0
UNIVERSITY OF TECHNOLOGY, JAMAICA
COLLEGE/ FACULTY: Engineering & Computing
SCHOOL/ DEPARTMENT: Engineering
Final Examination, Semester 1
Module Name:
Electrical Workshop
Module Code:
ELE1003
Date:
December 2024
Theory/ Practical: Theory
Groups:
ENG 1
Duration:
2 Hours
Instructions:
1. The paper has two sections. Section A has 25 multiple-choice
questions and Section B has written questions.
2. Shade in the letter that corresponds with the correct answer for the
multiple-choice questions in Section A on the Scantron sheet
provided.
3. Start each of the three (3) questions in Section B on a new page.
4. Use the tables provided on page 8 to complete question 2d in Section
5. Ensure that all calculations are clearly written.
6. Answer all questions
7. Return the question paper at the end of the examination.
DO NOT TURN THIS PAGE UNTIL YOU ARE TOLD TO DO SO
Page 1 of 8
SECTION B
Question 1 [25 Marks]
Three (3) lamps, each rated at 45W/110V, 75W/110V and 100W/110V are connected to a
120V power source.
a. Draw and label the configuration for these lamps when they are connected in
i) Series
ii) Parallel
b. Calculate the current flowing through each lamp when they are connected in:
i) Series
ii) Parallel
c. Explain the effect of shorting out the 60W/110V lamp when the three (3) lamps are
connected in:
i) Series
ii) Parallel
[6 + 12 + 7 Marks]
Question 2 [25 Marks]
a. List three (3) main factors that should be considered when selecting cable(s) for a
given task.
b. What is the minimum allowable cross-sectional area of a PVC twin copper cable and
the nearest suitable cable size which will supply a 220 V board 55 m from the supply
point. The total load is 25 A. Maximum allowable voltage drop is 6V. The resistivity
of copper is 1.7 x 10-6 Q-cm (1cm2 = 100mm2)
c. An aluminium wire 7.5 m long is connected in parallel with a copper wire 6 m long.
When a current of 5 A is passed through the combination, it is found that the current
in the aluminium wire is 3 A. The diameter of the aluminium wire is 1 mm.
Determine the diameter of the copper wire.
Resistivity of copper is 0.017 µ12-m ; that of the aluminium is 0.028 µS2-m.
d. Twelve (12) 1.5 mm2 PVC insulated cables are to be drawn into a plastic conduit
which is 8 m long between boxes and contain two (2) bends. A 4.0 mm2 PVC
insulated CPC is also included. Determine the minimum size conduit to contain these
conductors.
[3 + 8 +8 + 6 Marks]
Page 6 of 8
Question 3 [25 Marks]
You are required to install two lamps controlled from three different switching positions
as shown in Figure 2. The design should include a double pole main circuit breaker and
service entrance components. Using a PVC conduit system of wiring and single core
cable complete the following:
a. Draw a schematic diagram for the electrical design
b. Draw a suitable wiring diagram for the layout design shown
c.
Prepare a list of materials and accessories (indicating quantity and type where
necessary), required for the above task.
d. Prepare a list of the tools needed to implement the design.
16+ 9+6 +4 Marks]
3'
Junction
Distribution
Box
Lamp A
Lamp B
8"
0
2' 6"
6"
Switch 1
Switch 2
Switch 3
Figure. 2: Board layout
Total = 100 Marks
END OF PAPER
Page 7 of 8