Assumption University Thailand EE4503 Electrical Systems Design Load Calculation 1 Assumption University Thailand Topics • Load Calculation (E.I.T.) • Load Calculation by Adding Branch Circuit • Load Calculation for condominium • Load Estimation 2 Assumption University Thailand Load Calculation (E.I.T.) lighting Building Residential Area Lighting (VA) 2,000 > 2,000 Hospital 50,000 > 50,000 Hotel, Condominium 20,000 20,001 – 100,000 > 100,000 Warehouse 12,500 > 12,500 Other Demand Factor (%) 100 35 40 20 50 40 30 100 50 100 3 Assumption University Thailand Load Calculation (E.I.T.) receptacles Non residential area Total Load from Demand Receptacle Factor (%) 100 10kVA > 10kVA Residential area 50 𝐿𝑚𝑎𝑥 + 0.4𝐿𝑟 4 Assumption University Thailand Load Calculation (E.I.T.) Demand Factor of Appliances Building Residential Area Lighting (VA) Kitchen Hot Water Air Condition Office, Store Kitchen Hotel, Other Demand Factor (%) 10A+30% of extra first two + 25% of other 100 First maximum device + 80% of the second max. + 60% of the rest Hot Water 100% of the largest + 25% of the rest Kitchen Same as Office Hot Water Same as Office Air Condition 75 5 Assumption University Thailand Load Calculation by Adding Branch Circuit • Add of all branch circuit • Then multiply by the demand factor Number of Panels 1 2-3 4-6 7-10 > 10 Demand Factor (%) 100 90 80 70 60 6 Assumption University Thailand Load Calculation for Condominium • Load: common area + individual room Type Residential Number of Rooms Coincident Factor (%) 1-10 90 11-20 80 21-30 70 31-40 60 > 41 50 Non residential 1-10 100 > 11 85 7 Assumption University Thailand Load Estimation • Quick estimate of the load • Many common tables, just refer to one 8 Assumption University Thailand Load Estimation http://static.schneider-electric.us/assets/consultingengineer/appguidedocs/section3_0307.pdf 9 Assumption University Thailand Load Estimation http://static.schneider-electric.us/assets/consultingengineer/appguidedocs/section3_0307.pdf 10 Assumption University Thailand Load Estimation (E.I.T.) lighting Type School Computer Center, Meeting Room, Kitchen Walk way, Balcony Cafeteria Hospital – Operation Room Hospital – Patient Room Office, Shopping Store Drawing Room Laboratory VA/m2 25 20 8 18 100 14 30 60 50 11 Assumption University Thailand Load Estimation (E.I.T.) receptacles Type Auditorium, Cafeteria, Church, Sport Complex Drawing Room Hospital Machine Room Office School VA/m2 2 7 10 15 10 7 12 Assumption University Thailand Load Estimation (E.I.T.) air condition Type Bank Department Store Hospital Office Grocery Store Cafeteria VA/m2 80 50 70 70 90 90 13 Assumption University Thailand Reference • Electrical Systems Design: ประสิ ทธิ ์ พิทยพัฒน์ 14