Uploaded by davyhoo

1-DataSheet-1

advertisement
Project No. 4786996266
LABORATORY DATA PACKAGE
File
EX16085
Page
1
Number of pages in this package __59__ [ including additional pages _N/A___ ]
(Fill in when using printed copy as record)
CLIENT INFORMATION
Company Name TIANJIN PUYOU MECHANICAL & ELECTRICAL EQUIPMENT MFG CO LTD
Address 190 Middle Rd
Fortune Centre Unit 14-10
, 188979
Singapore
AUDIT INFORMATION:
Description of Tests
UL Standard for Safety
for Centrifugal
Stationary Fire Pumps
for Fire-Protection
Service
ULC Other Recognized
Document, Guide for the
Investigation of Pumps
for Fire Protection
Service
[] Tests Conducted by1
[x] UL Staff conducting
or witnessing testing
Per Standard No.
UL 448
Edition/
Revision
Date
ULC/ORDC448-79
10/
February
05, 2016
2/ December
1979
Gao Yingru
(WTDP, TMP, WMT only)
[] UL Staff supervising
UL Staff in training
[]Authorized Signatory
Rossen Marinov
(CTDP, TPTDP, TCP, PPP, SMT)
Printed Name
Signature. Include date for
CTDP, TPTDP, TCP, PPP, WMT,
TMP, SMT
TESTS TO BE CONDUCTED:
Test
No.
1
Done3
x
Test Name
HYDROSTATIC STRENGTH
2
X
OPERATION
[ ] Comments/Parameters
[x] Tests Conducted by2
[ ] Link to separate data files4
Gao Yingru,2013-11-20 to 201311-22
Gao Yingru,2013-11-20 to 201311-22
Instructions 1 - When all tests are conducted by one person, name can be inserted here instead of including
name on each page containing data.
2 - When test conducted by more than one person, name of person conducting the test can be
inserted next to the test name instead of including name on each page containing data. Test dates
may be recorded here instead of entering test dates on the individual datasheet pages.
ULS-00448-QXJY-DataSheet-2004
Form Page 1
Form Issued:
Form Revised:
Copyright © 2015 UL LLC
2004-01-30
2015-04-13
Only those products bearing the UL Mark should be considered as being covered by UL.
Project No. 4786996266
LABORATORY DATA PACKAGE
File
EX16085
Page
2
3 - Use of this field is optional and may be employed differently. If used to include a date
instead of entering the testing date on the individual datasheet pages, the date shall be the
date the test was conducted.
4 – Link to separate data files for a test can be inserted here. The link must be to a server
that is accessible to UL staff, that provides for backup, required retention periods and a path,
including file name, that does not change and result in a broken link. Not applicable to DAP.
Special Instructions -
[ ] Unless specified otherwise in the individual Methods, the tests shall be
conducted under the following ambient conditions. Confirmation of these
conditions shall be recorded at the time the test is conducted.
Ambient
Temperature, C
±
Relative
Humidity, %
±
Barometric
Pressure, mBar
±
[x] No general environmental conditions are specified in the Standard(s) or
have been identified that could affect the test results or measurements.
RISK ANALYSIS RELATED TO TESTING PERFORMANCE:
The following types of risks have been identified. Take necessary
precautions. This list is not all inclusive.
[x] Electric shock
[ ] Radiation
[ ] Energy related hazards
[ ] Chemical hazards
[ ] Fire
[x] Noise
[x] Heat related hazards
[x] Vibration
[x] Mechanical
[ ] Other (Specify)__
ULS-00448-QXJY-DataSheet-2004
Form Page 2
Form Issued:
Form Revised:
Copyright © 2015 UL LLC
2004-01-30
2015-04-13
Only those products bearing the UL Mark should be considered as being covered by UL.
Project No. 4786996266
LABORATORY DATA PACKAGE
File
EX16085
Page
3
Conversion Instructions –
•
Length
1 inch = 25.4 millimeter
1 millimeter = 0.0394 inch
1 foot = 12 inches
1 inch = 0.0833 feet
•
Weight
1 pound = 0.4536 kilogram
1 kilogram = 2.2046 pound
•
Flow
1 gallon/minute [US] = 0.2271 cubic meter/hour
1 cubic meter/hour = 4.4029 gallon/minute [US]
•
Pressure
1 pound/square inch = 0.0689 bar
1 bar = 14.5038 pound/square inch
1 pound/square inch = 0.7032 meter of head
1 meter of head = 1.4220 pound/square inch
ULS-00448-QXJY-DataSheet-2004
Form Page 3
Form Issued:
Form Revised:
Copyright © 2015 UL LLC
2004-01-30
2015-04-13
Only those products bearing the UL Mark should be considered as being covered by UL.
Project No.
4786996266
Tested by:
Gao Yingru
File
EX16058
Page
Date
4
2013-11-20
to 201311-22
WITNESS TEST DATA PROGRAM (WTDP) INFORMATION:
Environment:
Accommodations and Environmental conditions, including
proper power source meet the requirements of the test
standard or UL default criteria (ISO/IEC 17025 Clause
5.3.1, 5.3.2. 5.3.3, 5.3.4)
[ ]Yes [ ]No [x]N/A
Personnel:
Lab Management shall authorize personnel to operate
particular types of equipment used in testing.
