IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 33, NO. 2, APRIL 2018 1013 Power Engineering Letters Unstable Operation of Photovoltaic Inverter From Field Experiences Chun Li , Senior Member, IEEE Abstract—This letter presents records of unstable operations in grid-connected photovoltaic generation plants. The instabilities involve a wide range of frequencies from tens to thousands of Hertz. Possible causes of the instabilities are discussed based on the literature survey. This letter suggests new industry standards or grid codes for photovoltaic generation integration should consider such practical challenges. Index Terms—Photovoltaic inverter, harmonics, instability, power quality, distributed energy resources. I. INTRODUCTION S PHOTOVOLTAIC (PV) generations are penetrating into power grid rapidly, power quality issues, especially “harmonics” from PV inverters, attract wide interests. Model development, computer simulation and laboratory tests on inverter “harmonic” instability are available in literatures [1]–[7]. However, unstable operations from real grid-connected PV plants are rarely reported. Field experiences from real PV operations are duly needed for research validations, design improvement and code establishment. This letter presents original records of unstable PV operations covering a wide range of frequencies from tens to thousands of Hertz. Possible causes for the instabilities are discussed based on literature reviews due to unavailability of PV facility models (even black-box model) and internal operating record. The letter suggests future PV connection standards or grid codes should consider these practical challenges. A Fig. 1. Current and voltage waveforms under normal and unstable operations. Fig. 2. Current and voltage waveforms under inverters restart. II. RECORDS OF UNSTABLE PV OPERATIONS This section presents three types of unstable operation records from grid-connected PV plants. A. Unstable PV Operation at Low-Order Harmonics The first instability example is from a PV plant under 500 kW. The plant is connected to utility’s 44 kV feeder via a 600 V/44 kV step-up transformer. Fault level at 44 kV Point of Connection (PoC) is close to 200 MVA. Approximately 30 inverters are paralleled at the 600 V bus where no local load is supplied. The Manuscript received September 12, 2016; revised January 4, 2017; accepted January 9, 2017. Date of publication January 19, 2017; date of current version March 22, 2018. Paper no. TPWRD-00161-2016. The author is with Hydro One Networks, Inc., Toronto, ON M5G 1P5, Canada (e-mail: chester.li@hydroone.com). Color versions of one or more of the figures in this letter are available online at http://ieeexplore.ieee.org. Digital Object Identifier 10.1109/TPWRD.2017.2656020 inverter specifications guarantee total current harmonic distortion below 2% at rated power. The left half of Fig. 1 shows a snapshot of PV current and voltage waveforms at 90% of rated power output, where harmonic is not a concern. However, the PV output currents could become highly distorted as shown in the right half of Fig. 1. FFT analysis from 12-cycle window shows that the distortion concentrated at 420 Hz. The magnitude of the 7th harmonic current approaches 20% of the PV rated current. The PV inverters typically restart upon the instability as shown in Fig. 2, probably by internal protective control. The distortions drop to normal level once inverters restart. Harmonic instabilities are also recorded at other frequencies. Fig. 3 shows current and voltage waveforms of a 28 kV/600 V 0885-8977 © 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications standards/publications/rights/index.html for more information. Authorized licensed use limited to: Univ Of Incheon. Downloaded on February 11,2025 at 05:50:34 UTC from IEEE Xplore. Restrictions apply. 1014 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 33, NO. 2, APRIL 2018 Fig. 3. Current and voltage waveforms under partial inverter shutdown. Fig. 4. PV current waveforms with high-frequency oscillations. solar farm partially shutting down its inverters under oscillations at 780 Hz. The farm has 50 inverters in parallel. In both events there was no any utility switching, outage or fault event could be correlated to the harmonic outburst. The causes of the instabilities are very likely inside the solar plants but in-yard operating records are not available. Some simulation and laboratory studies show that interactions among multi-paralleled PV inverters and the grid impedance characteristics could cause similar instabilities [1]–[4]. B. Unstable Operation at High Frequency Inverter instabilities at high frequencies (HF) are reported in simulation or laboratory studies [1], [3], however field records are not available in literature. Figs. 4 and 5 show currents and voltages of a PV plant under 