PRODUCED BY THE OPERATIONS DIRECTORATE OF ENERGY NETWORKS ASSOCIATION Technical Specification 12-6 Issue 2 2014 Time fuse-links for use with current transformer releases on circuit-breakers www.energynetworks.org PUBLISHING AND COPYRIGHT INFORMATION Supplied by ENA to: Nick Thompson (Schneider Electric). Delivered to: nick.thompson@se.com on 09/03/2021 at 10:38. © ENA 2021 Unauthorised sharing or distribution is prohibited. © 2014 Energy Networks Association All rights reserved. No part of this publication may be reproduced, stored in a retrieval system or transmitted in any form or by any means, electronic, mechanical, photocopying, recording or otherwise, without the prior written consent of Energy Networks Association. Specific enquiries concerning this document should be addressed to: Operations Directorate Energy Networks Association 6th Floor, Dean Bradley House 52 Horseferry Rd London SW1P 2AF This document has been prepared for use by members of the Energy Networks Association to take account of the conditions which apply to them. Advice should be taken from an appropriately qualified engineer on the suitability of this document for any other purpose. First published, 1973 Revised, 2014 Amendments since publication Issue Date Amendment 1 1973 First issue 2 2014 Major revision and updating of reference publications. This issue includes the following principal technical changes. Scope extended to cover protection of ENA TS 35-1 distribution transformers with rated powers up to and including 1 500 kVA for use on 11 kV and 20 kV systems. Rated current of low voltage distributor fuse-links changed to align with preferred values in ENA TS 12-08. New Clause 4: Classification added with requirement for time fuse-links to generally conform to BS EN 60269-1, BS 88-1 and BS HD 60269-2, BS 88-2. Clause 7.2: Mountings amended so covers have degree of protection not less than IP3X in accordance with BS EN 60529. Tables 2 & 3: LV distributor fuses with rated currents of 150 A, 300 A and 600 A changed to 200 A, 315 A and 630 A respectively to align with ENA TS 12-08. Time fuse-link selections added for 1 250 kVA and 1 500 kVA distribution transformers associated with 11 kV systems. New Table 4 added with time fuse-link selections for distribution transformers associated with 20 kV systems. Details of all other technical, general and editorial amendments are included in the associated Document Amendment Summary for this Issue (available on request from the Operations Directorate of ENA). ENA Technical Specification 12-6 Issue 2 2014 Page 3 Contents Supplied by ENA to: Nick Thompson (Schneider Electric). Delivered to: nick.thompson@se.com on 09/03/2021 at 10:38. © ENA 2021 Unauthorised sharing or distribution is prohibited. Foreword ................................................................................................................................ 5 1 Scope .............................................................................................................................. 7 2 Normative references ....................................................................................................... 7 3 Terms and definitions ....................................................................................................... 7 4 Classification .................................................................................................................... 8 5 Characteristics of fuses .................................................................................................... 8 6 5.1 Ratings ................................................................................................................... 8 5.2 Time/current characteristics .................................................................................... 8 5.3 Resistance .............................................................................................................. 8 Markings .......................................................................................................................... 9 7 Standard conditions for construction ................................................................................ 9 8 7.1 Construction and dimensions .................................................................................. 9 7.2 Mountings ............................................................................................................... 9 Tests ................................................................................................................................ 9 8.1 Type tests ............................................................................................................... 9 8.1.1 Temperature rise ......................................................................................... 9 8.1.2 Time/current characteristics ...................................................................... 10 8.1.3 Resistance ................................................................................................ 10 8.1.4 Duty .......................................................................................................... 10 Annex A (informative) Self Certification Conformance Declaration ...................................... 21 Annex B (informative) Selection of time fuse-links ............................................................... 