Electrical Installation (EEng5143) — Assignment 1
General Instructions: Write your answers in a clear, organized manner. Show all calculations stepby-step (including units) so they can be easily followed. When necessary, state and justify any
assumptions
1. A room measuring 12 m × 9 m requires an illuminance of 50 lux on the floor. A total of 36
identical lamps are used. If 50% of each lamp’s emitted luminous flux falls on the floor
and the maintenance factor is 0.8, determine the luminous intensity of each lamp (in
candela), assuming each lamp can be approximated as a point source.
Answer
Given
Required
The illumination required, E = 50 lux (lumens/m²)
The luminous intensity of each lamp
Working area, A = 12m x 9m = 108m²
Number of lamps, N = 36
Coefficient of utilization, CU = 50%= 0.5
maintenance factor or LLF = 0.8
solution
Total flux required at the floor
Φ(floor) = E x A = 50 x 108 = 5400 lm
Flux emitted per lamp
Each lamp delivers 50% x 0.8 = 40% of its total emitted flux to the floor:
36 x 0.4 x Φ(lamp) = 5400 => Φ (lamp) = 5400 / 14.4 = 375 lm
Luminous intensity (I)
I = Φ(lamp) / (4 π) = 375 / (4 π)= 29.84 cd per lamp
Or
π΄∗πΈ
108∗50
Lumen output of the lamp, Ln = πΌπ∗ππ’∗πΏπΏπΉ= 36∗0.5∗0.8 = 375 lumen
Power of lamp in candela = Lumen output of lamp/4π = 275/ 4π = 29.84 cd per lamp
2. An incandescent lamp hangs from the ceiling. A small horizontal screen on a bench is 2 m
vertically below the lamp and receives an illuminance of 63.5 lux. The screen is then moved 1.5
m horizontally along the bench. Assuming the lamp behaves as a point source, calculate the
illuminance at the new position.
Answer
Given
Required
Assume that, initially screen is at position A
Illuminance at point B = EB
Illuminance at point A = EA = 63.5 lux
Distance between screen & lamp = dA = h = 2m
Solution
Luminous intensity of lamp = I = EA x dA² (From inverse square law, E = (I/d²)
= 63.5/2² = 254 candela
When the screen is moved horizontally a distance of 1.5m, let the new position be B
Now, the distance between lamp & screen = dB = √ (2² +1.5²) = 2.5m
Illuminance at point B = EB = (I/dB²) cosθ
But cosθ = h/dB = dA/dB= 2/2.5=0.8
i.e., EB = (I/dB2) x dA /dB = (I x dA)/dB³ = (254 x 2)/2.5³ = 32.5 lux
or EB=
(πΌ π₯ πππ π)
ππ΄²
=
254 π₯ 0.8
2.5²
203.2
= 6.25 = 32.5 lux
3. Two identical light sources, each with a uniform intensity of 600 cd, are mounted at a height of
8 m and spaced 30 m apart. Calculate the total illumination:
(a) directly beneath one of the lamps, and
(b) at the point midway between the two lamps.
Answer
Given
Luminous intensity of lamps = I1 = I2 = 600 cd
Mounting height, h = 8m
spacing = 30 m
solution
a) Illumination directly underneath the source 1
E = Illumination underneath source 1 due to source 1 + Illumination underneath source 1 due to
source
Illumination underneath source 1 due to source 1 = I1 /d1² (here d1 = h) = 600/8² = 9.4 lux
Illumination underneath source 1 due to source 2 = (I2/d2²) cosθ
From figure, d2 = √ (30² + 8²) = 31m
cosθ = 8/d2 = 8/31 = 0.258
Illumination underneath source 1 due to source 2 = (I2/d2²) cosθ = (600/31²) x 0.258 = 0.161 lux
Illumination directly underneath the source 1, E = 9.4 + 0.161 = 9.561 lux
b) Illumination at midpoint due to the two sources
Distance between midpoint & each light source, d = √ (15² + 8²) = 17m
Cosθ = 8/17 = 0.47
Now, Illumination at a midpoint due to the two sources,
E = illumination due to source 1 + illumination due to source 2
= (I1/d²) cosθ + (I2/d²) cosθ = (600/17²) x 0.47 + (600/172) x 0.47 = 1.95 lux
4. An office 30 m × 15 m is to be illuminated using twin 40 W fluorescent luminaires, each
luminaire having a total luminous flux of 5600 lumens. The luminaires are mounted so that the
working plane to luminaire height is 3 m, and the required average illuminance on the work plane
is 240 lux. Assume a coefficient of utilization (CU) of 0.6 and a maintenance factor (MF) of 0.8.
The building height is 5 m and the spacing-to-mounting height ratio (SHR) is 1.25.
(a) Determine the number of luminaires required to meet the specified average illuminance.
(b) Using the given SHR, sketch a suitable layout for the luminaires across the floor plan and
justify your spacing.
