Dynamic VAR’s [D-VAR] What are D-VAR Devices? • Dynamic VARs… Fully integrated modular STATCOM with proprietary 3X overload • Instantaneously injects precise amounts of reactive power into a network • Can be seamlessly integrated with static shunt devices as part of a larger solution Ref. American Superconductors Transmission Problems That D-VAR Can Solve: •Voltage Stability / Voltage Collapse - •Uncontrolled rapid decline in system voltage • Steady State Voltage Regulation - • Wind farms, radial lines, etc... • Import/ Transfer Capability Restrictions • Limited ability to reliably import, export, or transfer power • Mitigate voltage flicker/ power quality - • Wind farms, industrial facilities Ref. American Superconductors Single Phase DC/AC Inverter + 1A 2A Lf Cf DC 1B AC 2B - • Devices 1A, 1B, 2A and 2B are IGBT’s acting as fast switches • Capacitors hold DC charge • Lf and Cf are AC smoothing filter components Ref. American Superconductors D-VAR Unit Proprietary Power Electronics Technology Each D-VAR system has continuous reactive power… with temporary overload capability up to 3 times its continuous rating. Each phase is individually controlled. Ref. American Superconductors East End of Long Island Southold Orient Point Generating Peconic Areas of Voltage Collapse Concerns Mattituck Tuthill Riverhead Bridgehampton Amagansett East Hampton Buell Southampton Tiana Double Circuit 69kV fault Installation Site Ref. American Superconductors Hero Proposed Solution for the East End Voltage Issues 8 MVA D-VAR Installed at Bridgehampton Easthampton 69 kV To Bridgehampton To Buell Load 13.8 kV Load To East Hampton Diesels 13.8 kV VT 8 MVA D-VAR 480-13800 V Padmount Transformers VT Inputs to DVAR for Voltage Control Ref. American Superconductors Northeast Utilities Danbury Area D-VAR solution by American Superconductors Frost Bridge Long Mountain Carmel Hill G Rocky River West Brookfield Shepaug G Bates Rock Stony Hill G Plumtree 345 kV 115 kV Hydro Generator Substation Trans. Capacitor Distrib. Capacitor D-VAR TM Northeast Utilities Danbury Area Comparison of Load-flow Results Per Unit Voltages Solution Problem SW Connecticut Imports Ref. American Superconductors D-VAR™ Solution’s Dynamic Voltage Support Provides a total of -48 MVAR/+84 MVAR 600V 34.5 kV 26 MW 97% Lagging PF T1 60/90 MVA with LTC 9 X 3.6 MVAR 26 units 115 kV VTs Utility Interconnection Point The dynamic MVARs are sized to prevent the wind farm from tripping off-line for the faults that the utility specified. 34.5 kV UDG collector system 600V Joslyn VBM Switch 28 MW 97% Lagging PF 28 units 4x2500 KVA 34500-480V padmount transformers 8/24 MVAR D-VAR D-VARs . Dynamic 2 x 8 x 3 = 48 MVAR 8/24 MVAR D-VAR 600V 26 MW 97% Lagging PF 26 units 1200 Amp Breaker Joslyn VBU Switch Dynamic Capacitor Banks 2 x 18 MVAR = 36 MVAR Caprock Wind Farm, New Mexico; D-VAR built by American Superconductors