23 B.0 B.1 B.2 B.3 B.4 General ................................................................................................................. 23 Inrush current of the distribution transformer ......................................................... 23 Overload rating of the distribution transformer ...................................................... 23 Faults in distribution transformer terminal zone ..................................................... 23 Discrimination between the low voltage distributor fuse-links and the distribution transformer high voltage circuit-breaker .............................................. 23 Annex C (informative) Explanatory notes ............................................................................ 26 C.0 C.1 C.2 General ................................................................................................................. 26 Clause 5.3 ............................................................................................................ 26 Clause 11.4........................................................................................................... 26 Figures Figure 1 — Time/current characteristics of time fuse-links.................................................... 17 Figure 2 — Dimensions of time fuse-links............................................................................. 18 Figure 3 — Circuit diagram for duty tests ............................................................................. 19 Figure 4 — Test rig for fuse-links.......................................................................................... 20 ENA Technical Specification 12-6 Issue 2 2014 Page 4 Supplied by ENA to: Nick Thompson (Schneider Electric). Delivered to: nick.thompson@se.com on 09/03/2021 at 10:38. © ENA 2021 Unauthorised sharing or distribution is prohibited. Tables Table 1 — Resistance of time fuse-links ................................................................................. 8 Table 2 — Selection of time fuse-link ratings for 11 kV systems ........................................... 12 Table 3 — Selection of time fuse-link ratings for 6.6 kV systems .......................................... 14 Table 4 — Selection of time fuse-link ratings for 20 kV systems ........................................... 15 ENA Technical Specification 12-6 Issue 2 2014 Page 5 Supplied by ENA to: Nick Thompson (Schneider Electric). Delivered to: nick.thompson@se.com on 09/03/2021 at 10:38. © ENA 2021 Unauthorised sharing or distribution is prohibited. Foreword This Technical Specification (TS) is published by the Energy Networks Association (ENA) and comes into effect from date of publication. It has been prepared under the authority of the ENA Engineering Policy and Standards Manager and has been approved for publication by the ENA Electricity Networks and Futures Group (ENFG). The approved abbreviated title of this engineering document is “ENA TS 12-6”. This issue cancels and replaces Issue 1 1973. This Specification has been revised with direction from the ENA Protection Assessment Panel to ensure requirements for time fuse-links conform to relevant BS EN Standards for fuse-links. The scope of this issue has been extended to cover protection of ENA TS 35-1 distribution transformers with rated powers up to and including 1 500 kVA for use on 11 kV and 20 kV systems. Level 1 headings in this issue have been aligned with those in BS HD 60269-2, BS 88-2 for the purposes on conformance declaration by manufacturers. Where the term “shall” or “must” is used in this document it means the requirement is mandatory. The term “may” is used to express permission. NOTE: Commentary, explanation and general informative material is presented in smaller type, and does not constitute a requirement. Supplied by ENA to: Nick Thompson (Schneider Electric). Delivered to: nick.thompson@se.com on 09/03/2021 at 10:38. © ENA 2021 Unauthorised sharing or distribution is prohibited. ENA Technical Specification 12-6 Issue 2 2014 Page 6 This page deliberately left blank ENA Technical Specification 12-6 Issue 2 2014 Page 7 Supplied by ENA to: Nick Thompson (Schneider Electric). Delivered to: nick.thompson@se.com on 09/03/2021 at 10:38. © ENA 2021 Unauthorised sharing or distribution is prohibited. 1 Scope The time fuse-links covered by this Specification are intended to protect distribution transformers covered by ENA TS 35-1 [N1] with rated powers from 200 kVA to 1 500 kVA and to discriminate with low voltage distributor fuse-links covered by ENA TS 12-08 [N2] connected to the transformer secondaries with current ratings up to 630 A. NOTE: Distribution transformers with rated powers exceeding 1 500 kVA are intended to be protected by relays. This Specification covers time fuse-links for use with current transformer release coils of circuitbreakers, where each protection element is fitted with one conventional a.c. release coil. They are primarily for use with standard 6.6 kV, 11 kV and 20 kV distribution switchgear as covered by ENA TS 41-36 [3] but may be used with other circuit-breakers. 