(c) Repeat (b) using edge distance/offset from wall, same for both ends and deT = deA = 0.3S.
Answer
Given
Working area, A = 30m x 15m = 450m²
Required illumination level, E = 240 lux
Power per lamp (two lamps per luminaire) =40W
Lumen output of lamp (luminous flux per lamp), Ln = 5600 lumens
Coefficient of utilization, CU = 0.6
Maintenance factor, MF or Light Loss Factor (LLF) = 0.8
Mounting Height (H) =3m
Spacing -to-mounting -height ratio (SHR) = 1.25
Solution
A. Number of lamps required, π =
π΄∗πΈ
πΏπ∗πΆπ∗πΏπΏπΉ
=
450∗240
5600∗0.6∗0.8
≈ 40.18 lamps = 41 luminaires
required
B. Layout using the spacing-to-mounting-height ratio (SHR)
Maximum spacing allowed: S(max) = SHR x Hm = 1.25 x 3 = 3.75 m
We choose 8 colums
οΌ Along 30m: 8 columns => sx =30/8=3.75m (at the SHR limit)
οΌ Along 15m: 5 rows => sy=15/5=3.0m (within limit)
οΌ Grid: 8 x 5= 40 luminaries close to the required 41 – acceptable engineering
rounding
(c) Layout with Specified Edge Distance deT = deA = 0.3S
πΏ
L=(n-1) S + 2(0.3S) =(n-0.4) S => S=π−0.4
οΌ Along 30m, try n=9, S= 30/8.6=3.4 ≤ 3.75 edge distance = 0.3(3.49) =1.05m
πΏ
L=(n-1) S + 2(0.3S) =(n-0.4) S => S=π−0.4
οΌ Among 15m try m =5: S= 15/4.6=3.26 ≤ 3.75, edge distance =0.3(3.26) =0.98m
Grid: 9*5 45 luminaries, edge offset =1.05 (length) and 0.98m (width)
5. A 300 m long and 4 m wide road is to be illuminated using 40 W high-pressure sodium (SON)
lamps, each providing a uniform luminous intensity of 222.8 cd. The lamps are mounted on poles 9
m high, placed along the curb (single-sided mounting arrangement). Design a street lighting scheme
that achieves an estimated minimum illuminance of 0.6 lux on the road surface, and provide a sketch
showing a suitable arrangement of the street lighting poles.
(a) Determine the number of lamps and the center-to-center spacing of poles along the road to meet
the minimum 0.6 lux requirement.
(b) Compute the illuminance at a representative point (mid-span between two adjacent poles, and at
the far edge of the road) to demonstrate that the 0.6 lux minimum is met.
(c) Provide a plan view sketch of the pole layout for the full 300 m length showing pole positions,
mounting side, and the chosen spacing.
Answer
Given Data
ο·
ο·
ο·
ο·
ο·
ο·
Road Length (L): 300 m
Road Width (W) 4m
Pole Height (h): 9m
Luminous Intensity (I): 222.8 cd (Uniform)
Target Minimum Illuminance (Emin): 0.6
Arrangement: Single-sided along curb
Solution
Y=4m away horizontal from the pole line and mid span (x=s/2along the length)
π 2
Horizontal distance from either pole : r = √(2) + 4²
π 2
π 2
Slant distance to either lamp d = √π 2 + β2 = √(2) + 16 + 81 = √(2) + 97
Cos θ = h/d= 9/d
The illuminance contributed by both adjacent pole must be at least 0.6 lux
πΌ.
222.8 .∗9
Emin = 2*π² Cos θ = 2*
π³
Cos θ = 4010.4/ π³≥0.6
π 3 ≤ 4010.4/0.6 = 6684 ο¨d ≤ 18.84
π 2
π 2
d²=(2) + 97 ο¨ 18.84² = (2) + 97
π 2
π 2
354.9=(2) + 97ο¨ (2) + =257.9 ο¨ s/2 = 16.06m ο¨S ≤ 32.12
To distribute pole evenly along the 300 m run:
Number of spans = 300/32.12 = 9.34 ο¨ 10 spans
Exact spacing S = 300/10 =30 m
Number of lambs = 10 spans + 1 = 11 poles/ lamps
B proof of minimum illuminance verification
At S = 30 m. mid- span x = 15 m, far edge y = 4 m
οΌ D = √152 + 42 + 9² = √225 + 16 + 81 = √322 = 17.94 m
οΌ Cos θ = 9/17.94 = 0.5017
οΌ Emin = 2
222.8∗0.5017
17.94²
111.78
2 * 321.81 = 0.695 lux
Since 0.695 ≥ 0.6 lux the requirement is satisfied
C pan view sketch of the pole layout
11 poles along one curb (single-sided), placed at 0, 30, 60, ... , 300 m; mounting height 9 m; road width 4
m.
S = 30 m
Pole height = H= 9 m
h=9m
4m
L = 300m ( 10 spans 11 poles )
L = 300m ( 10 spans 11 poles )