Project No. 4786996266 LABORATORY DATA PACKAGE File EX16085 Page 1 Number of pages in this package __59__ [ including additional pages _N/A___ ] (Fill in when using printed copy as record) CLIENT INFORMATION Company Name TIANJIN PUYOU MECHANICAL & ELECTRICAL EQUIPMENT MFG CO LTD Address 190 Middle Rd Fortune Centre Unit 14-10 , 188979 Singapore AUDIT INFORMATION: Description of Tests UL Standard for Safety for Centrifugal Stationary Fire Pumps for Fire-Protection Service ULC Other Recognized Document, Guide for the Investigation of Pumps for Fire Protection Service [] Tests Conducted by1 [x] UL Staff conducting or witnessing testing Per Standard No. UL 448 Edition/ Revision Date ULC/ORDC448-79 10/ February 05, 2016 2/ December 1979 Gao Yingru (WTDP, TMP, WMT only) [] UL Staff supervising UL Staff in training []Authorized Signatory Rossen Marinov (CTDP, TPTDP, TCP, PPP, SMT) Printed Name Signature. Include date for CTDP, TPTDP, TCP, PPP, WMT, TMP, SMT TESTS TO BE CONDUCTED: Test No. 1 Done3 x Test Name HYDROSTATIC STRENGTH 2 X OPERATION [ ] Comments/Parameters [x] Tests Conducted by2 [ ] Link to separate data files4 Gao Yingru,2013-11-20 to 201311-22 Gao Yingru,2013-11-20 to 201311-22 Instructions 1 - When all tests are conducted by one person, name can be inserted here instead of including name on each page containing data. 2 - When test conducted by more than one person, name of person conducting the test can be inserted next to the test name instead of including name on each page containing data. Test dates may be recorded here instead of entering test dates on the individual datasheet pages. ULS-00448-QXJY-DataSheet-2004 Form Page 1 Form Issued: Form Revised: Copyright © 2015 UL LLC 2004-01-30 2015-04-13 Only those products bearing the UL Mark should be considered as being covered by UL. Project No. 4786996266 LABORATORY DATA PACKAGE File EX16085 Page 2 3 - Use of this field is optional and may be employed differently. If used to include a date instead of entering the testing date on the individual datasheet pages, the date shall be the date the test was conducted. 4 – Link to separate data files for a test can be inserted here. The link must be to a server that is accessible to UL staff, that provides for backup, required retention periods and a path, including file name, that does not change and result in a broken link. Not applicable to DAP. Special Instructions - [ ] Unless specified otherwise in the individual Methods, the tests shall be conducted under the following ambient conditions. Confirmation of these conditions shall be recorded at the time the test is conducted. Ambient Temperature, C ± Relative Humidity, % ± Barometric Pressure, mBar ± [x] No general environmental conditions are specified in the Standard(s) or have been identified that could affect the test results or measurements. RISK ANALYSIS RELATED TO TESTING PERFORMANCE: The following types of risks have been identified. Take necessary precautions. This list is not all inclusive. [x] Electric shock [ ] Radiation [ ] Energy related hazards [ ] Chemical hazards [ ] Fire [x] Noise [x] Heat related hazards [x] Vibration [x] Mechanical [ ] Other (Specify)__ ULS-00448-QXJY-DataSheet-2004 Form Page 2 Form Issued: Form Revised: Copyright © 2015 UL LLC 2004-01-30 2015-04-13 Only those products bearing the UL Mark should be considered as being covered by UL. Project No. 4786996266 LABORATORY DATA PACKAGE File EX16085 Page 3 Conversion Instructions – • Length 1 inch = 25.4 millimeter 1 millimeter = 0.0394 inch 1 foot = 12 inches 1 inch = 0.0833 feet • Weight 1 pound = 0.4536 kilogram 1 kilogram = 2.2046 pound • Flow 1 gallon/minute [US] = 0.2271 cubic meter/hour 1 cubic meter/hour = 4.4029 gallon/minute [US] • Pressure 1 pound/square inch = 0.0689 bar 1 bar = 14.5038 pound/square inch 1 pound/square inch = 0.7032 meter of head 1 meter of head = 1.4220 pound/square inch ULS-00448-QXJY-DataSheet-2004 Form Page 3 Form Issued: Form Revised: Copyright © 2015 UL LLC 2004-01-30 2015-04-13 Only those products bearing the UL Mark should be considered as being covered by UL. Project No. 4786996266 Tested by: Gao Yingru File EX16058 Page Date 4 2013-11-20 to 201311-22 WITNESS TEST DATA PROGRAM (WTDP) INFORMATION: Environment: Accommodations and Environmental conditions, including proper power source meet the requirements of the test standard or UL default criteria (ISO/IEC 17025 Clause 5.3.1, 5.3.2. 