2 Normative references The following referenced documents, in whole or part, are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. Standards publications BS 2572:1990, Specification for phenolic laminated sheet and epoxy cotton fabric laminated sheet BS EN 60269-1:2007+A1:2009, BS 88-1: 2007, Low-voltage fuses. General requirements BS HD 60269-2:2013, BS 88-2: 2013, Low-voltage fuses. Supplementary requirements for fuses for use by authorized person (fuses mainly for industrial application). Examples of standardized systems of fuses A to K BS EN 60529:1992+A2:2013, Degrees of protection provided by enclosures (IP code) Other publications [N1] ENA TS 35-1, Distribution transformers (from 16 kVA to 2 000 kVA) [N2] ENA TS 12-08, The application of fuse-links to 11 kV/400 V and 6.6 kV/400 V underground distribution networks [N3] ENA TS 41-36, Switchgear for service up to 36 kV (cable and overhead conductor connected) NOTE: ENA Engineering Documents are revised when necessary by the issue either of revised pages or complete new editions. It is important that users ascertain they are in possession of the latest issues. 3 Terms and definitions For the purposes of this document, the following terms and definitions apply. 3.1 FLC full load current 3.2 release coil current operated coil that operates the trip mechanism of a circuit-breaker Supplied by ENA to: Nick Thompson (Schneider Electric). Delivered to: nick.thompson@se.com on 09/03/2021 at 10:38. © ENA 2021 Unauthorised sharing or distribution is prohibited. ENA Technical Specification 12-6 Issue 2 2014 Page 8 3.3 time fuse-link fuse-link used to shunt a.c. release coils that have characteristics conforming to this Specification 4 Classification Time fuse-links shall generally conform to the requirements of BS EN 60269-1, BS 88-1 and BS HD 60269-2, BS 88-2 system E (bolted) except where modified by this Specification. 5 Characteristics of fuses 5.1 Ratings Time fuse-links shall have normal rated currents of 3 A, 5 A, 7.5 A, 10 A, 12.5 A and 15 A. A time fuse-link shall be capable of carrying its rated current indefinitely without causing a permanent change in the time/current characteristic and without exceeding the temperature rise permitted. 5.2 Time/current characteristics All time fuse-links shall operate within the boundaries of the time/current characteristics shown in Fig. 1. 5.3 Resistance The hot resistance of a time fuse-link, when measured in accordance with Clause 8.1.3 shall not exceed the appropriate value given in Table 1. Table 1 — Resistance of time fuse-links Time fuse-link rating (A) Resistance (Ω) 3 0.073 5 0.043 7.5 0.031 10 0.028 12.5 0.020 15 0.017 The impedance of release coils which are to be used in conjunction with the time fuse-links covered by this Specification should conform to the following in order that operation of the release may not occur due to spill current through the coil, so defeating discrimination in the event of a high fault current. a) Release coils which are set to operate at 2 A should have an impedance of 1.5 ohm or more when the release is in a reset condition. b) Release coils which are set to operate at 5 A should have an impedance of 0.24 ohm or more when the release is in a reset condition. ENA Technical Specification 12-6 Issue 2 2014 Page 9 6 Markings Supplied by ENA to: Nick Thompson (Schneider Electric). Delivered to: nick.thompson@se.com on 09/03/2021 at 10:38. © ENA 2021 Unauthorised sharing or distribution is prohibited. Each time fuse-link shall be marked with the following. a) Name or identity of manufacturer. b) Rated current. c) Manufacturer's list number. d) The word 'time fuse-link'. The rated current marking shall be in the position shown in Fig. 2. 7 Standard conditions for construction 7.1 Construction and dimensions Each time fuse-link shall be fitted with terminal tags and shall conform to Fig. 2. It shall be of sealed construction and suitable for withstanding the conditions of vibration and humidity experienced in service (see ENA TS 41-36 [3] for normal service conditions). The terminal tags shall be suitably plated to ensure a consistent low resistance connection. 7.2 Mountings Mountings for time fuse-links shall be designed to accept the standard link shown in Fig. 2. Securing of a link to its mounting, for both mechanical and electrical purposes, shall be by means of screws which engage with the terminal tags of the link. The screws shall be captive to the mounting and designed for manipulation by a screwdriver. The mounting shall be such that, when a time fuse-link is assembled to it, the link shall conform to Clause 5.2 regarding its time/current characteristic and Clause 8.1.1 regarding temperature rise. The mounting may be either front or back connected. If designed for front connection, should the assembly be external to the switchgear, the mounting shall be provided with a cover which completely shields the connections and the time fuse-links to degree of protection not less than IP3X in accordance with BS EN 60529. The material and the design of the mounting shall be such that the assembly is suitable for normal service conditions regarding both normal and fault current carrying capacity, vibration and humidity. Any terminals, connection screws or current carrying studs which are of a size less than M6 shall be made of phosphor-bronze or stainless steel and be not less in size than M5. 