1. Basic details of PRS • Not required any external source of power to function • Pressure from the fluid on the diaphragm - activates the open/close action of the valves. • • • • High accuracy , High rangeability , Large flow Tight shut off capability Easy ,Fast & inexpensive maintenance Low noise level Slam Shutoff • The control mechanism is having latching arrangement that hold the main valve stem in open position. • The sensing element is pilot regulator (Pilot) which continuously monitors the line pressure which is to be safeguarded. • This pilot is spring loaded diaphragm type valve and incase of over-pressurization it gives pressure signal to control mechanism which in turn trips off the main valve. • The rack latched by the ball gets released resulting in downward movement of plug and plug rod by closing the valve. The visual indicator will indicate the position as “CLOSE”. Valve Pressure Regulator - Monitor valve (Fail to Close) • In the absence of the pressure in the system, the valve is kept in closed condition by the action of spring, which keeps the valve pressed against assembly. • the The plug desired control pressure is adjusted through set screw of pilot. • The plug rod is controlled by the diaphragm on which the following forces act a) Downwards : spring load , regulated pressure (Pa) in the chamber ‘E’ & the weight of the plug assembly. b) Upward : pressure(Pm) in the Motorization chamber ‘F’ Pressure Regulator – Active valve (Fail to Open) • If there is no pressure, the valve is kept in a fully open position by mean of spring force. • The pressure that modify the main valve position & thus control flow, is feed by the first stage of pilot that reduces the pressure slightly higher to outlet pressure and • communicate Downwards (outlet this pressure rises): Closing pressure directly pressure(Pm) in the to chamber ‘E’ & the the pilot input weight of the plug and assembly main regulator • diaphragm. Upwards (outlet pressure drops) : spring load , Motorization pressure(Pm) in the chamber ‘F’. Typical installation of Active & Monitor Configuration • Monitor regulator regulator. is installed upstream of the main (active) • The two regulators are virtually identical from the point of view of their mechanical construction. • Normally, Monitor remains wide open and Active regulator regulates the outlet pressure at the set value. • Monitor regulator takes over and regulates the controlled pressure at its set value, which is marginally higher than that of Active