5.3.3, 5.3.4) [ ]Yes [ ]No [x]N/A Personnel: Lab Management shall authorize personnel to operate particular types of equipment used in testing. (ISO/IEC 17025 5.5.3) [x]Yes [ ]No Equipment: Testing is being conducted within the test equipment calibration dates. (See Test Instrument Information Page and ISO/IEC 17025 5.5.1, 5.5.2, 5.5.4, 5.5.5, 5.5.8,) [x]Yes [ ]No Calibrations for testing equipment is traceable to SI Units. Refer to 00-OP-C0032 (Calibration Certificate Analysis). (ISO/IEC 17025 5.6.2.2) [x]Yes [ ]No Critical Consumables: Critical consumables are compliant with test standard requirements. (ISO/IEC 17025 Clause 4.6) [ ]Yes [ ]No [x]N/A Sample Identification: Identification of items to be tested has been made (e.g. model no., Serial No., etc.) (See Test Sample Identification page and ISO/IEC 17025 Clause 5.8.2) [x]Yes [ ]No Additional Requirements: Testing at a third party laboratory selected by UL and not part of the Third Party Test Data Program requires a Mutual Nondisclosure (NDA) and Confidentiality Agreement, 00-LE-F0025, or alternate agreement form approved by UL’s Legal Department to be stored and included with the Test Package. [ ]Yes [ ]No [x]N/A Summary: The test facility [ was ][ was not ] deemed to have the environment and capabilities necessary to perform the tests included in this data package. ULS-00448-QXJY-DataSheet-2004 Form Page 4 Form Issued: Form Revised: Copyright © 2015 UL LLC 2004-01-30 2015-04-13 Only those products bearing the UL Mark should be considered as being covered by UL. Project No. 4786996266 Tested by: Gao Yingru File EX16058 Page Date 5 2013-11-20 to 201311-22 [x] The CAS Staff as indicated below, (a competent L1, L2 or L3 in a similar CCN/Standard for a similar test method) was utilized to conduct the witnessing of tests on behalf of the project handler. (Please complete the table below to document the rationale and approval.) Name of UL Staff conducting WTDP Rossen Marinov CCN/Standard to be witnessed QXXW Test(s) to be witnessed All L1, L2 or L3 Competency L3 Similar CCN/Standard Competency N/A L3 Reviewer Approval & Date (Similar CCN/Standard) Bob Xia [ ] The Field Services Staff Member, as indicated below, (with a competent program competency as authorized by the FOM) was informed and utilized to conduct the witnessing of tests on behalf of the project handler. (Please complete the table below to document the information and approval.) Name of UL Staff conducting WTDP CCN/Standard to be witnessed ULS-00448-QXJY-DataSheet-2004 Form Page 5 Test(s) to be witnessed FOM Approver (name) Form Issued: Form Revised: Copyright © 2015 UL LLC L3 Reviewer Approval & Date 2004-01-30 2015-04-13 Only those products bearing the UL Mark should be considered as being covered by UL. Project No. 4786996266 Tested by: Gao Yingru File EX16058 Page Date 6 2013-11-20 to 201311-22 TEST LOCATION: (To be completed by Staff Conducting the Testing) []UL or Affiliate [X]WTDP []CTDP []TPTDP []TCP []PPP []WMT []TMP []SMT Company Name: TIANJIN PUYOU MECHANICAL & ELECTRICAL EQUIPMENT MFG CO LTD Address: No 7. Beijing St. Jinnan Ecomomic Development Area (west Area), Tianjin, P.R., China ULS-00448-QXJY-DataSheet-2004 Form Page 6 Form Issued: Form Revised: Copyright © 2015 UL LLC 2004-01-30 2015-04-13 Only those products bearing the UL Mark should be considered as being covered by UL. Project No. 4786996266 Tested by: Gao Yingru File EX16058 Page Date 7 2013-11-20 to 201311-22 TEST EQUIPMENT INFORMATION [x] UL test equipment information is recorded on Meter Use in UL’s Laboratory Project Management (LPM) database. [ ] UL test equipment information is recorded on <<insert location and local laboratory equipment system identification.