i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 5 8 9 e1 5 9 5 Available online at www.sciencedirect.com w w w . i i fi i r . o r g journal homepage: www.elsevier.com/locate/ijrefrig Proposal of an eco-friendly high-performance air-conditioning system. Part 1. Possibility of improving existing air-conditioning system by an evapo-transpiration condenser Huynh Thi Minh Thu a, Haruki Sato b,* a Graduate School of Science and Technology, Keio University, 3-14-1 Hiyoshi, Kohoku-ku, Yokohama 223-8522, Japan b Department of System Design Engineering, Faculty of Science and Technology, Keio University, 3-14-1 Hiyoshi, Kohoku-ku, Yokohama 223-8522, Japan article info abstract Article history: Air-conditioning (AC) system consumes high energy and releases waste-heat. In the pre- Received 27 January 2012 sent study, we propose a method to improve its performance and minimize waste-heat by Received in revised form replacing existing air-cooled condenser by an evaporation and transpiration, evapo- 28 March 2013 transpiration, condenser. The improvement is confirmed by performing experiment for a Accepted 6 April 2013 conventional air-cooled AC system and a water-cooled AC system. Condenser temperature Available online 15 April 2013 in the air-cooled system is higher than outdoor-temperature by 5e10 C, while it is 5 to Keywords: expected to reach up to 30% in summer with the testing system. Based on these results, an Air-conditioning evapo-transpiration heat-exchanger was developed as a new condenser. Heat-transfer Energy saving coefficient of the testing heat-exchanger is at least 4 times higher than that of air-cooled Heat island condenser. Even hot fluid is used inside copper-tubing, its outlet-air temperature is as Condenser nearly as outdoor temperature. 5 C in case of the testing system. From simulation results, saving energy consumption is Evapo-transpiration ª 2013 Elsevier Ltd and IIR. All rights reserved. Exergy Proposition de système de conditionnement d’air hautement performant et écologique. Partie 1. Possibilité d’améliorer un système de conditionnement d’air existant à l’aide d’un condenseur à évapotranspiration Mots clés : conditionnement d’air ; économies d’énergie ; ı̂lot de chaleur ; condenseur ; évapotranspiration ; exergie * Corresponding author. Tel.: þ81 45 563 1141x43045; fax: þ81 45 566 1729. E-mail address: hsato@sd.keio.ac.jp (H. Sato). 0140-7007/$ e see front matter ª 2013 Elsevier Ltd and IIR. All rights reserved. http://dx.doi.org/10.1016/j.ijrefrig.2013.04.004 1590 1. i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 5 8 9 e1 5 9 5 Nomenclature Q_ cond E_ Air-conditioning system outdoor temperature [K] To condenser temperature [K] Tcond DT ¼ Tcond To temperature difference between condenser and outdoor [K] outlet-air temperature from outdoor unit [K] Tao P power consumption rate [W] Heat exchanger temperatures at inlet and outlet of fan [K] Tfi, Tfo Thwi, Thwo temperatures at inlet and outlet of hot water [K] overall heat-transfer coefficient [W m2 K1] Uo heat-transfer rate releases from hot water [W] qhw outside surface area [m2] Ao Introduction Annual global average temperature trend continues increasing. One-degree Celsius increase in summer has been correlated with 3.8% increase in peak demand load for air-conditioning (Peck and Richie, 2009). Air-cooled condensers have contributed large amount of small-scale air-conditioning due to its advantages of easy maintenance with convenient size. However, cooling by sensible heat from air is only expected to get low heat-transfer performance that makes high condensing temperature, i.e. 15e20 C above that of the ambient air in some cases (Hosoz and Kilicarslan, 2004). In studies of Chow et al. (2002) and Hajidavalloo (2007), they mentioned that the coefficient of performance (COP) of an air-conditioner decreases about 2e4% by increasing each degree Celsius in condenser temperature. In addition, by releasing waste-heat to the surroundings, it further increases temperatures outside, which contributes to heat island problem in urban area. Moreover, hot-air flow of the waste-heat contains exergy, which is available energy that can transfer to work, generally it is not re-used. Other types of condensers that commonly used in airconditioning system are water-cooled and evaporative condensers (Hosoz and Kilicarslan, 2004). Most of water-cooled condensers reject heat by connected with cooling tower, while evaporative condenser is compact by combining functions of an air-cooled condenser with a water-cooled condenser and a cooling tower. Cooling by water evaporation has much higher performance compared to air-cooled condenser. In evaporative condenser, fin combined with packing material have been used (Ettouney et al., 2001). Cellulose is a common material for evaporative packing (Hajidavalloo, 2007; Hu and Huang, 2005), but it requires