New floodlit
tennis courts
Existing Hotel
patio
Existing
outdoor
Pool
New pool/cafe
New
summer
house by
existing
outdoor pool
Location of Pool/Cafe
distribution board
Up
Footpath
Existing hotel building
New hotel
extension
Location of existing
hotel CCU and
distribution boards
Draw in and label
the route for the
distribution circuit
to the pool/cafe.
A
Up
A
New hotel extension west elevation
Scale 1:100
B
A
A
A
Car Park
A
A
A
A
A
A
A
A
A
A
A
A
A
ground
SITE PLAN
SCALE 1:500
(Stated scales are correct when
drawings are printed on A3 size.)
Able Skills 2365 Drawings V-2
New café and basement pool south elevation
Elevations
scale 1:100
Proposed new hotel extension and café with
basement swimming pool
Site Plan and
Elevations
Drawing 1 of 5
Drawing Number 2365-AS1
Suite GF 01
Room GF 02
Service
Cupboard
Corridor
Service Cupboard
Scale 1:50 when printed at A3
Corridor
6.
a) Show, on the drawing, positions of lighting, socket-outlets and fused connection units for the rooms in the new hotel block shown above, giving consideration to the
following items of equipment in each room
•
kettle
•
TV
•
provision for phone charging and/or laptop use
•
supply to a 700 W air handling unit for heating/cooling (installed by specialist)
•
electric towel rail.
b)
Show, on the drawing, any further distribution boards that may be required in the hotel extension.
c)
Show on the drawing, how each circuit in the new hotel extension is to be arranged. (The arrangement must take into account that a fault in any one room must not
effect another room.) Each circuit should originate at a distribution board.
d)
Give each circuit a unique form of identification, marked on the drawings
e)
Complete the legend below using recognised symbols and descriptions for each symbol used..
Additional Notes:
Explain briefly your choices and the reasons for them.
Able Skills 2365 Drawings V-2
Proposed new hotel extension and
café with basement swimming pool
Hotel Extension
Ground Floor Plan
Drawing 2 of 5
Drawing Number 2365-AS2
Up
2
Main pool
Up
2
sauna
Pool and pump
equipment
2
Plunge pool
FCU for
hand dryer
Male changing
FCU for
hand dryer
Female changing
2
Scale 1:50 when printed at A3
Able Skills 2365 Drawings V-2
Proposed new hotel extension and
café with basement swimming pool
Swimming Pool Floor Plan
Basement
Drawing 3 of 5
Drawing Number 2365-AS3
2
2
Down
2
Food holding unit
2
Gas
cooker
2
2
Servery
counter
2
2 x Fridges
16 A
Isolator for
Food holding unit
16 A per phase
2
2
2
2
2
2 x Fridges
16 A
Fridges
Dishwasher
16 A
2
Down
Fire Alarm panel
2
2
x2 vending
machines
230 V 1.2 kW
each
New TP-N DB
Zdb = 0.21 Ω
2
Scale 1:50 when printed at A3
Able Skills 2365 Drawings V-2
Proposed new hotel extension and
café with basement swimming pool
Café Floor Plan
Ground Floor
Drawing 4 of 5
Drawing Number 2365-AS4
2
symbol
Legend (For ALL drawings)
description
symbol
description
2
2
2
2
Summerhouse floor plan
Scale 1:50
There is no express requirement to
'design' these circuits. Their loads are
already accounted for in the 32A supply to
the summer house, fed from the Cafe DB
Summerhouse east elevation
Scale 1:50 (at A3)
Able Skills 2365 Drawings V-2
Proposed new hotel extension and
café with basement swimming pool
New poolside
summerhouse
Drawing 5 of 5
Drawing Number 2365-AS5