>> Inst. ID No. Instrument Type Test Number +, Test Title or Conditioning 6-76 Stopwatch 0609537 Function /Range Last Cal. Date Next Cal. Date 1,2, OPERATION 0 to 7200 Sec 2013-1021 2014-10-21 Pressure Gauge 1, HYDROSTATIC STRENGTH 0 to 10 MPa 2013-0827 2014-08-27 1205103 Pressure Gauge 2, OPERATION 0 to 4 MPa 2013-1022 2014-10-22 1308102 Pressure Gauge 2, OPERATION 0 to 6 MPa 2013-0822 2014-08-22 03023 Flowmeter 2, OPERATION 0 to 300 M^3/Hr 2013-1015 2014-10-15 13005 Flowmeter 2, OPERATION 0 to 650 M^3/Hr 2013-1015 2014-10-15 1# Measuring Tape 2, OPERATION 0 to 1000 mm 2013-0913 2014-09-13 1306428 AF Torque Meter 2, OPERATION 50Nm to 5kNm 20 to 30000RPM 2013-0830 2014-08-30 + - If Test Number is used, the Test Number must be identified on the data sheet pages or on the Data Sheet Package cover page. The following additional information is required when using client’s or rented equipment, or when a UL ID Number for an instrument number is not used. The Inst. ID No. below corresponds to the Inst. ID No. above. Inst. ID No. 6-76 0609537 1205103 1308102 03023 13005 1# Make/Model/Serial Number/Asset No. TINAN FU/PC396/6-76 Leierda Instrument Co Ltd/0-10MPa/0609537 Xi’an Xiyi Huashan Instrument Manufacturer/0-4MPa/1205103 Xi’an Xiyi Huashan Instrument Manufacturer/0-4MPa/1308102 Zhonghuan Tianyi Co Ltd/LWGY-150/03023 Zhonghuan Tianyi Co Ltd/LWGY-200/13005 Xiongshi/5m/1# ULS-00448-QXJY-DataSheet-2004 Form Page 7 Form Issued: Form Revised: Copyright © 2015 UL LLC 2004-01-30 2015-04-13 Only those products bearing the UL Mark should be considered as being covered by UL. Project No. 4786996266 Tested by: Gao Yingru Inst. ID No. 1306428AF File EX16058 Page Date 8 2013-11-20 to 201311-22 Make/Model/Serial Number/Asset No. Beijing Sanjing Technology Co Ltd/10000AF/1306428AF ULS-00448-QXJY-DataSheet-2004 Form Page 8 Form Issued: Form Revised: Copyright © 2015 UL LLC 2004-01-30 2015-04-13 Only those products bearing the UL Mark should be considered as being covered by UL. Project No. 4786996266 Tested by: Gao Yingru File EX16058 Page Date 9 2013-11-20 to 201311-22 TEST SAMPLE IDENTIFICATION: The table below is provided to establish correlation of sample numbers to specific product related information. Refer to this table when a test identifies a test sample by "Sample No." only. Sample Card No. N/A Date Received N/A Rated Capacity, GPM 500 750 1000 500 750 1000 750 1000 [] Test No.+ Sample No. All N/A Manufacturer, Product Identification and Ratings [Pumping Equipment for Fire Service] (Centrifugal Fire Pumps) Centrifugal Fire Pumps, Vertical Turbine, For requested ratings refer to the table below. Model Dsg Rated Net Pressure Range, psi Approx Speed, RPM Number of Stages 350QHBC 40-47 1470 2 350QHBC 58-70 1470 3 350QHBC 77-233 1470 4 - 10 350QHBC 40-44 1470 2 350QHBC 54-65 1470 3 350QHBC 72-218 1470 4 - 10 350QHBC 40 1470 2 350QHBC 49-61 1470 3 350QHBC 47-57 1620 2 350QHBC 71-86 1620 3 350QHBC 95-286 1620 4 – 10 350QHBC 45-54 1620 2 350QHBC 67-81 1620 3 350QHBC 90-270 1620 4 – 10 350QHBC 41-51 1620 2 350QHBC 62-76 1620 3 350QHBC 53-65 1770 2 350QHBC 79-98 1770 3 350QHBC 105-229 1770 4 – 7 350QHBC 48-62 1770 2 ULS-00448-QXJY-DataSheet-2004 Form Page 9 Form Issued: Form Revised: Copyright © 2015 UL LLC 2004-01-30 2015-04-13 Only those products bearing the UL Mark should be considered as being covered by UL. Project No. 4786996266 Tested by: Gao Yingru 1250 1250 1500 1250 1500 1500 2000 1500 2000 File EX16058 Page Date 10 2013-11-20 to 201311-22 350QHBC 73-217 1770 3 – 7 350QHBC 40-58 1770 2 350QHBC 66-202 1770 3 - 7 400QHBC 44-57 1470 2 400QHBC 66-228 1470 3 - 8 400QHBC 40-55 1470 2 400QHBC 61-218 1470 3 - 8 400QHBC 55-71 1620 2 400QHBC 82-283 1620 3 - 8 400QHBC 51-68 1620 2 400QHBC 77-272 1620 3 - 8 400QHBC 66-82 1770 2 400QHBC 99-123 1770 3 400QHBC 132-246 1770 4 - 6 400QHBC 40-73 1770 2 400QHBC 87-220 1770 3 - 6 400QHBC 78-96 1900 2 400QHBC 117-144 1900 3 400QHBC 156-288 1900 4 - 6 400QHBC 69-87 1900 2 400QHBC 104-262 1900 3 - 6 + - If Test Number is used, the Test Number or Numbers the sample was used in must be identified on the data sheet pages or on the Data Sheet Package cover page. [ ] Sampling Procedure [ ] This document contains data or information using color and if printed, should be printed in color to retain legibility and the information represented by the color. ULS-00448-QXJY-DataSheet-2004 Form Page 10 Form Issued: Form Revised: Copyright © 2015 UL LLC 2004-01-30 2015-04-13 Only those products bearing the UL Mark should be considered as being covered by UL. Project No. 4786996266 Tested by: Gao Yingru HYDROSTATIC STRENGTH File EX16058 Page Date 11 2013-11-20 to 201311-22 UL 448, Edition 10, Section 26 ULC C448, Edition 2, Section 4.3 Maximum Working Test Test Pressure, Pressure, No. Model MPa MPa 1-A 350QHBC* 2.10 4.22 1-B 400QHBC** 2.33 4.69 Results Key: [A] Acceptable [B] Unacceptable *Test Pressure Dwell Time, min. 5 5 Results A A Compliance Criterion: The sample shall withstand the test pressure