large space for evaporation. However, size of these condensers is large and recently they are applied for medium- and largescale cooling system, in which, additional pump is required to operate. We propose a new air-conditioning system using an evapotranspiration heat-exchanger for higher performance condenser to reduce its temperature with convenient size and creating comfortable space at the outdoor unit. The possibility for developing a new air-conditioning system will be discussed in this paper. By experiments, we examine the relationship of power consumption of conventional air-conditioning system condenser heat-transfer rate [W] exergy [W] and average condense-temperature for every hour. Effect of condenser-temperature to the system performance is also demonstrated by simulation. Besides, waste-heat and its exergy from air-cooled outdoor-unit are also evaluated. Temperatures of condenser and compressor of a watercooled system are measured to confirm the possibility of reducing those temperatures in the new system. Performance of new system is also expected based on this result. An evapo-transpiration heat-exchanger, which is proposed for new condenser, will be explained by its heat-transfer coefficient and possibility to minimizing environmental effect of the new outdoor-unit. 2. Experiment description 2.1. Air-conditioning systems An existing commercial air-conditioning system using R410A as refrigerant, nominal cooling capacity of 2.5 kW and catalogue COP of 5.68 is used as a baseline system. This conventional system has an air-cooled condenser, which is coppertubing of 22.3 m length and 8 mm outside diameter. A water-cooled air-conditioning system, which was modified from conventional system by using a water-cooled condenser that connected with cooling tower, as shown in Fig. 1, is used as a testing system. Water-cooled condenser is a double copper-tubing adjacent to each other, with total length of 21 m, refrigerant outside diameter of 6.35 mm and water outside diameter of 8 mm. The cooling tower used in the testing system has nominal cooling capacity of 13.6 kW with a 0.25-kW pump and a 0.05-kW fan being commercially available as the minimum capacity. Fig. 1 e Sketch of conventional AC (left) and testing AC systems (right). i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 5 8 9 e1 5 9 5 1591 Fig. 2 e Testing heat-exchanger. A: Heat exchanger (copper tube and ceramics), B: water-drop pipe, C: bath-pump, D: cooling water tank, E: fan, F: duct. For the present purpose, we are testing the condensing ability under various conditions for the testing system compared to conventional system in actual summer weather. Experiment of the conventional system was operated 4 days in summer 2009 (daytime) and 5 days in summer 2010 (24 h); while testing system was operated 5 days long (24 h) in summer 2010. 2.2. Testing heat-exchanger A prototype of a new heat-exchanger has been set-up and tested in summer 2009. The experiment is sketched in Fig. 2. The heat-exchanger consists of copper tubes covered with porous ceramics. Hot water flows inside copper tube and is circulated. Tap water drops from top to ceramic surface and is circulated from bottom tank by a 13-W bath-pump. A fan of 1740 m3 h1 flow-rate is put in front of the heat-exchanger. Airflow is ducted by an acrylic duct. Type-T-thermocouples are used to measure temperatures; data is connected to computer and recorded by data logger CADAC with the uncertainty of 0.02% of reading þ0.03 C. For the air-conditioning systems, temperatures were measured at inlet, middle, outlet of condensers and evaporators; before and after compressors; before expansion valves; and inlet and outlet of cooling water, as in Fig. 3. For heat exchanger, temperatures at inlet and outlet of hot water; top, middle and bottom of copper-tube and ceramics surfaces; inlet and outlet of air flow; in the water tank; and of the ambient are recorded. 3. Calculation 3.1. Air-conditioning performance 3.1.1. Coefficient of performance A typical ideal vapor compression cycle is sketched in Fig. 4. In order to estimate COP of the air-conditioning system, properties of refrigerant are evaluated using REFPROP 8.0. COPtheo ¼ h1 h4 h2 h1 COP ¼ hsys ,COPtheo Fig. 3 e Positions of thermocouples in the air-conditioning system. Fig. 4 e Heat pump cycle on Peh diagram. (1) (2) 1592 i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 5 8 9 e1 5 9 5 Fig. 5 e Middle-condenser temperature (every minute). In which, hsys is system correction factor and is calculated at nominal condition by: hsys ¼ COPcata COPtheo n (3) COPtheo_n is theoretical COP at nominal condition and COPcata is COP in manufacturer’s catalogue. Nominal condition is assumed that: outdoor temperature of 35 C, indoor setting temperature of 27 C, indoor relative humidity is about 43%, dew point temperature is 13.5 C and evaporation temperature is 7 C lower than dew point, which is 6.5 C. 3.1.2. 