(ISO/IEC 17025 5.5.3)
[x]Yes [ ]No
Equipment:
Testing is being conducted within the test equipment
calibration dates. (See Test Instrument Information
Page and ISO/IEC 17025 5.5.1, 5.5.2, 5.5.4, 5.5.5,
5.5.8,)
[x]Yes [ ]No
Calibrations for testing equipment is traceable to SI
Units. Refer to 00-OP-C0032 (Calibration Certificate
Analysis). (ISO/IEC 17025 5.6.2.2)
[x]Yes [ ]No
Critical Consumables:
Critical consumables are compliant with test standard
requirements. (ISO/IEC 17025 Clause 4.6)
[ ]Yes [ ]No [x]N/A
Sample Identification:
Identification of items to be tested has been made
(e.g. model no., Serial No., etc.) (See Test Sample
Identification page and ISO/IEC 17025 Clause 5.8.2)
[x]Yes [ ]No
Additional Requirements:
Testing at a third party laboratory selected by UL and
not part of the Third Party Test Data Program requires
a Mutual Nondisclosure (NDA) and Confidentiality
Agreement, 00-LE-F0025, or alternate agreement form
approved by UL’s Legal Department to be stored and
included with the Test Package.
[ ]Yes [ ]No [x]N/A
Summary:
The test facility [ was ][ was not ] deemed to have the environment and
capabilities necessary to perform the tests included in this data package.
ULS-00448-QXJY-DataSheet-2004
Form Page 4
Form Issued:
Form Revised:
Copyright © 2015 UL LLC
2004-01-30
2015-04-13
Only those products bearing the UL Mark should be considered as being covered by UL.
Project No.
4786996266
Tested by:
Gao Yingru
File
EX16058
Page
Date
5
2013-11-20
to 201311-22
[x] The CAS Staff as indicated below, (a competent L1, L2 or L3 in a similar
CCN/Standard for a similar test method) was utilized to conduct the
witnessing of tests on behalf of the project handler. (Please complete the
table below to document the rationale and approval.)
Name of UL Staff
conducting WTDP
Rossen Marinov
CCN/Standard
to be
witnessed
QXXW
Test(s) to be
witnessed
All
L1, L2 or
L3
Competency
L3
Similar
CCN/Standard
Competency
N/A
L3 Reviewer
Approval &
Date (Similar
CCN/Standard)
Bob Xia
[ ] The Field Services Staff Member, as indicated below, (with a competent
program competency as authorized by the FOM) was informed and utilized to
conduct the witnessing of tests on behalf of the project handler. (Please
complete the table below to document the information and approval.)
Name of UL Staff
conducting WTDP
CCN/Standard to
be witnessed
ULS-00448-QXJY-DataSheet-2004
Form Page 5
Test(s) to be
witnessed
FOM Approver
(name)
Form Issued:
Form Revised:
Copyright © 2015 UL LLC
L3 Reviewer
Approval & Date
2004-01-30
2015-04-13
Only those products bearing the UL Mark should be considered as being covered by UL.
Project No.
4786996266
Tested by:
Gao Yingru
File
EX16058
Page
Date
6
2013-11-20
to 201311-22
TEST LOCATION: (To be completed by Staff Conducting the Testing)
[]UL or Affiliate
[X]WTDP []CTDP
[]TPTDP
[]TCP
[]PPP
[]WMT
[]TMP
[]SMT
Company Name: TIANJIN PUYOU MECHANICAL & ELECTRICAL EQUIPMENT MFG CO LTD
Address: No 7. Beijing St. Jinnan Ecomomic Development Area (west
Area), Tianjin, P.R., China
ULS-00448-QXJY-DataSheet-2004
Form Page 6
Form Issued:
Form Revised:
Copyright © 2015 UL LLC
2004-01-30
2015-04-13
Only those products bearing the UL Mark should be considered as being covered by UL.
Project No.
4786996266
Tested by:
Gao Yingru
File
EX16058
Page
Date
7
2013-11-20
to 201311-22
TEST EQUIPMENT INFORMATION
[x] UL test equipment information is recorded on Meter Use in UL’s Laboratory
Project Management (LPM) database.
[ ] UL test equipment information is recorded on <<insert location and local
laboratory equipment system identification.>>
Inst.
ID No.
Instrument
Type
Test Number +, Test
Title or
Conditioning
6-76
Stopwatch
0609537
Function
/Range
Last Cal.
Date
Next Cal.
Date
1,2, OPERATION
0 to
7200 Sec
2013-1021
2014-10-21
Pressure
Gauge
1, HYDROSTATIC
STRENGTH
0 to 10
MPa
2013-0827
2014-08-27
1205103
Pressure
Gauge
2, OPERATION
0 to 4
MPa
2013-1022
2014-10-22
1308102
Pressure
Gauge
2, OPERATION
0 to 6
MPa
2013-0822
2014-08-22
03023
Flowmeter
2, OPERATION
0 to 300
M^3/Hr
2013-1015
2014-10-15
13005
Flowmeter
2, OPERATION
0 to 650
M^3/Hr
2013-1015
2014-10-15
1#
Measuring
Tape
2, OPERATION
0 to
1000 mm
2013-0913
2014-09-13
1306428
AF
Torque
Meter
2, OPERATION
50Nm to
5kNm
20 to
30000RPM
2013-0830
2014-08-30
+ - If Test Number is used, the Test Number must be identified on the data sheet pages or on the
Data Sheet Package cover page.