without rupture. *UL 448 requires a 1-minute test pressure dwell time and ULC/ORD-C448-79 requires a 5-minute test pressure dwell time. Notes: The following components have been subjected to hydrostatic testing: *350QHBC – 10 Stage bowl & column assembly **400QHBC – 8 Stage bowl & column assembly ULS-00448-QXJY-DataSheet-2004 Form Page 11 Form Issued: Form Revised: Copyright © 2015 UL LLC 2004-01-30 2015-04-13 Only those products bearing the UL Mark should be considered as being covered by UL. Project No. 4786996266 Tested by: Gao Yingru File EX16058 Page Date 12 2013-11-20 to 201311-22 UL 448, Edition 10, Section 24 ULC C448, Edition 2, Section 4.2 OPERATION Model Designation: 350QHBC Number of Stages: Outlet Tested for Multistage Multiport Pump 2-10 Minimum Submergence, in. [1]: Refer to individual test sheets Maximum Bearing Span, in. [1]: 10ft Suction Pipe Diameter, in.: N/A [ ] same as discharge Discharge Pipe Diameter, in.: N/A [ ] same as suction Suction Elevation: N/A Refer to individual test sheets [ ] same as discharge Discharge Elevation: [ ] same as suction MaxImp, Maxstage Rated Speed, rpm Impeller Diameter(s), _inch_ (units) Rated Capacity, gpm Size, in. (inlet x outlet) Rated Net Pressure, psig 500 10 233 1470 9.84 750 10 218 1470 9.84 1000 10 202 1470 9.84 Min Submergence and Max bearing Span Impeller Diameter(s), _inch_ (units) Test Condition[2] Test Condition[2] Results A A A MinImp, Minstage Rated Capacity, gpm Size, in. (inlet x outlet) Rated Net Pressure, psig Rated Speed, rpm 500 10 40 1470 9.06 750 10 40 1470 9.06 1000 10 40 1470 9.06 Min Submergence and Max bearing Span Results A* A* A* Note: The distance from water surface to center of pressure gauge (0.7m) was added to discharge pressure. The power of gear box was removed from power of pump. *Regarding minimum impeller&minimum stage, Client preferred higher net pressure to comply UL requirement, as the result is lower than 40 psi. Results Key: [A] Acceptable [B] Unacceptable ULS-00448-QXJY-DataSheet-2004 Form Page 12 Form Issued: Form Revised: Copyright © 2015 UL LLC 2004-01-30 2015-04-13 Only those products bearing the UL Mark should be considered as being covered by UL. Project No. 4786996266 Tested by: Gao Yingru File EX16058 Page Date 13 2013-11-20 to 201311-22 Compliance Criteria: As referenced in Section 24 of UL 448. 1. Pump developed the rated capacity and pressure (as least 40 psi) 2. Pump developed 65 percent of rated pressure at 150 percent of rated capacity. 3. Maximum net pressure developed did not exceed 140 percent of rated pressure. 4. Maximum horsepower required to drive pump was determined. [1] For vertical turbine pumps only. [2] For pumps connected to suction piping (split case, in-line, end suction, etc.) insert either “LIFT” for 15 ft. suction lift or “HEAD” for Positive pressure test condition. For vertical turbine pumps (without suction vessel), insert “MIN SUB” for Minimum submergence [and] [or] “MAX SPAN” for Maximum bearing span test condition(s). Refer to attached sheets for data recorded during test and performance curve information. ULS-00448-QXJY-DataSheet-2004 Form Page 13 Form Issued: Form Revised: Copyright © 2015 UL LLC 2004-01-30 2015-04-13 Only those products bearing the UL Mark should be considered as being covered by UL. Project No. 4786996266 Tested by: Gao Yingru File EX16058 Page Date 14 2013-11-20 to 201311-22 UL 448, Edition 10, Section 24 ULC C448, Edition 2, Section 4.2 OPERATION Model Designation: 350QHBC Number of Stages: Outlet Tested for Multistage Multiport Pump 2-10 Minimum Submergence, in. [1]: Refer to individual test sheets Maximum Bearing Span, in. [1]: 10ft Suction Pipe Diameter, in.: N/A [ ] same as discharge Discharge Pipe Diameter, in.: N/A [ ] same as suction Suction Elevation: N/A Refer to individual test sheets [ ] same as discharge Discharge Elevation: [ ] same as suction MaxImp, Maxstage Rated Speed, rpm Impeller Diameter(s), _inch_ (units) Rated Capacity, gpm Size, in. (inlet x outlet) Rated Net Pressure, psig 500 10 286 1620 9.84 750 10 270 1620 9.84 1000 10 253 1620 9.84 Min Submergence and Max bearing Span Impeller Diameter(s), _inch_ (units) Test Condition[2] Test Condition[2] Results A A A MinImp, Minstage Rated Capacity, gpm Size, in. (inlet x outlet) Rated Net Pressure, psig Rated Speed, rpm 500 10 47 1620 9.06 750 10 45 1620 9.06 1000 10 41 1620 9.06 Min