8 Tests 8.1 Type tests 8.1.1 Temperature rise Each rating of time fuse-link shall be tested for temperature rise at rated current in surroundings free from external draughts and mounted vertically in a test rig conforming to Fig. 4 in an ambient temperature between 15 °C and 40 °C inclusive. The temperature rise shall be measured at the point indicated on Fig. 4. Connections between the terminals of the test rig and the source of supply shall be by copper cables, pvc-insulated, size 7/0.67 mm. Each cable shall have a minimum length of 1 m. ENA Technical Specification 12-6 Issue 2 2014 Page 10 Supplied by ENA to: Nick Thompson (Schneider Electric). Delivered to: nick.thompson@se.com on 09/03/2021 at 10:38. © ENA 2021 Unauthorised sharing or distribution is prohibited. The temperature rise shall be measured by thermocouples attached by a low melting point alloy or by some equally effective means of attachment. After the fuse-link on test has carried its rated current continuously for sufficient time to allow its temperature to become steady, the temperature rise shall not exceed 40 °C. 8.1.2 Time/current characteristics Tests to prove compliance of the fuse-links with the time/current characteristics shown in Fig. 1 shall be conducted as follows. The fuse-link shall be tested in surroundings free from external draughts and mounted vertically in a test rig conforming to Fig. 4 in an ambient temperature between 15 °C and 40 °C inclusive. Connections between the terminals of the test rig and the source of supply shall be by copper cables, pvc-insulated, size 7/0.67 mm. Each cable shall have a minimum length of 1 m. At the beginning of each test, the connections, test rig and fuse-link shall each be at a temperature within plus or minus 10% of ambient temperature. Not less than six off time fuse-links of each current rating shall be tested at various values of current such that the results, when plotted, can be shown to result in a characteristic curve which lies within the appropriate envelope shown in Fig. 1. 8.1.3 Resistance The resistance of each rating of time fuse-link shall be measured at 60% of the melting time when carrying a direct current which causes melting in 0.2 seconds. The resistance values so measured shall not exceed the values given in Table 1. 8.1.4 Duty Time fuse-links conforming with this Specification shall be capable of operating satisfactorily under all conditions of fault which may occur in service. The tests for duty described in this clause are arranged to simulate actual service conditions. The tests shall be made from a single phase a.c. supply of frequency 50 Hz ± 2.5 Hz and the test circuit shall conform to Fig. 3. The test circuit consists of a current transformer the primary winding of which is energised from the test supply; the secondary winding being connected to a time fuse-link and coil connected in parallel. The coil shall have an impedance of 7.2 ohm minimum at a power factor between 0.5 and 0.7. If a release coil is used, these values shall apply in the reset condition. The characteristics of the current transformer and the magnitude of the primary test current shall be such that: a) when the time fuse-link is replaced by a solid link, the secondary current of the current transformer has a minimum steady state peak value of 1 400 A; b) when the time fuse-link is removed, the steady state voltage applied to the coil has a minimum peak value of 950 V. If a release coil is used, it must be held in the reset condition. The overall power factor of the test supply shall be between 0.2 and 0.3 whilst the voltage need not exceed that necessary to circulate the value of current required to satisfy conditions a) and b) above. ENA Technical Specification 12-6 Issue 2 2014 Page 11 Supplied by ENA to: Nick Thompson (Schneider Electric). Delivered to: nick.thompson@se.com on 09/03/2021 at 10:38. © ENA 2021 Unauthorised sharing or distribution is prohibited. Each test shall be made with the test supply set to conform to the foregoing requirements and the primary circuit shall be closed at an instant between 0° and 60° on a rising voltage wave. The test current shall flow for not less than 0.25 seconds. Three tests shall be made each with a time fuse-link of maximum current rating inserted in a test rig conforming to Fig. 4. In each test the fuse-link must operate without any of the following occurring. a) Damage sufficient to render unserviceable any parts of the assembly other than the time fuse-link itself. b) External arcing or bursting of the time fuse-link. c) Reduction of the insulation resistance below 100 000 ohms, when measured at 250 V within 3 minutes of the conclusion of the test. Two of the three tests shall be made with the metal cover of the test rig connected to one of the terminals of the secondary winding of the current transformer, the remaining test to be made with the metal cover connected to the other terminal of the secondary winding. Supplied by ENA to: Nick Thompson (Schneider Electric). Delivered to: nick.thompson@se.com on 09/03/2021 at 10:38. © ENA 2021 Unauthorised sharing ENA Technical Specification 12-6 Issue 2 2014 Page 12 Table 2 — Selection of time fuse-link ratings for 11 kV systems 1 2 3 4 5 6 7 8 9 10 Power Transformer Rating Transformer Primary FLC Current Transformer Ratio Maximum Sustained Current in Time Fuse-Link (150% Transformer Rating) Time FuseLink Rating