The following additional information is required when using client’s or
rented equipment, or when a UL ID Number for an instrument number is not used.
The Inst. ID No. below corresponds to the Inst. ID No. above.
Inst. ID No.
6-76
0609537
1205103
1308102
03023
13005
1#
Make/Model/Serial Number/Asset No.
TINAN FU/PC396/6-76
Leierda Instrument Co Ltd/0-10MPa/0609537
Xi’an Xiyi Huashan Instrument Manufacturer/0-4MPa/1205103
Xi’an Xiyi Huashan Instrument Manufacturer/0-4MPa/1308102
Zhonghuan Tianyi Co Ltd/LWGY-150/03023
Zhonghuan Tianyi Co Ltd/LWGY-200/13005
Xiongshi/5m/1#
ULS-00448-QXJY-DataSheet-2004
Form Page 7
Form Issued:
Form Revised:
Copyright © 2015 UL LLC
2004-01-30
2015-04-13
Only those products bearing the UL Mark should be considered as being covered by UL.
Project No.
4786996266
Tested by:
Gao Yingru
Inst. ID No.
1306428AF
File
EX16058
Page
Date
8
2013-11-20
to 201311-22
Make/Model/Serial Number/Asset No.
Beijing Sanjing Technology Co Ltd/10000AF/1306428AF
ULS-00448-QXJY-DataSheet-2004
Form Page 8
Form Issued:
Form Revised:
Copyright © 2015 UL LLC
2004-01-30
2015-04-13
Only those products bearing the UL Mark should be considered as being covered by UL.
Project No.
4786996266
Tested by:
Gao Yingru
File
EX16058
Page
Date
9
2013-11-20
to 201311-22
TEST SAMPLE IDENTIFICATION:
The table below is provided to establish correlation of sample numbers to
specific product related information. Refer to this table when a test
identifies a test sample by "Sample No." only.
Sample Card
No.
N/A
Date
Received
N/A
Rated
Capacity,
GPM
500
750
1000
500
750
1000
750
1000
[] Test
No.+
Sample
No.
All
N/A
Manufacturer, Product Identification and Ratings
[Pumping Equipment for Fire Service]
(Centrifugal Fire Pumps) Centrifugal Fire
Pumps, Vertical Turbine, For requested
ratings refer to the table below.
Model
Dsg
Rated Net
Pressure Range,
psi
Approx
Speed, RPM
Number of Stages
350QHBC
40-47
1470
2
350QHBC
58-70
1470
3
350QHBC
77-233
1470
4 - 10
350QHBC
40-44
1470
2
350QHBC
54-65
1470
3
350QHBC
72-218
1470
4 - 10
350QHBC
40
1470
2
350QHBC
49-61
1470
3
350QHBC
47-57
1620
2
350QHBC
71-86
1620
3
350QHBC
95-286
1620
4 – 10
350QHBC
45-54
1620
2
350QHBC
67-81
1620
3
350QHBC
90-270
1620
4 – 10
350QHBC
41-51
1620
2
350QHBC
62-76
1620
3
350QHBC
53-65
1770
2
350QHBC
79-98
1770
3
350QHBC
105-229
1770
4 – 7
350QHBC
48-62
1770
2
ULS-00448-QXJY-DataSheet-2004
Form Page 9
Form Issued:
Form Revised:
Copyright © 2015 UL LLC
2004-01-30
2015-04-13
Only those products bearing the UL Mark should be considered as being covered by UL.
Project No.
4786996266
Tested by:
Gao Yingru
1250
1250
1500
1250
1500
1500
2000
1500
2000
File
EX16058
Page
Date
10
2013-11-20
to 201311-22
350QHBC
73-217
1770
3 – 7
350QHBC
40-58
1770
2
350QHBC
66-202
1770
3 - 7
400QHBC
44-57
1470
2
400QHBC
66-228
1470
3 - 8
400QHBC
40-55
1470
2
400QHBC
61-218
1470
3 - 8
400QHBC
55-71
1620
2
400QHBC
82-283
1620
3 - 8
400QHBC
51-68
1620
2
400QHBC
77-272
1620
3 - 8
400QHBC
66-82
1770
2
400QHBC
99-123
1770
3
400QHBC
132-246
1770
4 - 6
400QHBC
40-73
1770
2
400QHBC
87-220
1770
3 - 6
400QHBC
78-96
1900
2
400QHBC
117-144
1900
3
400QHBC
156-288
1900
4 - 6
400QHBC
69-87
1900
2
400QHBC
104-262
1900
3 - 6
+ - If Test Number is used, the Test Number or Numbers the sample was used in must be identified
on the data sheet pages or on the Data Sheet Package cover page.
[ ] Sampling Procedure [ ] This document contains data or information using color and if printed,
should be printed in color to retain legibility and the information
represented by the color.
ULS-00448-QXJY-DataSheet-2004
Form Page 10
Form Issued:
Form Revised:
Copyright © 2015 UL LLC
2004-01-30
2015-04-13
Only those products bearing the UL Mark should be considered as being covered by UL.
Project No.
4786996266
Tested by:
Gao Yingru
HYDROSTATIC STRENGTH
File
EX16058
Page
Date
11
2013-11-20
to 201311-22
UL 448, Edition 10, Section 26
ULC C448, Edition 2, Section 4.3
Maximum
Working
Test
Test
Pressure,
Pressure,
No.