Submergence and Max bearing Span Results A A A Results Key: [A] Acceptable [B] Unacceptable Note: The distance from water surface to center of pressure gauge (0.7m) was added to discharge pressure. The power of gear box was removed from power of pump. Compliance Criteria: As referenced in Section 24 of UL 448. ULS-00448-QXJY-DataSheet-2004 Form Page 14 Form Issued: Form Revised: Copyright © 2015 UL LLC 2004-01-30 2015-04-13 Only those products bearing the UL Mark should be considered as being covered by UL. Project No. 4786996266 Tested by: Gao Yingru File EX16058 Page Date 15 2013-11-20 to 201311-22 1. Pump developed the rated capacity and pressure (as least 40 psi) 2. Pump developed 65 percent of rated pressure at 150 percent of rated capacity. 3. Maximum net pressure developed did not exceed 140 percent of rated pressure. 4. Maximum horsepower required to drive pump was determined. [1] For vertical turbine pumps only. [2] For pumps connected to suction piping (split case, in-line, end suction, etc.) insert either “LIFT” for 15 ft. suction lift or “HEAD” for Positive pressure test condition. For vertical turbine pumps (without suction vessel), insert “MIN SUB” for Minimum submergence [and] [or] “MAX SPAN” for Maximum bearing span test condition(s). Refer to attached sheets for data recorded during test and performance curve information. ULS-00448-QXJY-DataSheet-2004 Form Page 15 Form Issued: Form Revised: Copyright © 2015 UL LLC 2004-01-30 2015-04-13 Only those products bearing the UL Mark should be considered as being covered by UL. Project No. 4786996266 Tested by: Gao Yingru File EX16058 Page Date 16 2013-11-20 to 201311-22 UL 448, Edition 10, Section 24 ULC C448, Edition 2, Section 4.2 OPERATION Model Designation: 350QHBC Number of Stages: Outlet Tested for Multistage Multiport Pump 2-7 Minimum Submergence, in. [1]: Refer to individual test sheets Maximum Bearing Span, in. [1]: 10ft Suction Pipe Diameter, in.: N/A [ ] same as discharge Discharge Pipe Diameter, in.: N/A [ ] same as suction Suction Elevation: N/A Refer to individual test sheets [ ] same as discharge Discharge Elevation: [ ] same as suction MaxImp, Maxstage Rated Speed, rpm Impeller Diameter(s), _inch_ (units) Rated Capacity, gpm Size, in. (inlet x outlet) Rated Net Pressure, psig 750 10 228 1770 9.84 1000 10 216 1770 9.84 1250 10 201 1770 9.84 Min Submergence and Max bearing Span Impeller Diameter(s), _inch_ (units) Test Condition[2] Test Condition[2] Results A A A MinImp, Minstage Rated Capacity, gpm Size, in. (inlet x outlet) Rated Net Pressure, psig Rated Speed, rpm 750 10 52 1770 9.06 1000 10 48 1770 9.06 1250 10 44 1770 9.06 Min Submergence and Max bearing Span Results A A B[2] Results Key: [A] Acceptable [B] Unacceptable Note: The distance from water surface to center of pressure gauge (0.7m) was added to discharge pressure. The power of gear box was removed from power of pump. Compliance Criteria: As referenced in Section 24 of UL 448. 1. Pump developed the rated capacity and pressure (as least 40 psi) ULS-00448-QXJY-DataSheet-2004 Form Page 16 Form Issued: Form Revised: Copyright © 2015 UL LLC 2004-01-30 2015-04-13 Only those products bearing the UL Mark should be considered as being covered by UL. Project No. 4786996266 Tested by: Gao Yingru File EX16058 Page Date 17 2013-11-20 to 201311-22 2. Pump developed 65 percent of rated pressure at 150 percent of rated capacity. 3. Maximum net pressure developed did not exceed 140 percent of rated pressure. 4. Maximum horsepower required to drive pump was determined. [1] For vertical turbine pumps only. [2] For pumps connected to suction piping (split case, in-line, end suction, etc.) insert either “LIFT” for 15 ft. suction lift or “HEAD” for Positive pressure test condition. For vertical turbine pumps (without suction vessel), insert “MIN SUB” for Minimum submergence [and] [or] “MAX SPAN” for Maximum bearing span test condition(s). Refer to attached sheets for data recorded during test and performance curve information. ULS-00448-QXJY-DataSheet-2004 Form Page 17 Form Issued: Form Revised: Copyright © 2015 UL LLC 2004-01-30 2015-04-13 Only those products bearing the UL Mark should be considered as being covered by UL. Project No. 4786996266 Tested by: Gao Yingru File EX16058 Page Date 18 2013-11-20 to 201311-22 UL 448, Edition 10, Section 24 ULC C448, Edition 2, Section 4.2 OPERATION