3.2. Overall heat-transfer coefficient of new heat-exchanger Heat released by hot water is evaluated by : _ hw cpw ðThwi Thwo Þ q_ hw ¼ m Heat transfer rate is also calculated by : (6) q_ hw ¼ Uo Ao DTlm (7) where DTlm ¼ DTo DTi =ðlnðDTo =DTi ÞÞ: logarithmic mean temperature difference with DTo ¼ Thwo Tfi and DTi ¼ Thwi Tfo. Power consumption For the same outdoor temperature and indoor setting temperature for the same space, cooling load required for the two systems is assumed to be the same. Hence, we have: Pconv COPnew ¼ Pnew COPconv (4) Then; power consumption of new system is estimated : COPconv Pnew ¼ Pconv COPnew ð5Þ 4. Results and discussions 4.1. Effects of condenser temperatures to the performance of a conventional air-conditioning system For the present purposes, condenser and compressor temperatures are concerned. Thermocouple at the middle of the condenser copper-tubing, which is supposed to be very close to condenser temperature, is used as condenser Fig. 6 e Integral power consumption vs. condenser (left) and compressor (right) temperatures. i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 5 8 9 e1 5 9 5 1593 Fig. 9 e Temperatures of condenser vs. outdoor. Fig. 7 e Estimated COP vs. condenser temperature. 4.2. temperature. Thermocouple right after the compressor, which is close to compressor temperature, is used as compressor temperature. In the experiment, data is recorded every minute. At low outdoor-temperature, temperature at condenser is divided into two regions: high temperature (ON or operating mode) and low temperature (OFF or stop mode), as in Fig. 5. In order to compare the performance among air-conditioning systems, integral power consumption for an hour is considered. In this paper, we consider integral power consumption and average temperatures of outdoor, condenser, compressor for every hour. From now on, hourly average temperature of outdoor, middle-condenser and right after compressor are briefly called as outdoor temperature, condenser temperature and compressor temperature. From experimental results of the conventional AC system, higher condenser temperature, which leads to higher compressor temperature, makes integral power consumption higher, as shown in Fig. 6. Hence, higher performance is expected to achieve at lower condenser temperature, as simulation result in Fig. 7. Fig. 8 e Waste-heat and its exergy of air-cooled outdoorunit. Exergy of waste-heat from air-cooled outdoor unit For air-cooled outdoor unit, hot-air flow of waste-heat contains exergy, but it is not utilized for other purposes. In consequence, it transfers directly to the ambient air and performs some change to the surrounding air. Amount of this exergy is calculated by: To (8) E_ ¼ Q_ cond ðTao To Þ To ln Tao Waste-heat and its exergy of hot-air flow from air-cooled condenser are described in Fig. 8. Because condensertemperature increases drastically as outdoor-temperature increases, exergy also increases considerably. For example, in this experiment, at 34.5 C outdoor-temperature, condenser temperature is nearly 45 C, waste-heat is about 0.9 kW and its exergy is estimated to be approximately 0.15 kW. 4.3. Condenser and compressor temperatures in air and water-cooled systems Temperatures of compressor and condenser are sketched in Figs. 9 and 10, respectively, for conventional and testing airconditioning systems at outdoor temperatures from 27 C to 35 C. In Fig. 9, condenser temperature increases sharply with increasing of outdoor temperature. Temperature at condenser surface is approximately from 5 to 10 C higher than that of the water condenser, which is nearly the same as outdoor Fig. 10 e Temperatures of compressor vs. outdoor. 1594 i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 5 8 9 e1 5 9 5 Fig. 11 e Temperature difference between condenser and outdoor vs. outdoor temperature. temperature. Likewise, temperature right after the compressor of the conventional system is higher about 10e20 C than that of the water system, which is just higher than outdoor temperature about 5 C Fig. 10. Fig. 13 e Estimated COP vs. outdoor temperature. conventional system up to more than 30%, as shown in Fig. 13. Therefore, with the same cooling space, if any new air-conditioning system can have low condenser-temperature as the testing system without using cooling tower, its integral power consumption is expected to save 30%, as shown in Fig. 14. 