Model
MPa
MPa
1-A
350QHBC*
2.10
4.22
1-B
400QHBC**
2.33
4.69
Results Key: [A] Acceptable [B] Unacceptable
*Test
Pressure
Dwell Time,
min.
5
5
Results
A
A
Compliance Criterion: The sample shall withstand the test pressure without
rupture.
*UL 448 requires a 1-minute test pressure dwell time and ULC/ORD-C448-79
requires a 5-minute test pressure dwell time.
Notes: The following components have been subjected to hydrostatic testing:
*350QHBC – 10 Stage bowl & column assembly
**400QHBC – 8 Stage bowl & column assembly
ULS-00448-QXJY-DataSheet-2004
Form Page 11
Form Issued:
Form Revised:
Copyright © 2015 UL LLC
2004-01-30
2015-04-13
Only those products bearing the UL Mark should be considered as being covered by UL.
Project No.
4786996266
Tested by:
Gao Yingru
File
EX16058
Page
Date
12
2013-11-20
to 201311-22
UL 448, Edition 10, Section 24
ULC C448, Edition 2, Section 4.2
OPERATION
Model Designation:
350QHBC
Number of Stages:
Outlet Tested for Multistage
Multiport Pump
2-10
Minimum Submergence, in. [1]:
Refer to individual test sheets
Maximum Bearing Span, in. [1]:
10ft
Suction Pipe Diameter, in.:
N/A
[ ] same as discharge
Discharge Pipe Diameter, in.:
N/A
[ ] same as suction
Suction Elevation:
N/A
Refer to individual
test sheets
[ ] same as discharge
Discharge Elevation:
[ ] same as suction
MaxImp, Maxstage
Rated
Speed,
rpm
Impeller
Diameter(s),
_inch_
(units)
Rated
Capacity,
gpm
Size, in.
(inlet x
outlet)
Rated Net
Pressure,
psig
500
10
233
1470
9.84
750
10
218
1470
9.84
1000
10
202
1470
9.84
Min
Submergence
and
Max
bearing Span
Impeller
Diameter(s),
_inch_
(units)
Test
Condition[2]
Test
Condition[2]
Results
A
A
A
MinImp, Minstage
Rated
Capacity,
gpm
Size, in.
(inlet x
outlet)
Rated Net
Pressure,
psig
Rated
Speed,
rpm
500
10
40
1470
9.06
750
10
40
1470
9.06
1000
10
40
1470
9.06
Min
Submergence
and
Max
bearing Span
Results
A*
A*
A*
Note:
The distance from water surface to center of pressure gauge (0.7m) was added to
discharge pressure.
The power of gear box was removed from power of pump.
*Regarding minimum impeller&minimum stage, Client preferred higher net pressure to
comply UL requirement, as the result is lower than 40 psi.
Results Key: [A] Acceptable [B] Unacceptable
ULS-00448-QXJY-DataSheet-2004
Form Page 12
Form Issued:
Form Revised:
Copyright © 2015 UL LLC
2004-01-30
2015-04-13
Only those products bearing the UL Mark should be considered as being covered by UL.
Project No.
4786996266
Tested by:
Gao Yingru
File
EX16058
Page
Date
13
2013-11-20
to 201311-22
Compliance Criteria: As referenced in Section 24 of UL 448.
1. Pump developed the rated capacity and pressure (as least 40 psi)
2. Pump developed 65 percent of rated pressure at 150 percent of rated
capacity.
3. Maximum net pressure developed did not exceed 140 percent of rated
pressure.
4. Maximum horsepower required to drive pump was determined.
[1]
For vertical turbine pumps only.
[2]
For pumps connected to suction piping (split case, in-line, end suction, etc.)
insert either “LIFT” for 15 ft. suction lift or “HEAD” for Positive pressure
test condition. For vertical turbine pumps (without suction vessel), insert
“MIN SUB” for Minimum submergence [and] [or] “MAX SPAN” for Maximum bearing
span test condition(s).
Refer to attached sheets for data recorded during test and performance curve
information.
ULS-00448-QXJY-DataSheet-2004
Form Page 13
Form Issued:
Form Revised:
Copyright © 2015 UL LLC
2004-01-30
2015-04-13
Only those products bearing the UL Mark should be considered as being covered by UL.
Project No.
4786996266
Tested by:
Gao Yingru
File
EX16058
Page
Date
14
2013-11-20
to 201311-22
UL 448, Edition 10, Section 24
ULC C448, Edition 2, Section 4.2
OPERATION
Model Designation:
350QHBC
Number of Stages:
Outlet Tested for Multistage
Multiport Pump
2-10
Minimum Submergence, in. [1]:
Refer to individual test sheets
Maximum Bearing Span, in. [1]:
10ft
Suction Pipe Diameter, in.:
N/A
[ ] same as discharge
Discharge Pipe Diameter, in.:
N/A
[ ] same as suction
Suction Elevation:
N/A
Refer to individual
test sheets
[ ] same as discharge
Discharge Elevation:
[ ] same as suction
MaxImp, Maxstage
Rated
Speed,
rpm
Impeller
Diameter(s),
_inch_
(units)
Rated
Capacity,
gpm
Size, in.