Model Designation: 350QHBC Number of Stages: Outlet Tested for Multistage Multiport Pump 2-7 Minimum Submergence, in. [1]: Refer to individual test sheets Maximum Bearing Span, in. [1]: 10ft Suction Pipe Diameter, in.: N/A [ ] same as discharge Discharge Pipe Diameter, in.: N/A [ ] same as suction Suction Elevation: N/A Refer to individual test sheets [ ] same as discharge Discharge Elevation: [ ] same as suction MaxImp, Maxstage Rated Speed, rpm Impeller Diameter(s), _inch_ (units) Rated Capacity, gpm Size, in. (inlet x outlet) Rated Net Pressure, psig 750 10 266 1900 9.84 1000 10 253 1900 9.84 1250 10 238 1900 9.84 Min Submergence and Max bearing Span Impeller Diameter(s), _inch_ (units) Test Condition[2] Test Condition[2] Results A A A MinImp, Minstage Rated Capacity, gpm Size, in. (inlet x outlet) Rated Net Pressure, psig Rated Speed, rpm 750 10 61 1900 9.06 1000 10 56 1900 9.06 1250 10 52 1900 9.06 Min Submergence and Max bearing Span Results A A A Results Key: [A] Acceptable [B] Unacceptable Note: The distance from water surface to center of pressure gauge (0.7m) was added to discharge pressure. The power of gear box was removed from power of pump. Compliance Criteria: As referenced in Section 24 of UL 448. 1. Pump developed the rated capacity and pressure (as least 40 psi) ULS-00448-QXJY-DataSheet-2004 Form Page 18 Form Issued: Form Revised: Copyright © 2015 UL LLC 2004-01-30 2015-04-13 Only those products bearing the UL Mark should be considered as being covered by UL. Project No. 4786996266 Tested by: Gao Yingru File EX16058 Page Date 19 2013-11-20 to 201311-22 2. Pump developed 65 percent of rated pressure at 150 percent of rated capacity. 3. Maximum net pressure developed did not exceed 140 percent of rated pressure. 4. Maximum horsepower required to drive pump was determined. [1] For vertical turbine pumps only. [2] For pumps connected to suction piping (split case, in-line, end suction, etc.) insert either “LIFT” for 15 ft. suction lift or “HEAD” for Positive pressure test condition. For vertical turbine pumps (without suction vessel), insert “MIN SUB” for Minimum submergence [and] [or] “MAX SPAN” for Maximum bearing span test condition(s). Refer to attached sheets for data recorded during test and performance curve information. ULS-00448-QXJY-DataSheet-2004 Form Page 19 Form Issued: Form Revised: Copyright © 2015 UL LLC 2004-01-30 2015-04-13 Only those products bearing the UL Mark should be considered as being covered by UL. Project No. 4786996266 Tested by: Gao Yingru File EX16058 Page Date 20 2013-11-20 to 201311-22 UL 448, Edition 10, Section 24 ULC C448, Edition 2, Section 4.2 OPERATION Model Designation: 400QHBC Number of Stages: 2 to 8 Minimum Submergence, in. [1]: Refer to individual test sheets Maximum Bearing Span, in. [1]: 10ft Suction Pipe Diameter, in.: N/A [ ] same as discharge Discharge Pipe Diameter, in.: N/A [ ] same as suction Suction Elevation: N/A Refer to individual test sheets [ ] same as discharge Discharge Elevation: [ ] same as suction MaxImp, MaxStage Rated Speed, rpm Impeller Diameter(s), __inch___ (units) Rated Capacity, gpm Size, in. (inlet x outlet) Rated Net Pressure, psig 1250 10 227 1470 10.94 1500 10 217 1470 10.94 Test Condition[2] Min Submergence and Max bearing Span Results A A MinImp, MinStage Rated Speed, rpm Impeller Diameter(s), __inch__ (units) Rated Capacity, gpm Size, in. (inlet x outlet) Rated Net Pressure, psig 1250 10 43 1470 10.12 1500 10 40 1470 10.12 Test Condition[2] Min Submergence and Max bearing Span Results A A Results Key: [A] Acceptable [B] Unacceptable Note: The distance from water surface to center of pressure gauge (0.7m) was added to discharge pressure. The power of gear box was removed from power of pump. Compliance Criteria: As referenced in Section 24 of UL 448. 1. Pump developed the rated capacity and pressure (as least 40 psi) 2. Pump developed 65 percent of rated pressure at 150 percent of rated capacity. 3. Maximum net pressure developed did not exceed 140 percent of rated pressure. 