Telephone Terminal Cabinet PEC / NEC Provisions on Telephone Terminal Cabinet Provisions of Installing Telephone Terminal Cabinet The Cabinet, according to the Philippine Electrical Code must have doors and are thus distinguished from large boxes with covers consisting of plates attached with screws and bolts. Telephone Terminal Wall Cabinet Specifications 1. Generally inside terminal room are preferred. This allows for access to power for telephone equipment. 2. Cabinets that should be used but must be approved by the authorities prior to installation. 3. An area 8’ in front of the cabinet must be kept clear for technician access 4. One isolated 20 Amp breaker circuit is extended to plywood backboard inside the cabinet is to be provided. 5. All access handles to accommodate a padlock. 6. A maximum on three foot radius 90 degree bends are allowed in each pulling section. Procedure in Installing cable wire In RJ11 Procedure / Safety Procedure in doing the activity: 1. Prepare the area for the installation of telephone terminal cabinet and frames. 2. All the necessary tools, materials and equipment should be ready. 3. Follow the proper use of PPE for body, head, hand and foot protection. 4. Ensure that mounting screws are installed in the upper and lower flanges on the right and left side of the cabinet. 5. Check the vertical and horizontal alignment of the cabinet using testing tool. 6. Locate the power and ground terminations at the top front side of the cabinet backplane. 7. Observe housekeeping activities. 8.Always Remember: SAFETY FIRST!!!