(inlet x
outlet)
Rated Net
Pressure,
psig
500
10
286
1620
9.84
750
10
270
1620
9.84
1000
10
253
1620
9.84
Min
Submergence
and
Max
bearing Span
Impeller
Diameter(s),
_inch_
(units)
Test
Condition[2]
Test
Condition[2]
Results
A
A
A
MinImp, Minstage
Rated
Capacity,
gpm
Size, in.
(inlet x
outlet)
Rated Net
Pressure,
psig
Rated
Speed,
rpm
500
10
47
1620
9.06
750
10
45
1620
9.06
1000
10
41
1620
9.06
Min
Submergence
and
Max
bearing Span
Results
A
A
A
Results Key: [A] Acceptable [B] Unacceptable
Note: The distance from water surface to center of pressure gauge (0.7m) was added to
discharge pressure.
The power of gear box was removed from power of pump.
Compliance Criteria:
As referenced in Section 24 of UL 448.
ULS-00448-QXJY-DataSheet-2004
Form Page 14
Form Issued:
Form Revised:
Copyright © 2015 UL LLC
2004-01-30
2015-04-13
Only those products bearing the UL Mark should be considered as being covered by UL.
Project No.
4786996266
Tested by:
Gao Yingru
File
EX16058
Page
Date
15
2013-11-20
to 201311-22
1. Pump developed the rated capacity and pressure (as least 40 psi)
2. Pump developed 65 percent of rated pressure at 150 percent of rated
capacity.
3. Maximum net pressure developed did not exceed 140 percent of rated
pressure.
4. Maximum horsepower required to drive pump was determined.
[1]
For vertical turbine pumps only.
[2]
For pumps connected to suction piping (split case, in-line, end suction, etc.)
insert either “LIFT” for 15 ft. suction lift or “HEAD” for Positive pressure
test condition. For vertical turbine pumps (without suction vessel), insert
“MIN SUB” for Minimum submergence [and] [or] “MAX SPAN” for Maximum bearing
span test condition(s).
Refer to attached sheets for data recorded during test and performance curve
information.
ULS-00448-QXJY-DataSheet-2004
Form Page 15
Form Issued:
Form Revised:
Copyright © 2015 UL LLC
2004-01-30
2015-04-13
Only those products bearing the UL Mark should be considered as being covered by UL.
Project No.
4786996266
Tested by:
Gao Yingru
File
EX16058
Page
Date
16
2013-11-20
to 201311-22
UL 448, Edition 10, Section 24
ULC C448, Edition 2, Section 4.2
OPERATION
Model Designation:
350QHBC
Number of Stages:
Outlet Tested for Multistage
Multiport Pump
2-7
Minimum Submergence, in. [1]:
Refer to individual test sheets
Maximum Bearing Span, in. [1]:
10ft
Suction Pipe Diameter, in.:
N/A
[ ] same as discharge
Discharge Pipe Diameter, in.:
N/A
[ ] same as suction
Suction Elevation:
N/A
Refer to individual
test sheets
[ ] same as discharge
Discharge Elevation:
[ ] same as suction
MaxImp, Maxstage
Rated
Speed,
rpm
Impeller
Diameter(s),
_inch_
(units)
Rated
Capacity,
gpm
Size, in.
(inlet x
outlet)
Rated Net
Pressure,
psig
750
10
228
1770
9.84
1000
10
216
1770
9.84
1250
10
201
1770
9.84
Min
Submergence
and
Max
bearing Span
Impeller
Diameter(s),
_inch_
(units)
Test
Condition[2]
Test
Condition[2]
Results
A
A
A
MinImp, Minstage
Rated
Capacity,
gpm
Size, in.
(inlet x
outlet)
Rated Net
Pressure,
psig
Rated
Speed,
rpm
750
10
52
1770
9.06
1000
10
48
1770
9.06
1250
10
44
1770
9.06
Min
Submergence
and
Max
bearing Span
Results
A
A
B[2]
Results Key: [A] Acceptable [B] Unacceptable
Note: The distance from water surface to center of pressure gauge (0.7m) was added to
discharge pressure.
The power of gear box was removed from power of pump.
Compliance Criteria: As referenced in Section 24 of UL 448.
1. Pump developed the rated capacity and pressure (as least 40 psi)
ULS-00448-QXJY-DataSheet-2004
Form Page 16
Form Issued:
Form Revised:
Copyright © 2015 UL LLC
2004-01-30
2015-04-13
Only those products bearing the UL Mark should be considered as being covered by UL.
Project No.
4786996266
Tested by:
Gao Yingru
File
EX16058
Page
Date
17
2013-11-20
to 201311-22
2. Pump developed 65 percent of rated pressure at 150 percent of rated
capacity.
3. Maximum net pressure developed did not exceed 140 percent of rated
pressure.
4. Maximum horsepower required to drive pump was determined.
[1]
For vertical turbine pumps only.
[2]
For pumps connected to suction piping (split case, in-line, end suction, etc.)
insert either “LIFT” for 15 ft. suction lift or “HEAD” for Positive pressure
test condition. For vertical turbine pumps (without suction vessel), insert
“MIN SUB” for Minimum submergence [and] [or] “MAX SPAN” for Maximum bearing
span test condition(s).
Refer to attached sheets for data recorded during test and performance curve
information.
ULS-00448-QXJY-DataSheet-2004
Form Page 17
Form Issued:
Form Revised:
Copyright © 2015 UL LLC
2004-01-30
2015-04-13
Only those products bearing the UL Mark should be considered as being covered by UL.
Project No.