4. Maximum horsepower required to drive pump was determined. ULS-00448-QXJY-DataSheet-2004 Form Page 20 Form Issued: Form Revised: Copyright © 2015 UL LLC 2004-01-30 2015-04-13 Only those products bearing the UL Mark should be considered as being covered by UL. Project No. 4786996266 Tested by: Gao Yingru File EX16058 Page Date 21 2013-11-20 to 201311-22 [1] For vertical turbine pumps only. [2] For pumps connected to suction piping (split case, in-line, end suction, etc.) insert either “LIFT” for 15 ft. suction lift or “HEAD” for Positive pressure test condition. For vertical turbine pumps (without suction vessel), insert “MIN SUB” for Minimum submergence [and] [or] “MAX SPAN” for Maximum bearing span test condition(s). Refer to attached sheets for data recorded during test and performance curve information. ULS-00448-QXJY-DataSheet-2004 Form Page 21 Form Issued: Form Revised: Copyright © 2015 UL LLC 2004-01-30 2015-04-13 Only those products bearing the UL Mark should be considered as being covered by UL. Project No. 4786996266 Tested by: Gao Yingru File EX16058 Page Date 22 2013-11-20 to 201311-22 UL 448, Edition 10, Section 24 ULC C448, Edition 2, Section 4.2 OPERATION Model Designation: 400QHBC Number of Stages: 2 to 8 Minimum Submergence, in. [1]: Refer to individual test sheets Maximum Bearing Span, in. [1]: 10ft Suction Pipe Diameter, in.: N/A [ ] same as discharge Discharge Pipe Diameter, in.: N/A [ ] same as suction Suction Elevation: N/A Refer to individual test sheets [ ] same as discharge Discharge Elevation: [ ] same as suction MaxImp, MaxStage Rated Speed, rpm Impeller Diameter(s), inch_ (units) Rated Capacity, gpm Size, in. (inlet x outlet) Rated Net Pressure, psig 1250 10 282 1620 10.94 1500 10 271 1620 10.94 Test Condition[2] Min Submergence and Max bearing Span Results A A MinImp, MinStage Rated Speed, rpm Impeller Diameter(s), inch_ (units) Rated Capacity, gpm Size, in. (inlet x outlet) Rated Net Pressure, psig 1250 10 54 1620 10.12 1500 10 51 1620 10.12 Test Condition[2] Min Submergence and Max bearing Span Results A A Results Key: [A] Acceptable [B] Unacceptable Note: The distance from water surface to center of pressure gauge (0.7m) was added to discharge pressure. The power of gear box was removed from power of pump. Compliance Criteria: As referenced in Section 24 of UL 448. 1. Pump developed the rated capacity and pressure (as least 40 psi) 2. Pump developed 65 percent of rated pressure at 150 percent of rated capacity. 3. Maximum net pressure developed did not exceed 140 percent of rated pressure. ULS-00448-QXJY-DataSheet-2004 Form Page 22 Form Issued: Form Revised: Copyright © 2015 UL LLC 2004-01-30 2015-04-13 Only those products bearing the UL Mark should be considered as being covered by UL. Project No. 4786996266 Tested by: Gao Yingru File EX16058 Page Date 23 2013-11-20 to 201311-22 4. Maximum horsepower required to drive pump was determined. [1] For vertical turbine pumps only. [2] For pumps connected to suction piping (split case, in-line, end suction, etc.) insert either “LIFT” for 15 ft. suction lift or “HEAD” for Positive pressure test condition. For vertical turbine pumps (without suction vessel), insert “MIN SUB” for Minimum submergence [and] [or] “MAX SPAN” for Maximum bearing span test condition(s). Refer to attached sheets for data recorded during test and performance curve information. ULS-00448-QXJY-DataSheet-2004 Form Page 23 Form Issued: Form Revised: Copyright © 2015 UL LLC 2004-01-30 2015-04-13 Only those products bearing the UL Mark should be considered as being covered by UL. Project No. 4786996266 Tested by: Gao Yingru File EX16058 Page Date 24 2013-11-20 to 201311-22 UL 448, Edition 10, Section 24 ULC C448, Edition 2, Section 4.2 OPERATION Model Designation: 400QHBC Number of Stages: 2 to 6 Minimum Submergence, in. [1]: Refer to individual test sheets Maximum Bearing Span, in. [1]: 10ft Suction Pipe Diameter, in.: N/A [ ] same as discharge Discharge Pipe Diameter, in.: N/A [ ] same as suction Suction Elevation: N/A Refer to individual test sheets [ ] same as discharge Discharge Elevation: [ ] same as suction MaxImp, MaxStage Rated Speed, rpm Impeller Diameter(s), ___inch____ (units) Rated Capacity, gpm Size, in. (inlet x outlet) Rated Net Pressure, psig 1500 10 245 1770 10.94 2000 10 219 1770 10.94 Test Condition[2] Min Submergence and Max bearing Span Results A A MinImp, MinStage Rated Speed, rpm Impeller Diameter(s), ___inch____ (units) Rated Capacity, gpm Size, in. (inlet x outlet) Rated Net Pressure, psig 1500 10 66 1770 10.12 2000 10 57 1770 10.12 Test Condition[2] Min Submergence and Max bearing Span Results A B[2,3] Results Key: [A] Acceptable [B] Unacceptable Note: The distance from water surface to center of pressure gauge (0.7m) was added to discharge pressure. The power of gear box was removed from power of pump. Compliance Criteria: As referenced in Section 24 of UL 448. 