Thermodynamics (ME2210-002) Spring 2026
Exam 3
April 9, 2026 (Thursday) 8:00 am – 9:15 am
Print your name:
Notes:
This exam consists of two problems with a total of 20 points.
This exam is open-book and closed-notes. The use of any unauthorized information through smart
phones, computers, tablets, or other devices is considered a violation of the academic integrity.
The following items are not allowed: lecture notes, solutions to homework, and summary sheets.
Illegible answers will not be graded.
Show all steps to receive full credit. Answers without descriptions of a solution process will not
receive credit. Likewise, the use of incorrect equations without showing the derivation of the equation
will receive no partial credit.
Giving or receiving unauthorized aid or assistance on exams are violations to the academic integrity.
If you need more space, you may write your solutions on the back of the exam sheets, or attach
additional sheets. Write your name on all attached sheets.
The following unit conversions may be useful:
1 kW = 1 kJ/s;
1 kJ/kg = 1000 m2 /s2
1. (10 points) Ammonia enters a compressor operating at steady state as saturated vapor at
a pressure of 0.8 bar with a mass flow rate of 2.5 kg/s. Ammonia exits at 4.5 bar, 80◦ C.
Due to imperfect insulation, there is an energy transfer by heat from the compressor to the
surroundings at the rate of 92.88 kW. Changes in kinetic and potential energy from inlet to
exit can be ignored. Note that Ammonia cannot be modeled as an ideal gas. Determine
(a) (4 points) the volumetric flow rates of Ammonia at the inlet and the exit, each in m3 /s.
[Hint: volumetric flow rate at the inlet is NOT equal to the volumetric flow rate at the exit.]
(b) (6 points) the power input to the compressor, in kW.
1
2. (10 points) A parallel-flow heat exchanger operating at steady state is shown in Fig. 1.
In the heat exchanger, Refrigerant 134a (R-134a) flows through a cooling tube. Refrigerant
134a enters the tube at 3.2 bar with a quality of 0.1, and exits at a pressure of 2 bar and
a temperature of 10◦ C. Air enters through a separate tube with a volumetric flow rate of
25 m3 /min at 42◦ C, 1 bar, and exits at 27◦ C, 0.95 bar. Air can be modeled as an ideal
gas, but Refrigerant 134a cannot be considered an ideal gas. Heat transfer at the outer
surface of the heat exchanger can be ignored. Kinetic and potential energy effects can also
be neglected. Determine
(a) (3 points) the mass flow rate of the air, in kg/min.
(b) (7 points) the rate of heat transfer, in kJ/min, between the air and refrigerant. [Define
the system first. Answers without a clear definition of the system will not receive partial
credit.]
air
R-134a
R-134a
air
Figure 1
2
Solutions
1. (10 points) Ammonia enters a compressor operating at steady state as saturated vapor at
a pressure of 0.8 bar with a mass flow rate of 2.5 kg/s. Ammonia exits at 4.5 bar, 80◦ C.
Due to imperfect insulation, there is an energy transfer by heat from the compressor to the
surroundings at the rate of 92.88 kW. Changes in kinetic and potential energy from inlet to
exit can be ignored. Note that Ammonia cannot be modeled as an ideal gas. Determine
(a) (4 points) the volumetric flow rates of Ammonia at the inlet and the exit, each in m3 /s.
[Hint: volumetric flow rate at the inlet is NOT equal to the volumetric flow rate at the exit.]
(b) (6 points) the power input to the compressor, in kW.
Solution: (This problem is a modified version of Homework 3, Problem 4)
(a) Consider the compressor and the Ammonia inside as the control volume. Apply the mass
flow rate balance equation:
X
X
dmCV
=
ṁi −
ṁe .
dt
i
i
(1)
Impose the assumptions of the problem: steady state; single inlet and exit. Equation (1)
implies ṁi = ṁe = ṁ = 2.5 kg/s.
The mass flow rate at the inlet (labeled as 1) and exit (labeled as 2) can be determined from:
ṁ =
A2 V2
A1 V1
=
.
v1
v2
(2)
If we can find v1 and v2 , we can identify the volumetric flow rate A1 V1 and A2 V2 .