4786996266
Tested by:
Gao Yingru
File
EX16058
Page
Date
18
2013-11-20
to 201311-22
UL 448, Edition 10, Section 24
ULC C448, Edition 2, Section 4.2
OPERATION
Model Designation:
350QHBC
Number of Stages:
Outlet Tested for Multistage
Multiport Pump
2-7
Minimum Submergence, in. [1]:
Refer to individual test sheets
Maximum Bearing Span, in. [1]:
10ft
Suction Pipe Diameter, in.:
N/A
[ ] same as discharge
Discharge Pipe Diameter, in.:
N/A
[ ] same as suction
Suction Elevation:
N/A
Refer to individual
test sheets
[ ] same as discharge
Discharge Elevation:
[ ] same as suction
MaxImp, Maxstage
Rated
Speed,
rpm
Impeller
Diameter(s),
_inch_
(units)
Rated
Capacity,
gpm
Size, in.
(inlet x
outlet)
Rated Net
Pressure,
psig
750
10
266
1900
9.84
1000
10
253
1900
9.84
1250
10
238
1900
9.84
Min
Submergence
and
Max
bearing Span
Impeller
Diameter(s),
_inch_
(units)
Test
Condition[2]
Test
Condition[2]
Results
A
A
A
MinImp, Minstage
Rated
Capacity,
gpm
Size, in.
(inlet x
outlet)
Rated Net
Pressure,
psig
Rated
Speed,
rpm
750
10
61
1900
9.06
1000
10
56
1900
9.06
1250
10
52
1900
9.06
Min
Submergence
and
Max
bearing Span
Results
A
A
A
Results Key: [A] Acceptable [B] Unacceptable
Note: The distance from water surface to center of pressure gauge (0.7m) was added to
discharge pressure.
The power of gear box was removed from power of pump.
Compliance Criteria: As referenced in Section 24 of UL 448.
1. Pump developed the rated capacity and pressure (as least 40 psi)
ULS-00448-QXJY-DataSheet-2004
Form Page 18
Form Issued:
Form Revised:
Copyright © 2015 UL LLC
2004-01-30
2015-04-13
Only those products bearing the UL Mark should be considered as being covered by UL.
Project No.
4786996266
Tested by:
Gao Yingru
File
EX16058
Page
Date
19
2013-11-20
to 201311-22
2. Pump developed 65 percent of rated pressure at 150 percent of rated
capacity.
3. Maximum net pressure developed did not exceed 140 percent of rated
pressure.
4. Maximum horsepower required to drive pump was determined.
[1]
For vertical turbine pumps only.
[2]
For pumps connected to suction piping (split case, in-line, end suction, etc.)
insert either “LIFT” for 15 ft. suction lift or “HEAD” for Positive pressure
test condition. For vertical turbine pumps (without suction vessel), insert
“MIN SUB” for Minimum submergence [and] [or] “MAX SPAN” for Maximum bearing
span test condition(s).
Refer to attached sheets for data recorded during test and performance curve
information.
ULS-00448-QXJY-DataSheet-2004
Form Page 19
Form Issued:
Form Revised:
Copyright © 2015 UL LLC
2004-01-30
2015-04-13
Only those products bearing the UL Mark should be considered as being covered by UL.
Project No.
4786996266
Tested by:
Gao Yingru
File
EX16058
Page
Date
20
2013-11-20
to 201311-22
UL 448, Edition 10, Section 24
ULC C448, Edition 2, Section 4.2
OPERATION
Model Designation:
400QHBC
Number of Stages:
2 to 8
Minimum Submergence, in. [1]:
Refer to individual test sheets
Maximum Bearing Span, in. [1]:
10ft
Suction Pipe Diameter, in.:
N/A
[ ] same as discharge
Discharge Pipe Diameter, in.:
N/A
[ ] same as suction
Suction Elevation:
N/A
Refer to individual
test sheets
[ ] same as discharge
Discharge Elevation:
[ ] same as suction
MaxImp, MaxStage
Rated
Speed,
rpm
Impeller
Diameter(s),
__inch___
(units)
Rated
Capacity,
gpm
Size, in.
(inlet x
outlet)
Rated Net
Pressure,
psig
1250
10
227
1470
10.94
1500
10
217
1470
10.94
Test
Condition[2]
Min
Submergence
and
Max
bearing Span
Results
A
A
MinImp, MinStage
Rated
Speed,
rpm
Impeller
Diameter(s),
__inch__
(units)
Rated
Capacity,
gpm
Size, in.
(inlet x
outlet)
Rated Net
Pressure,
psig
1250
10
43
1470
10.12
1500
10
40
1470
10.12
Test
Condition[2]
Min
Submergence
and
Max
bearing Span
Results
A
A
Results Key: [A] Acceptable [B] Unacceptable
Note: The distance from water surface to center of pressure gauge (0.7m) was added to
discharge pressure.
The power of gear box was removed from power of pump.
Compliance Criteria: As referenced in Section 24 of UL 448.
1. Pump developed the rated capacity and pressure (as least 40 psi)
2. Pump developed 65 percent of rated pressure at 150 percent of
rated capacity.
3. Maximum net pressure developed did not exceed 140 percent of
rated pressure.
4. Maximum horsepower required to drive pump was determined.
ULS-00448-QXJY-DataSheet-2004
Form Page 20
Form Issued:
Form Revised:
Copyright © 2015 UL LLC
2004-01-30
2015-04-13
Only those products bearing the UL Mark should be considered as being covered by UL.