1. Pump developed the rated capacity and pressure (as least 40 psi) 2. Pump developed 65 percent of rated pressure at 150 percent of rated capacity. 3. Maximum net pressure developed did not exceed 140 percent of rated pressure. ULS-00448-QXJY-DataSheet-2004 Form Page 24 Form Issued: Form Revised: Copyright © 2015 UL LLC 2004-01-30 2015-04-13 Only those products bearing the UL Mark should be considered as being covered by UL. Project No. 4786996266 Tested by: Gao Yingru File EX16058 Page Date 25 2013-11-20 to 201311-22 4. Maximum horsepower required to drive pump was determined. [1] For vertical turbine pumps only. [2] For pumps connected to suction piping (split case, in-line, end suction, etc.) insert either “LIFT” for 15 ft. suction lift or “HEAD” for Positive pressure test condition. For vertical turbine pumps (without suction vessel), insert “MIN SUB” for Minimum submergence [and] [or] “MAX SPAN” for Maximum bearing span test condition(s). Refer to attached sheets for data recorded during test and performance curve information. ULS-00448-QXJY-DataSheet-2004 Form Page 25 Form Issued: Form Revised: Copyright © 2015 UL LLC 2004-01-30 2015-04-13 Only those products bearing the UL Mark should be considered as being covered by UL. Project No. 4786996266 Tested by: Gao Yingru File EX16058 Page Date 26 2013-11-20 to 201311-22 UL 448, Edition 10, Section 24 ULC C448, Edition 2, Section 4.2 OPERATION Model Designation: 400QHBC Number of Stages: 2 to 6 Minimum Submergence, in. [1]: Refer to individual test sheets Maximum Bearing Span, in. [1]: 10ft Suction Pipe Diameter, in.: N/A [ ] same as discharge Discharge Pipe Diameter, in.: N/A [ ] same as suction Suction Elevation: N/A Refer to individual test sheets [ ] same as discharge Discharge Elevation: [ ] same as suction MaxImp, MaxStage Rated Speed, rpm Impeller Diameter(s), ___inch____ (units) Rated Capacity, gpm Size, in. (inlet x outlet) Rated Net Pressure, psig 1500 10 287 1900 10.94 2000 10 261 1900 10.94 Test Condition[2] Min Submergence and Max bearing Span Results A A MinImp, MinStage Rated Speed, rpm Impeller Diameter(s), ___inch____ (units) Rated Capacity, gpm Size, in. (inlet x outlet) Rated Net Pressure, psig 1500 10 78 1900 10.12 2000 10 69 1900 10.12 Test Condition[2] Min Submergence and Max bearing Span Results A A Results Key: [A] Acceptable [B] Unacceptable Note: The distance from water surface to center of pressure gauge (0.7m) was added to discharge pressure. The power of gear box was removed from power of pump. Compliance Criteria: As referenced in Section 24 of UL 448. 1. Pump developed the rated capacity and pressure (as least 40 psi) 2. Pump developed 65 percent of rated pressure at 150 percent of rated capacity. 3. Maximum net pressure developed did not exceed 140 percent of rated pressure. ULS-00448-QXJY-DataSheet-2004 Form Page 26 Form Issued: Form Revised: Copyright © 2015 UL LLC 2004-01-30 2015-04-13 Only those products bearing the UL Mark should be considered as being covered by UL. Project No. 4786996266 Tested by: Gao Yingru File EX16058 Page Date 27 2013-11-20 to 201311-22 4. Maximum horsepower required to drive pump was determined. [1] For vertical turbine pumps only. [2] For pumps connected to suction piping (split case, in-line, end suction, etc.) insert either “LIFT” for 15 ft. suction lift or “HEAD” for Positive pressure test condition. For vertical turbine pumps (without suction vessel), insert “MIN SUB” for Minimum submergence [and] [or] “MAX SPAN” for Maximum bearing span test condition(s). Refer to attached sheets for data recorded during test and performance curve information. ULS-00448-QXJY-DataSheet-2004 Form Page 27 Form Issued: Form Revised: Copyright © 2015 UL LLC 2004-01-30 2015-04-13 Only those products bearing the UL Mark should be considered as being covered by UL. Project No. 4786996266 Tested by: Gao Yingru File Page Date END OF DATASHEET PACKAGE. ULS-00448-QXJY-DataSheet-2004 Form Page 28 EX16058 28 2013-11-20 to 201311-22 THIS PAGE INTENTIONALLY LEFT BLANK Form Issued: Form Revised: Copyright © 2015 UL LLC 2004-01-30 2015-04-13 Only those products bearing the UL Mark should be considered as being covered by UL.