At the inlet, ammonia is a saturated vapor at p1 = 0.8 bar. From Table A-13, we find
v1 = 1.4020 m3 /kg.
At the exit, Table A-14 indicates that corresponding to the pressure of 4.5 bar, the saturation
temperature is Tsat = 1.25◦ C. Since T2 = 80◦ C > Tsat , refrigerant at the exit is a superheated
vapor.
From Table A-15, we find, corresponding to p2 = 4.5 bar and T2 = 80◦ C: v2 = 0.37369 m3 /kg.
So Eq. (2) leads to
A1 V1 = ṁv1 = 3.5050 m3 /s,
A2 V2 = ṁv2 = 0.9342 m3 /s.
(b) Apply the energy rate balance for a control volume:
X X 1 2
1 2
dECV
ṁi hi + Vi + gzi −
= Q̇CV − ẆCV +
ṁe he + Ve + gze . (3)
dt
2
2
e
i
Impose the assumptions of the problem: steady state; single inlet and exit; negligible change
in kinetic and potential energy. Equation (3) can be simplified into
ẆCV = ṁ (h1 − h2 ) + Q̇CV .
(4)
At the inlet, from Table A-14, we find h1 = 1391.78 kJ/kg.
3
At the exit, from Table A-15, we find h2 = 1634.63 kJ/kg.
The heat transfer for the system is Q̇CV = −92.88 kW. (Note the minus sign.)
Substituting these values into Eq. (4), we find
ẆCV = −700.0 kW.
So the power input to the compressor is 700.0 kW.
2. (10 points) A parallel-flow heat exchanger operating at steady state is shown in Fig. 1.
In the heat exchanger, Refrigerant 134a (R-134a) flows through a cooling tube. Refrigerant
134a enters the tube at 3.2 bar with a quality of 0.1, and exits at a pressure of 2 bar and
a temperature of 10◦ C. Air enters through a separate tube with a volumetric flow rate of
25 m3 /min at 42◦ C, 1 bar, and exits at 27◦ C, 0.95 bar. Air can be modeled as an ideal
gas, but Refrigerant 134a cannot be considered an ideal gas. Heat transfer at the outer
surface of the heat exchanger can be ignored. Kinetic and potential energy effects can also
be neglected. Determine
(a) (3 points) the mass flow rate of the air, in kg/min.
(b) (7 points) the rate of heat transfer, in kJ/min, between the air and refrigerant. [Define
the system first. Answers without a clear definition of the system will not receive partial
credit.]
Solution: (This problem is a modified version of of Homework 3, Problem 5)
(a) Consider the mass flow rate equation of air at the inlet # 3, and apply the ideal gas
model for air:
ṁ3 =
A3 V3
v3
p3 v3 = RT3 ⇒ v3 =
RT3
,
p3
we can determine the mass flow rate of air as
ṁ3 =
A3 V3 p3
= 27.65 kg/min.
RT3
(b) Consider air as the control volume. The control volume has 1 inlet and 1 exit.
Apply the energy rate balance for the control volume:
X X dEair
1 2
1 2
= Q̇air − Ẇair +
ṁi hi + Vi + gzi
−
ṁe he + Ve + gze . (5)
dt
2
2
e
i
Impose the assumptions of the problem: steady state; single inlet and exit; negligible change
in kinetic and potential energy; no work/power delivered by/to the system (Ẇair = 0). Note
that we cannot assume the CV is insulated (Q̇air ̸= 0). Equation (5) can be simplified into
0 = Q̇air + ṁ3 (h3 − h4 ).
⇒ Q̇air = ṁ3 (h4 − h3 ).
4
For air as an ideal gas, the specific enthalpy is a function of temperature only, and its value
can be determine from the property tables. From Table A-22, we find
h3 = 315.27 kJ/kg, h4 = 300.19 kJ/kg.
Therefore, the rate of heat transfer is
⇒ Q̇air = ṁ3 (h4 − h3 ) = −417.0 kJ/min.
So the rate of heat transfer from the air to the refrigerant is 417.0 kJ/min.
5