Primary Current (0.6 x 11.5 x FLC) Current in Time FuseLink kV kVA A – A A A A Min. 11 200 10.5 40/5 2.0 3 72.4 9.05 50/5 1.6 3 72.4 11 300 15.8 40/5 3.0 7.5 108 50/5 2.4 5 108 40/5 3.1 7.5 50/5 2.5 40/5 11 11 11 11 11 315 500 750 800 1 000 16.6 26.2 39.4 42 52.5 121) 131) Discrimination with Distributor Fuse-Links1) for Phase/Phase Fault Phase/neutral fault in secondary terminal zone System Nominal Voltage 11 Operating Time of Time Fuse-Link (Seconds) Minimum 1 Second Operating Current of Time Fuse-Link Secondary Current Corresponding to Column 10 Maximum Distributor Fuse-Link Rating which may be used to achieve Discrimination Maximum 1 Second Operating Current of Distributor Fuse-Link Max. A A A A 0.36 0.66 6.9 1 215 160 1 200 7.2 0.75 3.5 6.9 1 520 200 1 500 13.5 1.00 4.0 13.8 2 430 315 2 300 10.8 0.80 5.0 10.5 2 310 315 2 300 114 14.2 0.85 1.9 13.8 2 430 315 2 300 5 114 11.4 0.62 1.6 10.5 2 310 315 2 300 4.9 12.5 181 22.6 0.74 2.0 22.0 3 870 400 3 600 50/5 3.9 10 181 18.1 0.74 1.7 17.0 3 740 400 3 600 80/5 3.7 10 272 17.0 0.95 3.0 17.0 6 000 630 5 800 100/5 3.0 7.5 272 13.6 1.00 4.1 13.8 6 070 630 5 800 80/5 3.9 10 290 18.1 0.74 1.7 17.0 6 000 630 5 800 100/5 3.2 7.5 290 14.5 0.65 2.0 13.8 6 070 630 5 800 80/5 4.9 12.5 362 22.6 0.74 2.0 22.0 7 740 630 5 800 100/5 3.9 10 362 18.1 0.74 1.7 17.0 7 480 630 5 800 11 1 250 65.6 100/5 4.9 12.5 453 22.6 0.74 2.0 22.0 9 860 630 5 800 11 1 500 78.7 100/5 5.9 12.5 543 27.1 0.34 0.62 22.0 9 680 630 5 800 Supplied by ENA to: Nick Thompson (Schneider Electric). Delivered to: nick.thompson@se.com on 09/03/2021 at 10:38. © ENA 2021 Unauthorised sharing ENA Technical Specification 12-6 Issue 2 2014 Page 13 NOTE 1: 300 kVA and 750 kVA power transformers and 40/5A and 80/5A current transformer ratios are included to cater for existing installations only. NOTE 2: The same time fuse-link selections may be used for 1 600 kVA distribution transformers as for 1 500 kVA units. 1) Based on distributor fuse-links having the most unfavourable time/current characteristics specified in ENA TS 12-08. Supplied by ENA to: Nick Thompson (Schneider Electric). Delivered to: nick.thompson@se.com on 09/03/2021 at 10:38. © ENA 2021 Unauthorised sharing ENA Technical Specification 12-6 Issue 2 2014 Page 14 Table 3 — Selection of time fuse-link ratings for 6.6 kV systems 1 2 3 4 5 6 7 8 9 10 11 121) Discrimination with Distributor Fuse-Links1) for Phase/Phase Fault Phase/neutral fault in secondary terminal zone System Nominal Voltage Power Transformer Rating Transformer Primary FLC Current Transformer Ratio Maximum Sustained Current in Time Fuse-Link (150% Transformer Rating) Time FuseLink Rating Primary Current (0.6 x 11.5 x FLC) Current in Time FuseLink kV kVA A – A A A A Min. Max. A A A A 6.6 200 17.5 40/5 3.3 7.5 121 15.1 0.64 1.4 13.8 1 460 160 1 200 50/5 2.6 5 121 12.1 0.63 1.6 10.5 1 385 160 1 200 6.6 300 26.2 40/5 4.9 12.5 181 22.6 0.75 2.0 22.0 2 320 315 2 300 50/5 3.9 10 181 18.1 0.72 1.6 17.0 2 245 250 1 900 40/5 5.2 12.5 190 23.8 0.62 1.4 22.0 2 320 315 2 300 50/5 4.2 10 190 19.0 0.60 1.2 17.0 2 245 250 1 900 80/5 4.1 10 302 18.9 0.63 1.3 17.0 3 590 400 3 6002) 100/5 3.3 7.5 302 15.1 0.64 1.4 13.8 3 640 400 3 600 80/5 6.2 15 453 28.3 0.90 2.8 29.0 6 140 630 5 800 100/5 4.9 12.5 453 22.6 0.75 2.1 22.0 5 810 630 5 800 80/5 6.6 15 482 30.1 0.78 2.0 29.0 6 140 630 5 800 100/5 5.3 12.5 482 24.1 0.58 1.2 22.0 5 810 630 5 800 80/5 8.2 15 605 37.8 0.40 0.66 29.0 6 140 630 5 800 100/5 6.6 15 605 30.2 0.94 1.7 29.0 7 650 630 5 800 6.6 6.6 6.6 6.6 6.6 315 500 750 800 1 000 27.6 43.8 65.5 70.0 87.6 Operating Minimum 1 Time of Time Second Operating Fuse-Link Current of Time (Seconds) Fuse-Link Secondary Current Corresponding to Column 10 Maximum Maximum 1 Distributor Fuse- Second Operating Link Rating which Current of may be used to Distributor Fuseachieve Link Discrimination NOTE: 200 kVA, 300 kVA and 750 kVA power transformers and 40/5A and 80/5A current transformer ratios are included to cater for existing installations only. 1) 2) 131) Based on distributor fuse-links having the most unfavourable time/current characteristics specified in ENA TS 12-08. The maximum 1 second operating current of a 400 A BS 88 Part 5 400 A J Type fuse is less than 3 600 A and has been shown to grade with a 10 A TLF for practical purposes. Supplied by ENA to: Nick Thompson (Schneider Electric). Delivered to: nick.thompson@se.com on 09/03/2021 at 10:38. © ENA 2021 Unauthorised sharing ENA Technical Specification 12-6 Issue 2 2014 Page 15 Table 4 — Selection of time fuse-link ratings for 20 kV systems 1 2 3 4 5 6 7 8 9 10 Power Transformer Rating kV kVA A 20 300 8.7 20 20 20 20 20 315 500 750 800 1 000 Transformer Current Primary Transformer FLC. Ratio 9.1 14.4 21.6 23.1 28.9 Maximum Sustained Current in Time Fuse-Link (150% Transformer Rating) Time FuseLink Rating Primary Current Current in Time (0.6 x 11.5 x FuseFLC) Link – A A A A Min. 40/5 1.6 3 60 7.5 50/5 2) - 2) - 2) - 2) 40/5 1.7 3 50/5 -2) 40/5 121) 131) Discrimination with Distributor Fuse-Links1) for Phase/Phase Fault Phase/neutral fault in secondary terminal zone System Nominal Voltage 11 Minimum 1 Second Operating Current of Time Fuse-Link Secondary Current Corresponding to Column 10 Max. A A A A 0.65 4 6.9 2 208 200 1 500 - 2) - 2) - 2) - 2) - 2) - -2) 63 7.9 0.48 1.2 6.9 2 208 200 1 