
water flow through each branch of the
circuit.
• Balancing valves are installed in each
branch of the circuit and are manually
adjusted.
37
38
Balancing Valve
Download