How should grout be specified? As it relates to specifying grout for masonry, the MIM recommends the following: • • • • Grout shall be specified in conformance with ASTM C476. Conventional grout should be specified by proportions instead of by strength requirements. The minimum specified compressive strength of grout (f’g) shall be 2,000 psi (13.79 MPa), unless the structural design assumptions require a higher specified compressive strength of clay masonry or concrete masonry (f’m). In that case, the grout compressive strength shall equal or exceed f’m. Compressive strength shall be tested in accordance with ASTM C1019, when required. Fine or coarse grout are permitted, though the MIM recommends specifying coarse unless there is a known issue with grout space or clear cover due to reinforcement congestion or unit size. Coarse grout is the most common in the Michigan market and is generally less expensive on a unit basis. If conventional grout is specified by proportions, which the MIM recommends, then compressive strength testing of grout specimens is not required during construction unless the design requires an f’m of greater than 2,000 psi (13.79 MPa). TMS 602 Table 4, Minimum Special Inspections, requires periodic verification of the proportions of siteprepared grout for Level 2 and Level 3 Quality Assurance. TMS 402 (2016) Requirements TMS 402 Section 6.1.3.5 states that, “Reinforcement embedded in grout shall have a thickness of grout shall have thickness of grout between the reinforcement and masonry units of not less than 1/4 in. (6.4 mm) for fine grout of 1/2 in. (12.7 mm) for coarse grout.” For Strength Design of Masonry, TMS 402 Section 9.1.9.1.2 Grout compressive strength states, “For concrete masonry, the specified compressive strength of grout, f’g, shall equal or exceed the specified compressive strength of masonry, f’m, but shall not exceed 5,000 psi (34.47MPa). For clay masonry the specified compressive strength of grout, f’g, shall not exceed 6,000 psi (41.37 MPa).” In the 2022 edition of TMS 402, the grout compressive strength requirements were moved to Section 4.3, and thus apply to masonry designed under both the Allowable Stress Design and Strength Design methodologies. The grout compressive strength requirements are located in Table 4.3.1 of the TMS 402 (2022). TMS 602 (2016) Requirements TMS 602 Article 1.5 B states that the following must be submitted for each grout mix: 1) Mix designs indicating type and proportions of the ingredients according to the proportion requirements of ASTM C476, or 2) Mix designs and grout strength test performed in accordance with ASTM C476, or 3) Compressive strength tests performed in accordance with ASTM C1019, and slump flow and Visual Stability Index (VSI) as determined by ASTM C1611/C1611M. TMS 602 Article 1.6A Testing Agency’s services and duties and Table 4 – Minimum Special Inspection Requirements require that, as masonry construction begins, periodic verification of the proportions of site-prepared grout is required for Level 2 and Level 3 Quality Assurance. TMS 602 Article 2.2 Grout Materials states, 2.2 A. Unless otherwise required, provide grout that conforms to the requirements of ASTM C476. 2.2 B. When f’m exceeds 2,000 psi (13.79 MPa), provide grout compressive strength that equals or exceeds f’m. Determine compressive strength of grout in accordance with ASTM C1019. 2.2 C. Do not use admixtures unless acceptable. Field addition of admixtures is not permitted in self-consolidating grout. TMS 602 Article 3.5 C Grout pour height states, “Do not exceed the maximum grout pour height given in Table 6.” Table 6 – Grout space requirements Grout Type1 Maximum Grout Pour Height, ft (m) Fine Fine Fine Fine Coarse Coarse Coarse Coarse 1 (0.30) 5.33 (1.63) 12.67 (3.86) 24 (7.32) 1 (0.30) 5.33 (1.63) 12.67 (3.86) 24 (7.32) Minimum Clear Width of Grout Space2,3, in. (mm) 3/4 (19.1) 2 (50.8) 2 1/2 (63.5) 3 (76.2) 1 1/2 (38.1) 2 (50.8) 2 1/2 (63.5) 3 (76.2) Minimum Clear Grout Space Dimensions for Grouting Cells of Hollow Units3,4, in. x in. (mm x mm) 1 1/2 x 2 (38.1 x 50.8) 2 x 3 (50.8 x 76.2) 2 1/2 x 3 (63.5 x 76.2) 3 x 3 (76.2 x 76.2) 1 1/2 x 3 (38.1 x 76.2) 2 1/2 x 3 (63.5 x 76.2) 3 x 3 (76.2 x 76.2) 3 x 4 (76.2 x 102) 1 Fine and coarse grouts are defined in ASTM C476 2 For grouting between masonry wythes 3 Minimum clear width of grout space and minimum clear grout space dimensions are the net dimension of the space determined by subtracting masonry protrusions and the diameters of horizontal bars from the as-built cross section of the grout space. Select the grout type and maximum grout pour height based on the minimum clear space. 4 Minimum grout space dimension for AAC masonry units shall be 3 in. (76.2 mm) x 3 in. (76.2 mm) or a 3 in. (76.2 mm) diameter cell. As noted in Footnotes 2 and 3, the minimum width of grout space is used when the grout is placed in collar joints, where the minimum cell dimensions are used when grouting cells of hollow masonry units, including consideration of vertical alignment of the cells. The grout space dimensions are smallest clear dimensions, considering projections or obstructions into the grout space and the diameter of horizontal reinforcement. This is illustrated in TMS 402 (2016) Figure CC-3.2.1, which has been copied below for reference: ASTM C476 Requirements ASTM C476 covers two types of grout, fine and coarse grout, for use in the construction of masonry structures. Conventional grout is specified by (1) proportions or (2) strength requirements. Section 4 Grout Type and Proportions states: 4.1 Type – Grout type shall be specified as fine or coarse. 4.1.1 Fine grout shall be manufactured with fine aggregates. 4.1.2 Coarse grout shall be manufactured with a combination of coarse and fine aggregates. Note: Building code provisions and grout space dimensions should be reviewed when selecting grout type or types. 4.2 Proportions of Ingredients – Proportions shall be determined as follows: 4.2.1 Conventional Grout – Proportions shall be determined by one of the following methods: 4.2.1.1 Requirements of Table 1. 4.2.1.2 Specified Compressive Strength – Proportions established by 28-day compressive strength tests in accordance with Test Method C1019 that equal or exceed the specified compressive strength. The grout shall be mixed to a slump of 8 to 11 in. (200 to 280 mm) as determined by Test Method C143/C143M and shall have a minimum compressive strength of 2000 psi (14 MPa) at 28 days. Table 1 Conventional Grout Proportions by Volume Type Parts by Volume of Cement Parts by Volume of Hydrated Lime or Lime Putty Fine Grout 1 0 – 1/10 Coarse Grout 1 0 – 1/10 Aggregate, Measured in a Damp, Loose Condition Fine 2 1/4 to 3 times the sum of the volumes of the cementitious materials 2 1/4 to 3 times the sum of the volumes of the cementitious materials Coarse 1 to 2 times the sum of the volumes of the cementitious materials Resources: Society, The Masonry (2016). TMS 402/602 Building Code Requirements and Specification for Masonry Structures, 2016. The Masonry Society. ASTM Standard C476, “Standard Specification for Grout for Masonry,” ASTM International, West Conshohocken, PA, 2020.