Project No.
4786996266
Tested by:
Gao Yingru
File
EX16058
Page
Date
21
2013-11-20
to 201311-22
[1]
For vertical turbine pumps only.
[2]
For pumps connected to suction piping (split case, in-line, end suction,
etc.) insert either “LIFT” for 15 ft. suction lift or “HEAD” for
Positive pressure test condition. For vertical turbine pumps (without
suction vessel), insert “MIN SUB” for Minimum submergence [and] [or]
“MAX SPAN” for Maximum bearing span test condition(s).
Refer to attached sheets for data recorded during test and performance
curve information.
ULS-00448-QXJY-DataSheet-2004
Form Page 21
Form Issued:
Form Revised:
Copyright © 2015 UL LLC
2004-01-30
2015-04-13
Only those products bearing the UL Mark should be considered as being covered by UL.
Project No.
4786996266
Tested by:
Gao Yingru
File
EX16058
Page
Date
22
2013-11-20
to 201311-22
UL 448, Edition 10, Section 24
ULC C448, Edition 2, Section 4.2
OPERATION
Model Designation:
400QHBC
Number of Stages:
2 to 8
Minimum Submergence, in. [1]:
Refer to individual test sheets
Maximum Bearing Span, in. [1]:
10ft
Suction Pipe Diameter, in.:
N/A
[ ] same as discharge
Discharge Pipe Diameter, in.:
N/A
[ ] same as suction
Suction Elevation:
N/A
Refer to individual
test sheets
[ ] same as discharge
Discharge Elevation:
[ ] same as suction
MaxImp, MaxStage
Rated
Speed,
rpm
Impeller
Diameter(s),
inch_
(units)
Rated
Capacity,
gpm
Size, in.
(inlet x
outlet)
Rated Net
Pressure,
psig
1250
10
282
1620
10.94
1500
10
271
1620
10.94
Test
Condition[2]
Min
Submergence
and
Max
bearing Span
Results
A
A
MinImp, MinStage
Rated
Speed,
rpm
Impeller
Diameter(s),
inch_
(units)
Rated
Capacity,
gpm
Size, in.
(inlet x
outlet)
Rated Net
Pressure,
psig
1250
10
54
1620
10.12
1500
10
51
1620
10.12
Test
Condition[2]
Min
Submergence
and
Max
bearing Span
Results
A
A
Results Key: [A] Acceptable [B] Unacceptable
Note: The distance from water surface to center of pressure gauge (0.7m) was added to
discharge pressure.
The power of gear box was removed from power of pump.
Compliance Criteria: As referenced in Section 24 of UL 448.
1. Pump developed the rated capacity and pressure (as least 40 psi)
2. Pump developed 65 percent of rated pressure at 150 percent of
rated capacity.
3. Maximum net pressure developed did not exceed 140 percent of
rated pressure.
ULS-00448-QXJY-DataSheet-2004
Form Page 22
Form Issued:
Form Revised:
Copyright © 2015 UL LLC
2004-01-30
2015-04-13
Only those products bearing the UL Mark should be considered as being covered by UL.
Project No.
4786996266
Tested by:
Gao Yingru
File
EX16058
Page
Date
23
2013-11-20
to 201311-22
4. Maximum horsepower required to drive pump was determined.
[1]
For vertical turbine pumps only.
[2]
For pumps connected to suction piping (split case, in-line, end suction,
etc.) insert either “LIFT” for 15 ft. suction lift or “HEAD” for
Positive pressure test condition. For vertical turbine pumps (without
suction vessel), insert “MIN SUB” for Minimum submergence [and] [or]
“MAX SPAN” for Maximum bearing span test condition(s).
Refer to attached sheets for data recorded during test and performance
curve information.
ULS-00448-QXJY-DataSheet-2004
Form Page 23
Form Issued:
Form Revised:
Copyright © 2015 UL LLC
2004-01-30
2015-04-13
Only those products bearing the UL Mark should be considered as being covered by UL.
Project No.
4786996266
Tested by:
Gao Yingru
File
EX16058
Page
Date
24
2013-11-20
to 201311-22
UL 448, Edition 10, Section 24
ULC C448, Edition 2, Section 4.2
OPERATION
Model Designation:
400QHBC
Number of Stages:
2 to 6
Minimum Submergence, in. [1]:
Refer to individual test sheets
Maximum Bearing Span, in. [1]:
10ft
Suction Pipe Diameter, in.:
N/A
[ ] same as discharge
Discharge Pipe Diameter, in.:
N/A
[ ] same as suction
Suction Elevation:
N/A
Refer to individual
test sheets
[ ] same as discharge
Discharge Elevation:
[ ] same as suction
MaxImp, MaxStage
Rated
Speed,
rpm
Impeller
Diameter(s),
___inch____
(units)
Rated
Capacity,
gpm
Size, in.
(inlet x
outlet)
Rated Net
Pressure,
psig
1500
10
245
1770
10.94
2000
10
219
1770
10.94
Test
Condition[2]
Min
Submergence
and
Max
bearing Span
Results
A
A
MinImp, MinStage
Rated
Speed,
rpm
Impeller
Diameter(s),
___inch____
(units)
Rated
Capacity,
gpm
Size, in.