500 -2) -2) -2) -2) -2) -2) -2) -2) -2) 2.7 5 99 12.4 0.52 1.2 10.5 3 360 315 2 300 50/5 2.2 3 9.9 0.27 0.48 6.9 2 760 315 2 300 80/5 2.0 3 9.3 0.33 0.64 6.9 4 416 400 3 600 100/5 1.6 3 7.4 0.68 5 6.9 5 520 400 3 600 80/5 2.2 3 9.9 0.27 0.48 6.9 4 416 400 3 600 100/5 1.7 3 7.9 0.48 1.2 6.9 5 520 400 3 600 80/5 2.7 5 12.4 0.52 1.2 10.5 6 720 630 5 800 100/5 2.2 3 9.9 0.27 0.48 6.9 5 520 400 3 600 149 159 199 Operating Time of Time Fuse-Link (Seconds) Maximum Maximum 1 Distributor Fuse- Second Operating Link Rating which Current of may be used to Distributor Fuseachieve Link Discrimination 20 1 250 36.1 100/5 2.7 5 249 12.4 0.52 1.2 10.5 8 400 630 5 800 20 1 500 43.3 100/5 3.2 7.5 299 14.9 0.62 1.4 13.8 11 040 630 5 800 NOTE 1: 300 kVA and 750 kVA power transformers and 40/5A and 80/5A current transformer ratios are included to cater for existing installations only. NOTE 2: The same time fuse-link selections may be used for 1 600 kVA distribution transformers as for 1 500 kVA units. Supplied by ENA to: Nick Thompson (Schneider Electric). Delivered to: nick.thompson@se.com on 09/03/2021 at 10:38. © ENA 2021 Unauthorised sharing ENA Technical Specification 12-6 Issue 2 2014 Page 16 NOTE 3: The time/current characteristics of 3 A time fuse-links are not compatible with faults in the secondary terminal zone of 200 kVA distribution transformers. 1) Based on distributor fuse-links having the most unfavourable time/current characteristics specified in ENA TS 12-08. 2) The time/current characteristics of 3 A time fuse-links are not compatible with faults in the secondary terminal zone of 300 kVA and 315 kVA distribution transformers with CT ratio of 50/5. Supplied by ENA to: Nick Thompson (Schneider Electric). Delivered to: nick.thompson@se.com on 09/03/2021 at 10:38. © ENA 2021 Unauthorised sharing or distribution is prohibited. ENA Technical Specification 12-6 Issue 2 2014 Page 17 Figure 1 — Time/current characteristics of time fuse-links Supplied by ENA to: Nick Thompson (Schneider Electric). Delivered to: nick.thompson@se.com on 09/03/2021 at 10:38. © ENA 2021 Unauthorised sharing or distribution is prohibited. ENA Technical Specification 12-6 Issue 2 2014 Page 18 Figure 2 — Dimensions of time fuse-links Supplied by ENA to: Nick Thompson (Schneider Electric). Delivered to: nick.thompson@se.com on 09/03/2021 at 10:38. © ENA 2021 Unauthorised sharing or distribution is prohibited. ENA Technical Specification 12-6 Issue 2 2014 Page 19 Figure 3 — Circuit diagram for duty tests Supplied by ENA to: Nick Thompson (Schneider Electric). Delivered to: nick.thompson@se.com on 09/03/2021 at 10:38. © ENA 2021 Unauthorised sharing or distribution is prohibited. ENA Technical Specification 12-6 Issue 2 2014 Page 20 Figure 4 — Test rig for fuse-links Supplied by ENA to: Nick Thompson (Schneider Electric). Delivered to: nick.thompson@se.com on 09/03/2021 at 10:38. © ENA 2021 Unauthorised sharing ENA Technical Specification 12-6 Issue 2 2014 Page 21 Annex A (informative) Self Certification Conformance Declaration ENA TS 12-6 Technical Specification for Time Fuse-Links (for use with Current Transformer Releases on Circuit Breakers) CLAUSE BY CLAUSE CONFORMANCE WITH ENA TS 12-6 Time fuse-links covered by ENA TS 12-6 shall conform with the clauses in this Specification. This check sheet identifies the clauses in ENA TS 12-6. The manufacturer shall declare conformance or otherwise, clause by clause, using the following levels of conformance declaration codes. Conformance declaration codes* Instructions for completion NA Clause is not applicable or appropriate to the product Cs1 the product is fully conforms with the requirements of this clause Cs2 the product partially conforms with the requirements of this clause Cs3 the product does not conform with the requirements of this clause Cs4 the product does not currently conform with the requirements of this clause, but the manufacturer proposes to modify and test the product in order to comply. When Cs1 code is entered no remark is necessary When any other code is entered the reason for non-conformance shall be entered Manufacturer: Product Reference: Name: Check sheet follows….. Signature: Date: Supplied by ENA to: Nick Thompson (Schneider Electric). Delivered to: nick.thompson@se.com on 09/03/2021 at 10:38. © ENA 2021 Unauthorised sharing ENA Technical Specification 12-6 Issue 2 2014 Page 22 Table A.1 — Self Certification Conformance Declaration Clause Clause Title 4 Classification 5 Characteristics of fuses 5.1 Ratings 5.2 Time/current characteristics 5.3 Resistance 6 Markings 7 Standards conditions for construction 7.1 Construction and dimensions 7.2 Mounting of time fuse-links 8 Tests 8.1 Type tests 8.1.1 Temperature rise 8.1.2 Time/current characteristics 8.1.3 Resistance 8.1.4 Duty Conformance code ENA TS 12-6 Conformance code BS EN 60269-21) 1) In addition, the manufacturer is to state the equivalent clause(s) in BS EN 60269-2, where they do not align with ENA TS 12-6. Remarks ENA Technical Specification 12-6 Issue 2 2014 Page 23 Supplied by ENA to: Nick Thompson (Schneider Electric). Delivered to: nick.thompson@se.com on 09/03/2021 at 10:38. © ENA 2021 Unauthorised sharing or distribution is prohibited. Annex B (informative) Selection of time fuse-links B.0 General Tables 2, 3 and 4 have been prepared to cover the