4.4. Expected performance of the new air-conditioning system 4.5. Temperature difference between condenser and outdoor, DT, is getting higher as outdoor temperature increases, as shown in Fig. 11. When outdoor temperature is higher, integral power consumption increases not only due to higher cooling load but also caused by higher pressure difference between condenser and evaporator. For that reason, higher DT is, higher energy requires. Fig. 12 shows the change of integral power consumption with respect to temperature difference between condenser and outdoor temperatures. The integral power consumption of the testing system is not included in the results since cooling tower has high power consumption. Based on experimental results, COP of the testing system is expected to be higher than that of the Transpiration and evaporation are main principles in developing the new heat-exchanger. Transpiration helps to minimize energy used for pump using porous ceramics, while heat-exchange rate between inside and outside is enhanced by evaporation of water. Even ceramics’ performance should be carefully investigated, its property to spread water automatically and continuously along copper-tube surface is satisfied. This experiment was carried out in summer weather to confirm the actual performance. Heat-transfer coefficient is evaluated in order to compare with that of the air-cooled condenser. The heat-transfer coefficient of the proposed heat-exchanger, which is calculated from Eq. (7), is demonstrated in Fig. 15. The overall heat- Fig. 12 e Integral power consumption vs. temperature difference between condenser and outdoor. Fig. 14 e Integral power consumption vs. outdoor temperature. Testing heat-exchanger i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 5 8 9 e1 5 9 5 Fig. 15 e Heat-transfer coefficients of the new heatexchanger. 1595 system. Higher condenser temperature makes higher energy consumption. By using ambient air to cool condenser, conventional outdoor unit releases heat including the exergy to the surroundings, which causes heat island problem in cities. In this experiment, at about 35 C outdoor-temperature, waste-heat is about 0.9 kW and exergy of outlet hot-air flow is estimated to be about 0.15 kW. It is confirmed by using testing air-conditioning system that condenser temperature is as low as outdoor-temperature, which makes temperature right after compressor lower, too. From simulation result, COP of the new testing system is estimated to be 30% higher than that of the conventional system. In order to achieve energy saving estimation above, a new heat-exchanger using evapo-transpiration has been proposed. The heat-transfer coefficient of this new heat-exchanger is evaluated at least 4 times higher than that of the air-cooled heat-exchanger used in the conventional system. Even hot fluid is used in this testing heat-exchanger, outlet-air temperature is as near as ambient temperature. Acknowledgments Authors are grateful to Toshiba Carrier for supporting to develop the new air-conditioning system. The study is supported by Global COE Program “Center for Education and Research of Symbiotic, Safe and Secure Design”, MEXT, Japan. The authors would like to thank to AUN/SEED-Net JICA (Japan International Corporation Agency) for giving scholarship to student. Fig. 16 e Outlet-air temperature of the new heat exchanger. references transfer coefficient is about 400e900 W m2 K1, which is much higher than the air-cooled condenser whose range of heat-transfer coefficient is from 50 to 90 W m2 K1 with air velocity of 0.5e3 m s1 (Seshimo and Fujii, 1992). By having higher performance, size of condenser of the new system is expected to be smaller than the existing one. By using water evaporation to cool hot water inside copper tube, outlet-air temperature is nearly or even lower than ambient temperature as shown in Fig. 16. In this prototype, the distance between two rows of copper-tubing is long enough that humidity of air at the outlet is not so higher than that of the ambient due to mixing with the air that does not contact with wet ceramics surface. Chow, T.T., Lin, Z., Yang, X.Y., 2002. Placement of condensing units of split-type air-conditioners at low-rise residences. Appl. Therm. Eng. 22, 1431e1444. Ettouney, H.M., El-Dessouky, H.T., Bouhamra, W., Al-Azmi, B., 2001. Performance of evaporative condensers. Heat Transfer Eng. 22, 41e55. Hajidavalloo, E., 2007. Application of evaporative cooling on the condenser of window-air-conditioner. Appl. Therm. Eng. 27, 1937e1943. Hosoz, M., Kilicarslan, A., 2004. Performance evaluations of refrigeration systems with air-cooled, water-cooled and evaporative condensers. Int. J. Energy Res. 28, 683e696. Hu, S.S., Huang, B.J., 2005. Study of a high efficiency residential split water-cooled air conditioner. Appl. Therm. Eng. 25, 1599e1613. Peck, S., Richie, J., 2009. Green Roofs and the Urban Heat Island Effect. Stamats Commercial Buildings Group, Cedar Rapids, The United States. Web site URL: http://www.buildings.com (quoted in 2012). Seshimo, Y., Fujii, M., 1992. Compact Heat Exchanger. Nikkan Kogyo Press Co., Ltd, Tokyo (in Japanese). 5. Conclusions High temperatures are measured in condenser and compressor of conventional air-cooled air-conditioning