(inlet x
outlet)
Rated Net
Pressure,
psig
1500
10
66
1770
10.12
2000
10
57
1770
10.12
Test
Condition[2]
Min
Submergence
and
Max
bearing Span
Results
A
B[2,3]
Results Key: [A] Acceptable [B] Unacceptable
Note: The distance from water surface to center of pressure gauge (0.7m) was added to
discharge pressure.
The power of gear box was removed from power of pump.
Compliance Criteria: As referenced in Section 24 of UL 448.
1. Pump developed the rated capacity and pressure (as least 40 psi)
2. Pump developed 65 percent of rated pressure at 150 percent of
rated capacity.
3. Maximum net pressure developed did not exceed 140 percent of
rated pressure.
ULS-00448-QXJY-DataSheet-2004
Form Page 24
Form Issued:
Form Revised:
Copyright © 2015 UL LLC
2004-01-30
2015-04-13
Only those products bearing the UL Mark should be considered as being covered by UL.
Project No.
4786996266
Tested by:
Gao Yingru
File
EX16058
Page
Date
25
2013-11-20
to 201311-22
4. Maximum horsepower required to drive pump was determined.
[1]
For vertical turbine pumps only.
[2]
For pumps connected to suction piping (split case, in-line, end suction,
etc.) insert either “LIFT” for 15 ft. suction lift or “HEAD” for
Positive pressure test condition. For vertical turbine pumps (without
suction vessel), insert “MIN SUB” for Minimum submergence [and] [or]
“MAX SPAN” for Maximum bearing span test condition(s).
Refer to attached sheets for data recorded during test and performance
curve information.
ULS-00448-QXJY-DataSheet-2004
Form Page 25
Form Issued:
Form Revised:
Copyright © 2015 UL LLC
2004-01-30
2015-04-13
Only those products bearing the UL Mark should be considered as being covered by UL.
Project No.
4786996266
Tested by:
Gao Yingru
File
EX16058
Page
Date
26
2013-11-20
to 201311-22
UL 448, Edition 10, Section 24
ULC C448, Edition 2, Section 4.2
OPERATION
Model Designation:
400QHBC
Number of Stages:
2 to 6
Minimum Submergence, in. [1]:
Refer to individual test sheets
Maximum Bearing Span, in. [1]:
10ft
Suction Pipe Diameter, in.:
N/A
[ ] same as discharge
Discharge Pipe Diameter, in.:
N/A
[ ] same as suction
Suction Elevation:
N/A
Refer to individual
test sheets
[ ] same as discharge
Discharge Elevation:
[ ] same as suction
MaxImp, MaxStage
Rated
Speed,
rpm
Impeller
Diameter(s),
___inch____
(units)
Rated
Capacity,
gpm
Size, in.
(inlet x
outlet)
Rated Net
Pressure,
psig
1500
10
287
1900
10.94
2000
10
261
1900
10.94
Test
Condition[2]
Min
Submergence
and
Max
bearing Span
Results
A
A
MinImp, MinStage
Rated
Speed,
rpm
Impeller
Diameter(s),
___inch____
(units)
Rated
Capacity,
gpm
Size, in.
(inlet x
outlet)
Rated Net
Pressure,
psig
1500
10
78
1900
10.12
2000
10
69
1900
10.12
Test
Condition[2]
Min
Submergence
and
Max
bearing Span
Results
A
A
Results Key: [A] Acceptable [B] Unacceptable
Note: The distance from water surface to center of pressure gauge (0.7m) was added to
discharge pressure.
The power of gear box was removed from power of pump.
Compliance Criteria: As referenced in Section 24 of UL 448.
1. Pump developed the rated capacity and pressure (as least 40 psi)
2. Pump developed 65 percent of rated pressure at 150 percent of
rated capacity.
3. Maximum net pressure developed did not exceed 140 percent of
rated pressure.
ULS-00448-QXJY-DataSheet-2004
Form Page 26
Form Issued:
Form Revised:
Copyright © 2015 UL LLC
2004-01-30
2015-04-13
Only those products bearing the UL Mark should be considered as being covered by UL.
Project No.
4786996266
Tested by:
Gao Yingru
File
EX16058
Page
Date
27
2013-11-20
to 201311-22
4. Maximum horsepower required to drive pump was determined.
[1]
For vertical turbine pumps only.
[2]
For pumps connected to suction piping (split case, in-line, end suction,
etc.) insert either “LIFT” for 15 ft. suction lift or “HEAD” for
Positive pressure test condition. For vertical turbine pumps (without
suction vessel), insert “MIN SUB” for Minimum submergence [and] [or]
“MAX SPAN” for Maximum bearing span test condition(s).
Refer to attached sheets for data recorded during test and performance
curve information.
ULS-00448-QXJY-DataSheet-2004
Form Page 27
Form Issued:
Form Revised:
Copyright © 2015 UL LLC
2004-01-30
2015-04-13
Only those products bearing the UL Mark should be considered as being covered by UL.
Project No.
4786996266
Tested by:
Gao Yingru
File
Page
Date
END OF DATASHEET PACKAGE.
ULS-00448-QXJY-DataSheet-2004
Form Page 28
EX16058
28
2013-11-20
to 201311-22
THIS PAGE INTENTIONALLY LEFT BLANK
Form Issued:
Form Revised:
Copyright © 2015 UL LLC
2004-01-30
2015-04-13
Only those products bearing the UL Mark should be considered as being covered by UL.