normal conditions which are met in service where time fuse-links are applied. The following conditions were considered in preparing these tables. B.1 Inrush current of the distribution transformer The choice of time fuse-link in Tables 2, 3 and 4 takes account of available information concerning the inrush currents of distribution transformers. For this purpose a time fuse-link is deemed satisfactory if it withstands without deterioration, the equivalent of ten times transformer primary full load current for 0.1 second. B.2 Overload rating of the distribution transformer In each case the selected time fuse-link permits the distribution transformer to carry 150% of rated load without the continuous normal current rating of the time fuse-link being exceeded. B.3 Faults in distribution transformer terminal zone The selected time fuse-link will operate in less than 5 seconds with a phase/neutral or phase/earth fault in the low voltage terminal zone of the transformer, when the cable sheaths are directly bonded to the neutral. This is the criterion which sets an upper limit to the rating of the fuse-link selected in Tables 2, 3 and 4. All other aspects could be satisfied with a time fuse-link of higher current rating than is listed in Tables 2, 3 and 4, i.e: a) withstanding inrush currents; b) permitting transformer overloads; c) discriminating with distributor fuses. It is, of course, essential that a terminal zone earth fault on the secondary side of the transformer is cleared quickly by the high voltage circuit-breaker even with the earth fault current restricted by source impedance, fault impedance and low voltage cable impedance to a value less than that determined from the distribution transformer impedance alone. A value of 0.6 has been used to calculate the values stated in column 7. B.4 Discrimination between the low voltage distributor fuse-links and the distribution transformer high voltage circuit-breaker A phase/phase fault on a low voltage distributor results in the most onerous condition. This condition gives a maximum phase/phase current on the low voltage side of the transformer which is 0.866 times the symmetrical 3-phase fault value. The corresponding currents in the high voltage lines have ratios of 2:1:1 the maximum value being equal to the symmetrical 3phase fault value. Thus with this type of fault a time fuse-link in one phase may pass a current corresponding to a 3-phase symmetrical fault whereas the distributor fuse-link passes only 0.866 of the symmetrical fault value. ENA Technical Specification 12-6 Issue 2 2014 Page 24 Consider now the headings of Tables 2, 3 and 4. Supplied by ENA to: Nick Thompson (Schneider Electric). Delivered to: nick.thompson@se.com on 09/03/2021 at 10:38. © ENA 2021 Unauthorised sharing or distribution is prohibited. Column 5 is the secondary current for the current transformer when the distribution transformer is on 150% load. Column 7 gives the current in the high voltage line of a phase/neutral (or phase/earth) fault in the low voltage terminal zone of the transformer. The value is based on: A transformer impedance of 5% for a delta/star connected transformer, this results in a fault current equal to 100 5√3 = 11.5 times A factor of 0.6 is introduced to take account of the estimated average low voltage earth fault impedance. Column 8 lists the current passed through the time fuse-link and corresponds to column 7 multiplied by the inverse of the current transformer ratio. Column 9 gives the limits of time within which the time fuse-link will melt when passing the currents of column 8. Columns 10 to 13 are concerned with the performance of the maximum rated distributor fuselink in relation to the chosen time fuse-link. The distributor fuse-link ratings conform with the requirements of ENA TS 12-08 and are listed in column 12. The time fuse-link rating is selected so that the transformer secondary current corresponding to the minimum one-second operating current of the time fuse-link has a safety margin over the maximum one-second operating current of the distributor fuse-link. This is based upon the assumption that the characteristic of the distributor fuse-link approaches that of the time fuse-link most closely at the one-second ordinate. The arcing time of the power fuse-link is negligible at this melting time. Column 10 is the minimum current which will melt the time fuse-link in 1 second; it is read directly from Fig. 1. Column 11 is the corresponding current in the low voltage circuit and is derived by multiplying column 10 by the current transformer ratio and the current transformation factor of the distribution transformer. As mentioned earlier the condition considered is a phase/phase fault on the low voltage side of the transformer since this is the most onerous. Under this condition the transformation ratio of the distribution transformer for current is equal to the voltage ratio multiplied by 0.866, e.g. for an 11 kV/433 V transformer the fault current in the low voltage circuit is equal to the fault current in the high voltage line which has maximum value multiplied by the current transformation factor 11 000 × 0.866 = 22 433 Using line 1 as an example, column 11 is derived: 6.9 A × 40 × 22 = 1 215 A 5 Supplied by ENA to: Nick Thompson (Schneider Electric). Delivered to: nick.thompson@se.com on 09/03/2021 at 10:38. © ENA 2021 Unauthorised sharing or distribution is prohibited. ENA Technical Specification 12-6 Issue 2 2014 Page 25 Column 13 states the current which causes a distributor fuse-link of maximum rating given in column 12, having the most unfavourable time/current characteristics specified in ENA TS 1208, to melt in one second. In all cases this value is less than the minimum secondary current required to operate the time fuse-link in one second, thus ensuring that the distributor fuse-link clears before the time fuse-link melts. If a greater margin of discrimination is required, then a distributor fuse-link of less than maximum rating should be fitted and this can be chosen by comparing the value given in column 11 with the time/current characteristic envelopes of the appropriate distributor fuse-link given in ENA TS 12-08. ENA Technical Specification 12-6 Issue 2 2014 Page 26 Supplied by ENA to: Nick Thompson (Schneider Electric). Delivered to: nick.thompson@se.com on 09/03/2021 at 10:38. © ENA 2021 Unauthorised sharing or distribution is prohibited. Annex C (informative) Explanatory notes C.0 General The following notes are an explanation of the reasons underlying the form of the Specification. C.1 Clause 5.3 This clause is concerned with ensuring that the high voltage circuit-breaker does not open on the occurrence of a fault beyond the low voltage distributor fuse-link. The condition to be avoided is current spilling through the release coil whilst it is still shunted by an intact time fuse-link. Excess spill can occur so opening the circuit-breaker unless the relative impedances of the fuse-link and the release coil are suitably matched. Maximum spill occurs immediately prior to clearance of the low voltage distributor fuse-link since the time fuse-link is increasing its temperature, and hence its resistance, during the period of the fault. Danger of mal-operation through spill current is present only at high values of fault current approaching the maximum throughput of the distribution transformer. Under these conditions a typical low voltage distributor fuse-link selected in accordance with this Specification clears at a time when approximately 60% of the melting time of the time fuse-link has expired. The choice of a current which causes melting in 0.2 second (see Clause 9.3) is arbitrary since the time is not critical provided it is sufficiently short to prevent appreciable heat loss from the time fuse-link element during the melting period. The resistance is measured under these conditions by oscillographic means. It will be noted that the impedances quoted are for a release coil which has a burden of at least 6 VA in a reset condition irrespective of whether it has a rating of 2 A or 5 A. For release coils which have a burden below 6 VA, special consideration may be necessary. The higher operating voltage of the 2 A rated coil compared with the 5 A coil results in better performance of the 2 A coil from the point of view of spill current on high through faults. The 5 A coil with the minimum impedance 0.24 ohm, if shunted by a 5 A time fuse-link, is liable to receive under maximum through fault conditions a spill current in the region of 50% in excess of its setting; it is considered, however, that the rapid clearance of the low voltage distributor fuse-link would result in a current pulse of a time duration insufficient to operate the circuitbreaker release coil. C.2 Clause 11.4 This clause is intended to ensure the ability of the fuse-link to operate satisfactorily under maximum fault conditions. Since the output of typical current transformers under maximum fault conditions consists mainly of spikes of voltage and current which are very large in crest value when compared with the knee point voltage and associated current of the current transformer, the fuse-links must be tested for interruption under voltage and current conditions which are typical as to waveshape and which have values equivalent to or greater than those to be expected in practice. Supplied by ENA to: Nick Thompson (Schneider Electric). Delivered to: nick.thompson@se.com on 09/03/2021 at 10:38. © ENA 2021 Unauthorised sharing or distribution is prohibited. ENA Technical Specification 12-6 Issue 2 2014 Page 27 It is considered that measurement of the peak value of the current and voltage is the best criterion of their severity rather than r.m.s. or other values. It is not considered practicable to determine sinusoidal values of current and voltage which would be equivalent, so far as the fuse-link is concerned, to given spikes of these quantities. The peak values of current and voltage stipulated (1 400 A and 950 V) are derived from tests and calculations of typical current transformers. When stipulating the peak current and voltage which the time fuse-link must handle, a current transformer primary current of 21.9 kA was considered. The specification is thus applicable on systems having fault levels up to 350 MVA at 11 kV or 250 MVA at 6.6 kV. In performing the duty tests, a release coil of 7.2 ohm impedance when in the non-operated (or reset) condition is specified. This is considered to be the maximum impedance likely to be encountered in practice and hence gives the maximum recovery voltage with which the fuselink has to deal.