500 kW when inverters restart upon HF oscillations. Fault level at PV 600 V bus is 7 MVA. FFT analysis from two-cycle data in Fig. 5 shows the oscillations focus at 2370 Hz. The meter samples 128 points per cycle. The HF voltage ripples vanish once the inverters restart (current recovery similar as Fig. 2 is omitted in order to illustrate the HF ripples). Inverter control system interactions with external grid characteristics might contribute to the unstable operation [1], [6]. C. Unstable Operation at Interharmonics The last example involves sub-synchronous oscillations in grid-connected PV operations. Three solar farms, 10 MVA each, Fig. 5. PV voltage waveforms with high-frequency oscillations. Fig. 6. PV current and voltage upon utility capacitor switching. are connected to utility substation via a 44 kV feeder of 30 km, all operating at constant power factor. Fault level at the 44 kV PoC is approximately 120 MVA. Weakly damped oscillations near 20 Hz are recorded when a 30 Mvar/44 kV capacitor is energized at the substation bus. Fig. 6 shows current waveforms and voltage RMS trends (updated every half cycle) measured at one solar farm’s 44 kV terminal in response to a capacitor switching. The voltage fluctuations are result of simultaneous oscillations from the three solar farms. FFT analysis with 6cycle data in Fig. 6 indicates that the output current contain a 80 Hz component with magnitude close to 75% of the fundamental current. The magnitude modulation at 20 Hz in Fig. 6 could be explained by the inverter interharmonic injection (80–60 = 20 Hz). The sub-synchronous oscillations triggered by capacitor switching transients could be result of Phase-Locked Loop dynamics in PV inverters [1], [2], [5], [7]. Due to lack of established standards to regulate PV inverter performance, utilities may face new voltage quality management challenges. It is further troublesome that the PV oscillations occur in wide spectra, which makes predicting and mitigating such “harmonics” with conventional filters difficult. Active damping technique is proposed in some researches [4], [6], however operating verification has not been reported. Future industry standards or grid codes may consider requiring PV inverters to demonstrate sufficient damping across reasonable frequency band and operation levels. Authorized licensed use limited to: Univ Of Incheon. Downloaded on February 11,2025 at 05:50:34 UTC from IEEE Xplore. Restrictions apply. IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 33, NO. 2, APRIL 2018 III. CONCLUSION This letter presents field records of unstable operations from grid-connected PV plants. Causes of the instabilities may involve interactions among PV inverter control systems and grid impedance characteristics. The frequencies of the instabilities vary in large scale therefore conventional filters may not mitigate the problems effectively and solutions from inverter control systems should be examined. Industry standards or grid codes to regulate PV inverter frequency characteristics should be considered to manage the new type of power quality disturbances. REFERENCES [1] L. Harnefors, X. Wang, A. Yepes, and F. Blaabjerg, “Passivity-based stability assessment of grid-connected VSCs—An overview,” IEEE J. Emerging Sel. Topics Power Electron., vol. 4, no. 1, pp. 116–125, Mar. 2016. 1015 [2] T. Messo, J. Jokipii, A. Aapro, and T. Suntio, “Time and frequency-domain evidence on power quality issues caused by grid-connected three-phase photovoltaic inverters,” in Proc. 16th Eur. Conf. Power Electron. Appl., 2014, pp. 1–9. [3] C. Yoon, H. Bai, R. Beres, X. Wang, C. Bak, and F. Blaabjerg, “Harmonic stability assessment for multi-paralleled, grid-connected inverters,” IEEE Trans. Sustainable Energy, vol. 7, no. 4, pp. 1388–1397, Feb. 2016. [4] J. He, Y. Li, D. Bosnjak, and B. Harris, “Investigation and active damping of multiple resonances in a parallel-inverter-based microgrid,” IEEE Trans. Power Electron., vol. 28, no. 1, pp. 234–246, Jan. 2013. [5] T. Messo, J. Jokipii, A. Makinen, and T. Suntio, “Modeling the grid synchronization induced negative-resistor-like behavior in the output impedance of a three-phase photovoltaic inverter,” in Proc. 4th IEEE Int. Symp. Power Electron. Distrib. Gener. Syst., 2013, pp. 1–7. [6] X. Wang, F. Blaabjerg, M. Liserre, Z. Chen, J. He, and Y. Li, “An active damper for stabilizing power electronics based AC systems,” IEEE Trans. Power Electron., vol. 19, no. 7, pp. 3318–3329, Jul. 2014. [7] B. Wen, D. Boroyevich, P. Mattavelli, Z. Shen, and R. Burgos, “Influence of phase-locked loop on input admittance of three-phase voltage-source converters,” in Proc. 28th IEEE Appl. Power Electron. Conf. Expo., 2013, pp. 897–904. Authorized licensed use limited to: Univ Of Incheon. Downloaded on February 11,2025 at 05:50:34 UTC from IEEE Xplore. Restrictions apply.