Uploaded by Domaakola

Genset 2D Topview 2

advertisement
2470
3000
7180
9960
Oil tank
10kL tank
Dimensions
4300 × 2400 × 1500 mm
2780
15000
12000
Generator 2
Generator 1
Roads for oil truck / ute for maintenance
Day
tank
3000
Load
bank
Day
tank
1800
1. Good work
2. Please show the overall layout/ key plan and
North in the layout.
3. The road access to the Generators is blocked
from the Oil Tank. Make the road access, such
that a truck/ crane can travel up to the generators
and load bank.
4. Please use the MM template / project name/
drawing name/ drawing number/
designer/reviewr/checker/ date etc. details.
5. Stamp the drawing with preliminary drawing.
6. Remove the cloud marks.
7. Add the below notes.
A. THIS IS A PRELIMINARY LAYOUT, WHICH
WILL BE CHANGED DURING DESIGN STAGE.
B. THE CABLES FROM THE GENERATOR TO
THE LV EMERGENCY SWITCHBOARD WILL BE
THROUGH DEDICATED TRENCHES FOR
GENERATOR 1 AND GENERATOR 2 TO AVOID
COMMON MODE FAILURE.
C. THE CABLE TRENCH ROUTES WILL BE
FINALISED IN THE DESIGN STAGE.
D. GENERATOR YARD
AND THE FUEL OIL
Container
TANK WILL BE FENCED, THE DETAIL OF
WHICH WILL BE PROVIDED IN THE DESIGN
STAGE
3900
3000
3000
6000
Day tank will be at the
rear end of the
generator, front end
will be Control panel
and terminals.
3500
3000
3000
2100
Move away from the
road. To here.
Oil truck
2000
Download